Moving the Air Conditioners 
 

Read this section completely before running or installing your Thermal Edge air conditioning 
equipment.   
 

Note:

 You will need to perform a Preliminary Test before mounting the air conditioner.  Refer to the 

Preliminary Test section in this manual for instructions on how to run this test.  You will also need to 
prepare the enclosure that is to be cooled for mounting in accordance with this manual and the 
template supplied. 
 

Note:

 Thermal Edge top mount air conditioning equipment must be mounted on a horizontal surface 

with a 

minimum of 3

 air space for condenser air return and supply.  If necessary, equipment may be 

mounted on a surface with up to a 5 degree slope. 
 
If air conditioner is to be shipped or transported at any time; pack in original packaging and strap to 
pallet to prevent damage.  Air conditioner must be kept upright at all times.  Air conditioners are not 
designed to be shipped attached to an equipment enclosure.  Air conditioners shipped which have 
internal damage due to shipping while attached to enclosures are warranty voided. 

 

Unit Label 
 

Each air conditioner has a unit label, be sure to record the data from the label to the template below 
and keep this information in a safe place for warranty and ordering parts.   To prevent damage to 
equipment, electrical panel and wiring, and to prevent personal injury, assure that the power source is 
compatible with the equipment before operating.  When recharging, refrigeration type and amount 
must be the same as shown on the unit label or air conditioner will not operate properly or may be 
damaged and may result in the warranty voided and UL listing voided. 
 

Voltage:_________________   Frequency:__________Hz

Phase:__________

Current Rating (A):

Cooling:___________ 

Heat:___________

Max Fuse:____________

 

Min.  Circuit Ampacity:________

Refrigerant:______________   Ounces:_______________
Design Pressure: 

High Side PSI:__________ Low Side PSI:__________

NEMA Type:______

IP:______

Model:________________________________________
S/N:__________________________________________

 

 
Operation 
 

Thermal Edge air conditioners will lower (or increase as necessary) the temperature inside an 
enclosure to ensure its proper operational temperature.  Our air conditioners, when sized properly, will 
provide cooling or heating automatically controlled by the temperature digital controller.  
 
Thermal Edge air conditioners operate as a “closed loop” system with no exposure or introduction of 
outside air.  This ensures that the enclosure is separated from and is not contaminated with ambient 
air, dirt, chemicals, dust, moisture or foreign matter so that sensitive enclosure components are 
protected and are kept at your required operational temperature. 
 

Содержание TM061 Series

Страница 1: ...User Technical Manual TM061 TM081 Series Rev 1 7...

Страница 2: ...le delay updated Remote Controller option description 1 6 10 01 18 B Slotnick Updated warranty unit specifications 1 7 10 02 18 B Slotnick Updated mounting instructions added sealed enclosure warning...

Страница 3: ...Moving the Air Conditioner 5 Unit Label 5 Operation 6 Preliminary Testing 6 Mounting the Air Conditioner 7 Unit Specifications 8 Options 10 System Faults 13 Digital Temperature Controller Programming...

Страница 4: ...cting the Equipment Thermal Edge air conditioning equipment is designed manufactured and packed to prevent damage from normal handling shock and vibration during shipment It is necessary to inspect yo...

Страница 5: ...he template below and keep this information in a safe place for warranty and ordering parts To prevent damage to equipment electrical panel and wiring and to prevent personal injury assure that the po...

Страница 6: ...r conditioner is the proper voltage and phase Check the electric power source for proper ground wire and neutral wire installation per 2008 NEC Assure that the electric power is protected by a circuit...

Страница 7: ...closure roof Be careful not to damage the gasket on the bottom of the air conditioner by trapping tools or objects between the air conditioner and the enclosure From inside the enclosure install the p...

Страница 8: ...ded Fuse Selection Amps KVA Rating K Watts Refrigerant Type Refrigerant Amount ounces Low High Unit Pressures psi TM061126 99 121 35 7 10 6 2 20 Amp Class CC CCMR Time Delay 1 3 R438a 24 120 320 TM061...

Страница 9: ...ses are not recommended of Ampere Rating Opening Time 110 15min Minimum 125 1hr Maximum 200 12sec Minimum 4min Maximum 2 SCCR rating is based on the SCCR rating for the circuit protection device insta...

Страница 10: ...s Note C Level Protection is strongly recommended for 4X applications requiring 316 stainless steel Low Ambient This option consists of circuitry to protect the compressor in a low ambient temperature...

Страница 11: ...r Available Heater capacities range from 100 Watts to 950 Watts Default Settings 55 F Heat Set Point 3 F Differential At the default settings the heater output turns on at 52 F and operates until the...

Страница 12: ...control all settings from a remote location with an applicable Allen Bradley Rockwell PLC A DIN rail is required inside the electrical enclosure for mounting the communication components Full specifi...

Страница 13: ...time delay A thermal overload protects the compressor against faults In the event that the snowflake status LED is not flashing on the display and the compressor is not running an internal fault may...

Страница 14: ...value 4 Use the UP or DOWN arrow key to change its value 5 Press SET to store the new value and move to the following parameter To exit Press SET UP arrow keys or wait 15 seconds without pressing a k...

Страница 15: ...45 F for 3 minutes after initial 30 min start up delay No Output 2 HA2 Condenser High Temperature Alarm P2 145 F for 3 minutes Compressor Off 2 LA2 Condenser Low Temperature Alarm P2 50 F for 3 minute...

Страница 16: ...life of the Air Conditioner Air Filter Service If the air conditioner is equipped with an optional condenser filter remove the filter and wash if washable or replace if not washable Dry thoroughly be...

Страница 17: ...VAC Compressor Thermal Overload TM061 31552 2 for 120VAC 31574 2 for 230VAC 480VAC TM081 31020 2 for 120VAC 31080 2 for 230VAC 480VAC Gasket Installation Kit 71318 TM68 Evaporator Fan 42100 1 1 for 12...

Страница 18: ...s on position ON OFF Toggle Switch then Retry Verify input power meets voltage requirements as shown in the UL label YES If problem is still present contact technical support Unit Overheats Insufficie...

Страница 19: ...sor Use meter 3 Check for faulty evaporator fan 3 Measure Temperature at Evaporator Verify Heat Load Requirements Is unit capacity adequate for internal head load Possible low refrigerant Is compresso...

Страница 20: ...ind controller CA YES NO Check Low Pressure Switch Connections and Verify Pressure switch is closed Use meter 3 P1 or P2 NO YES Check probe connections potential faulty probe LA LA2 HA HA2 YES Refer t...

Страница 21: ...g e Physical Dimensions Water overflow excessive Check drain is it plugged YES NO Clean condensate pan and drain add 1 tbsp bleach to upper pan monthly to kill mold Is Air Conditioner sealed against...

Страница 22: ...al edge com SP ENG 211 000 17 Rev 1 7 22 P a g e Electrical Schematics System Schematic Digital Controller Schematic Note Schematics apply to all voltages optional accessories wiring not provided in t...

Страница 23: ...dge factory in Dallas Texas Use of equipment for other than its designed purpose or operating conditions Operation in harsh oily corrosive or other abnormal environmental conditions without the proper...

Страница 24: ...Number Serial Number Customer name and contact info email phone number and address Shipping method Pack unit in a suitable packing for shipment preferably the original packaging if available Air Condi...

Страница 25: ...sembly channels facing UP 4 Starting from the left connect the wires by inserting them into the lower receptacles located on the front of connector in the following order NOTE If using stranded wires...

Отзывы: