Unit Specifications
The following table provides electrical and refrigeration specifications for the TM061 & TM081 Series
Air Conditioners.
TM061 Series
Nominal Capacity Rating: 6,000 BTUH
Standard Maximum Ambient: 131°F
Unit Weight: 111 lbs. (115/230VAC) / 154 lbs. (460VAC)
Model
Operating
Voltage
Range
(Volts)
Inrush
Current
(Start
Up
Current)
(Amps)
Loading
Current
(Running
Current)
(Amps)
SCCR
(Short
Circuit
Current
Rating)
(Amps)
Recommended
Fuse Selection
(Amps)
KVA Rating
(K-Watts)
Refrigerant
Type
Refrigerant
Amount
(ounces)
Low/High
Unit
Pressures
(psi)
TM061126
99-121
35.7
10.6
*2
20 Amp Class
CC, CCMR
Time Delay *
1.3
R438a
24
120 / 320
TM061236
207-253
22.7
6.0
*2
10 Amp Class
CC, CCMR
Time Delay *
1.4
R438a
24
230 / 344
TM061486
414-506
11.35
3.0
*2
5 Amp Class
CC, CCMR
Time Delay *
1.4
R438a
24
188 / 335
* HACR Type Circuit Breakers or Time-delay Fuses with the following electrical characteristics are
recommended. Fast-acting fuses are not recommended.
% of Ampere Rating
Opening Time
110 %
15min Minimum
125 %
1hr Maximum
200 %
12sec Minimum
4min Maximum
*2
SCCR rating is based on the SCCR rating for the circuit protection device installed in the panel /
enclosure per UL50 & UL508a to protect the AC unit. Typically 100KA – 200KA for Time-Delay Fuses.