background image

 

Chillers with an integral water-cooled or air-cooled 
condenser ship with a full refrigerant charge. Chillers 
designed for use with a remote air-cooled condenser 
and the remote condensers themselves ship with a 
nitrogen holding charge. Check the remote 
condenser for signs of leaks prior to rigging. This will 
ensure no coil damage has occurred after the unit 
left the factory. The condenser ships with the legs 
removed. Mount the legs to the condenser using the 
provided nuts, bolts, and washers. 
 

Unit Storage 

If the chiller is stored prior to installation, it is 
important to protect it from damage. Blow out any 
water from the evaporator and water-cooled 
condenser circuits to protect the unit from damage 
from freezing. Close any open refrigerant valves. 
Cover the equipment to keep dirt and debris from 
accumulating on it. Units charged with refrigerant 
should not be stored in areas warmer than 145°F. 
 

Installation - Chiller 

Foundation 

Install the chiller on a rigid, non-warping mounting 
pad, concrete foundation, or level floor suitable to 
support the full operating weight of the equipment. 
When installed the equipment must be level within 
¼ inch over its length and width. 
 

Unit Location 

The chiller is available in many different 
configurations for various environments. Refer to the 
proposal and order acknowledgement document for 
the equipment to verify the specific design 
conditions in which it can operate. 
 
Allow a minimum of 48 inches of clearance between 
the chiller and any walls or obstructions. For 
installations with multiple chillers, allow a minimum 
of 96 inches between chillers placed side-by-side or 
48 inches for chillers placed end-to-end. 
 
When locating the chiller it is important to consider 
accessibility to the components to allow for proper 
maintenance and servicing of the unit. In general, 
allow a minimum of 36 inches of clearance around 
and above the unit. Avoid locating piping or conduit 
over the unit to ensure easy access with an overhead 
crane or lift to lift out heavier components during 
replacement or service. 

Proper ventilation is another important 
consideration when locating the chiller. In general, 
locate the unit in an area that will not rise above 
110°F. In addition, ensure the condenser and 
evaporator refrigerant pressure relief valves can vent 
in accordance with all local and national codes. 
 
Chillers with an integral air-cooled condenser require 
a minimum of 36 inches of clearance at both the 
condenser air inlet and condenser air discharge, they 
are not, as standard, designed to have the condenser 
air discharge ducted. Improper clearance or poor 
ventilation will reduce the cooling capacity of the 
chiller and may cause high refrigerant pressure 
problems. In order to avoid possible low refrigerant 
pressure safety trips during start-up, maintain the 
inlet air temperature above 50°F. If outside air is 
ducted into an indoor chiller with an integral air-
cooled condenser, there is an option for low ambient 
heat pressure controls which allow for incoming air 
temperatures down to 0°F. Cooler temperatures than 
this require custom modifications. 
 

Rigging 

The chiller has a frame to facilitate easy movement 
and positioning with a crane or forklift. Follow 
proper rigging methods to prevent damage to 
components. Avoid impact loading caused by 
sudden jerking when lifting or lowering the chiller. 
Use pads where abrasive surface contact may occur. 
 

Chilled Process Fluid Piping 

Proper insulation of chilled process fluid piping is 
crucial to prevent condensation. The formation of 
condensation adds a substantial heat load to the 
chiller. 
 
The importance of properly sized piping between 
the chiller and process cannot be overemphasized. 
See the ASHRAE Handbook or other suitable design 
guide for proper pipe sizing. In general, run full size 
piping out to the process and reduce pipe size at 
connections as needed. One of the most common 
causes of unsatisfactory chiller performance is poor 
piping system design. Avoid long lengths of hoses, 
quick disconnect fittings, and manifolds wherever 
possible as they offer high resistance to water flow. 
When manifolds are required, install them as close to 
the use point as possible. Provide flow-balancing 
valves at each machine to assure adequate water 
distribution in the entire system. Typically, when 

Содержание Accuchiller EQ Series

Страница 1: ...Installation Operation Manual EQ Series Portable and Remote Condenser Chillers ...

Страница 2: ...Page Intentionally Blank ...

Страница 3: ... Refrigerant and Oil Charge 8 Oil Charge Determination 8 Setting Condenser Fan Controls 8 Installation Electrical 9 Standard Controller Operation 10 Changing Temperature Display Scale 10 Diagnostic Error Codes 12 SPI Communications Option 13 Start Up 15 Step 1 Connect Main Power 15 Step 2 Fill Coolant Circuit 15 Step 3 Check Condenser 16 Step 4 Check Refrigerant Valves 17 Step 5 Verify Freezestat ...

Страница 4: ...Page Intentionally Blank ...

Страница 5: ...s a hydro fluorocarbon HFC trade named R 407c as a chemical refrigerant for heat transfer purposes This chemical is sealed and tested in a pressurized system containing ASME coded vessels however a system failure will release it Refrigerant gas can cause toxic fumes if exposed to fire Place these units in a well ventilated area especially if open flames are present Failure to follow these instruct...

Страница 6: ...taining or repairing the equipment to protect against any sparks debris or fluid leaks Pre Installation Receiving Inspection When the unit arrives verify the information on the unit nameplate agrees with the order acknowledgement and shipping papers Inspect the equipment for any visible damage and verify all items shown on the bill of lading are present If damage is evident document it on the deli...

Страница 7: ...vice Proper ventilation is another important consideration when locating the chiller In general locate the unit in an area that will not rise above 110 F In addition ensure the condenser and evaporator refrigerant pressure relief valves can vent in accordance with all local and national codes Chillers with an integral air cooled condenser require a minimum of 36 inches of clearance at both the con...

Страница 8: ...geration pressures in the circuit To prevent damage to the condenser and or water regulating valve the water pressure should not exceed 150 psig Installation Remote Air Cooled Condenser Chillers designed for use with a remote air cooled condenser include a factory selected remote condenser The remote air cooled condenser typically ships separately from a different location than the chiller Locatio...

Страница 9: ...ing size and piping design have a significant impact on system performance and reliability All piping should conform to the applicable local and state codes CAUTION Use refrigerant grade copper tubing ASTM B280 only and isolate the refrigeration lines from building structures to prevent transfer of vibration All copper tubing must have a pressure rating suitable for R 407c tubing that is OD or lar...

Страница 10: ... at the condenser immediately drop at least 15 inches down from the liquid outlet before routing the piping to the chiller Make the drop leg before any bends or angles connecting to the remainder of the liquid connection piping Figure 3 Condenser Located at Chiller Level Figure 4 Condenser Located Above Chiller Unit Figure 5 Condenser Located Below Chiller Unit Caution Liquid line sizing for each ...

Страница 11: ...immediate drop of at least 15 inches at the condenser outlets to make a liquid seal Liquid line risers in the system will require an additional 0 5 psig pressure drop per foot of vertical rise When it is necessary to have a liquid line riser make the vertical run immediately after the condenser before any additional restrictions The liquid line risers must not exceed 10 feet in height from the con...

Страница 12: ...25 250 275 300 A A A A A A A A A A A A B B B B B B B B B B B B Calculating Refrigerant and Oil Charge To determine the approximate charge assume a combined chiller and remote condenser summer refrigerant charge of 4 6 Lbs of R 407c then refer to Table 5 to determine the charge required for the field installed piping per circuit The approximate charge per circuit is therefore the sum 4 6 and the va...

Страница 13: ...ter If the meter reads CBA open the main power disconnect and switch two line leads on the line power terminal blocks or the unit mounted disconnect Do not interchange any load leads that are from the unit contactors or the motor terminals WARNING This equipment contains hazardous voltages that can cause severe injury or death WARNING This equipment contains refrigerant under pressure Accidental r...

Страница 14: ...de If C is displayed the temperature display is in C mode To change from F to C press the Lower Set Point Temperature button down arrow To change from C to F press the Raise Set Point Temperature button up arrow After changing to the desired temperature scale the Set Point display shows the desired display units Press and release the Start button to store the new selection into the controller memo...

Страница 15: ...ssure is less than the setting of the high refrigerant pressure safety Low Refrig The Low Refrigerant Pressure light is red when the compressor suction pressure drops below the setting on the low refrigerant pressure safety This safety stops all compressors but allows pumps to continue running Pressing the Alarm Reset button resets the fault if the compressor suction pressure is above the setting ...

Страница 16: ...2 A D Converter Failure Controller requires servicing Contact Manufacturer for repair or replacement 103 Controller serial bus failure Controller requires servicing Contact Manufacturer for repair or replacement 105 CJC Error Controller requires servicing Contact Manufacturer for repair or replacement 109 Unused memory byte changed Controller requires servicing Contact Manufacturer for repair or r...

Страница 17: ...pt the Serial Peripheral Interface bus SPI bus which coincidently has the same abbreviation as the trade association To allow our unit to operate as a slave unit in a plastic processing system using this protocol we offer an option that includes an expansion module for the control board and a RS 485 communication port on the unit The communication hardware firmware is SPI 3 01 standard compliant U...

Страница 18: ...as occurred high or low temperature deviation 3 An alarm affecting the machine has occurred probe fault or pump fault 4 The controller has exceeded its over setpoint deviation 5 The controller has exceeded its below setpoint deviation Status Machine 1 20 42 This is the machine status in a 16 bit format as follows 0 Controlling 1 An alarm is present 2 An alarm affecting the process has occurred hig...

Страница 19: ... the compressor s crankcase heater Disconnect main power only when servicing the chiller The crankcase heater should remain on when the compressor is off to ensure liquid refrigerant does not accumulate in the compressor crankcase Connect main power at least 24 hours prior to initial start up Step 1 Connect Main Power Connect main power properly ensuring it matches the voltage shown on the namepla...

Страница 20: ... Water Chemistry Requirements Water Characteristic Quality Limitation Alkalinity HCO3 70 300 ppm Aluminum Al Less than 0 2 ppm Ammonium NH3 Less than 2 ppm Chlorides Cl Less than 300 ppm Electrical Conductivity 10 500µS cm Free aggressive Carbon Dioxide CO2 Less than 5 ppm Free Chlorine Cl2 Less than 1 PPM HCO3 SO4 2 Greater than 1 0 Hydrogen Sulfide H2S Less than 0 05 ppm Iron Fe Less than 0 2 pp...

Страница 21: ...l that the Freezestat is set properly Step 6 Turn On Control Power Some chillers may have a control power switch If present turn the control power switch on If not present turning the main power on should turn the control power on When the control power is on the panel displays are illuminated Due to extreme ambient temperatures that may occur during shipment the High Refrigerant Pressure switch m...

Страница 22: ...ly more than pay for it The preventative maintenance checklist in this manual is a great way to log and keep track of maintenance Once a Week 1 Air Cooled Units Only Check the surface of the air cooled condenser coil for dirt and debris To clean rinse thoroughly with water and use a mild detergent to remove smoke and or grease stains 2 Check to make sure that the To Process temperature is reasonab...

Страница 23: ...erature Control Pump Discharge Pressure Coolant Level Glycol Concentration Pump Seal Refrigerant Sight Glass Electrical Connections Incoming Voltage Compressor 1 L1 Amps Compressor 1 L2 Amps Compressor 1 L3 Amps Pump L1 Amps Pump L2 Amps Pump L3 Amps Fan 1 L1 Amps Fan 1 L1 Amps Fan 1 L3 Amps Clean Y Strainer Refrigerant Circuit Check Refrigerant Suction Pressure Refrigerant Discharge Pressure Refr...

Страница 24: ...t refrigeration service technician High refrigerant pressure sensor Replace if faulty Freezestat Low flow through evaporator Adjust flow to proper level Freezestat control module Check for proper setting Protected Setting Freezestat sensor Replace if faulty Low pump discharge pressure Pump running backwards Switch 2 legs of the incoming power Pump pressure gauge Replace if faulty Pump failure Repl...

Страница 25: ...e equipment and or system has been subject to misuse negligence or operation in excess of recommended limits including freezing or has been altered and or repaired without express factory authorization If equipment is installed in hostile environments unless such conditions were specified at the time of purchase or the serial number has been removed or defaced this warranty shall not apply All lab...

Страница 26: ...ponsible for any sales use excise or other applicable taxes associated with the replacement of parts under this warranty This warranty will be voided when in Thermal Care s opinion the equipment and or system has been subject to misuse negligence or operation in excess of recommended limits including freezing or has been altered and or repaired without express factory authorization This warranty s...

Страница 27: ...Notes ...

Страница 28: ...W Jarvis Ave Phone 847 966 2260 Phone 847 966 2636 Phone 847 966 8560 Niles IL 60714 3491 Fax 847 966 9358 Fax 847 966 2906 Fax 847 966 6065 www thermalcare com info thermalcare com service thermalcare com tcparts thermalcare com EQ Series IOM 2 313 25 December 2016 ...

Отзывы: