background image

5.  Remove fan/bracket assembly by removing 3 screws from 

the bracket and inlet ring assembly. 

6.  Remove the defective impeller fan from the bracket and 

replace with it with the new impeller fan. 

7.  Reassemble the new impeller fan by reversing the above 

procedure. Note: There are two pins on the backside of the 
cabinet that must align with the two holes in the impeller fan 
support bracket. 

7.6 Compressor/Capacitor Replacement 

This compressor is equipped with a two terminal external overload 
and a run capacitor, but no start capacitor or relay (See Figure 4). 

7.6A Checking Compressor Motor Circuits 

Perform the following tests if the impeller fan runs but the 
compressor does not with the fan switch and ventilation timer OFF 
and the humidity control ON. 

1.  Unplug the unit; remove the cabinet side and the electrical 

connection cover on the compressor top. 

2.  Plug in the unit and turn the humidity control to ON. Check for 

110 volts from compressor terminal R to overload terminal 
3 using an AC voltmeter. If voltage is present, go to step 
3. If no voltage, there may be a loose connection in the 
compressor circuit. Test each component for continuity. See 
the appropriate section if a defect is suspected. 

3.  Unplug the unit, and then disconnect the red and yellow wires 

from compressor terminals R & S. Using an ohmmeter check 
continuity between the points listed below. 

4.  Compressor terminals C and S: No continuity indicates an 

open start winding. The compressor must be replaced. 
Normal start winding resistance is 3 to 7 ohms. 

5.  Compressor terminals C and R: No continuity indicates an 

open run winding. The compressor must be replaced. Normal 
run winding resistance is .5 to 2 ohms. 

6.  Compressor terminal C and overload terminal 1: No continuity 

indicates a defective overload lead. 

7.  Overload terminals 1 and 3: If there is no continuity, the 

overload may be tripped. Wait 10 minutes and try again. 
If there is still no continuity, it is defective and must be 
replaced. 

8.  Compressor terminal C and compressor case: Continuity 

indicates a grounded motor. The compressor must be 
replaced. 

9.  Disconnect the wires from the run capacitor. Set the 

ohmmeter to the Rx1 scale. The capacitor is shorted and 
must be replaced if continuity exists across its terminals. 
If there is no needle movement with the meter set on the 
Rx100000 scale, the capacitor is open and must be replaced. 

10.  Reconnect the wires to the compressor and capacitor. Plug 

in and turn on the unit. If the compressor fails to start, 

replace the run capacitor. 

11.  If the unit still does not start, adding a hard-start kit (relay & 

capacitor) will provide greater starting torque. If this doesn't 
work, the compressor has an internal mechanical defect and 
must be replaced. 

7.6B Replacing a Burned Out Compressor 

The refrigerant and oil mixture in a compressor is chemically 
very stable under normal operating conditions. However, when an 
electrical short occurs in the compressor motor, the resulting high 
temperature arc causes a portion of the refrigerant oil mixture to 
break down into carbonaceous sludge, a very corrosive acid, and 
water. These contaminants must be carefully removed otherwise 
even small residues will attack replacement compressor motors 
and cause failures. 

The following procedure is effective only if the system is monitored 
after replacing the compressor to insure that the clean up was 
complete. 

1.  This procedure assumes that the previously listed compressor 

motor circuit tests revealed a shorted or open winding. 

2.  Remove and properly dispose of the system charge. DO NOT 

vent the refrigerant or allow it to contact your eyes or skin. 

3.  Remove the burned out compressor. Use rubber gloves if 

there is any possibility of contacting the oil or sludge. 

4.  To facilitate subsequent steps, determine the type of burn 

out that occurred. If the discharge line shows no evidence 
of sludge and the suction line is also clean or perhaps has 
some light carbon deposits, the burn out occurred while the 
compressor was not rotating. Contaminants are therefore 
largely confined to the compressor housing. A single 
installation of liquid and suction line filter/driers will probably 
clean up the system. 

If sludge is evident in the discharge line, it will likely be found in the 
suction line. This indicates the compressor burned out will running. 
Sludge and acid have been pumped throughout the system. Several 
changes of the liquid and suction filter/driers will probably be 
necessary to cleanse the system. 

5.  Correct the system fault that caused the burn out. Consult the 

factory for advice. 

6.  Install the replacement compressor with a new capacitor and 

an oversized liquid line filter. 

In a running burn out, install an oversized suction line filter/drier 
between the accumulator and compressor. Thoroughly flush the 
accumulator with refrigerant to remove all trapped sludge and to 
prevent the oil hole from becoming plugged. A standing burn out 
does not require a suction line filter/drier. 

FOR HVAC INSTALLER ONLY

14

Ultra-Aire XT150H Installer’s & Owner’s Manual

Содержание Ultra-Aire XT150H

Страница 1: ...tdoor air may be ducted to the unit via a six inch round duct This provides fresh air to dilute pollutants and maintain high oxygen content in the air The amount of fresh air ventilation can be regula...

Страница 2: ...igital Control WITHOUT Fresh Air 9 4 2 Humidity Control Adjustment 8 4 3 Fan Filter Switch 8 4 4 Ventilation Timer 8 4 4A Setting the Time 9 4 4B Ventilation Schedule 9 4 4C Automatic or Manual Mode 9...

Страница 3: ...th space to access the back or side panels for maintenance and service DO NOT INSTALL UNIT WITH THE SERVICE PANELS INACCESSIBLE Avoid directing the discharge air at people or over the water in pool ar...

Страница 4: ...l vibration and or noise A drain pan MUST be placed under the unit if installed above a living area or above an area where water leakage could cause damage Place the Ultra Aire XT150H on supports that...

Страница 5: ...ating system can be used to supply air to the home If the existing supply goes to isolated areas of the home discharge the supply of the Ultra Aire XT150H into the supply of the existing heating syste...

Страница 6: ...lter enclosure of the unit The 6 round collar includes a manual damper Adjust the manual damper to provide the desired amount of fresh air for ventilation The amount of fresh air should be based on th...

Страница 7: ...edrooms den etc By ducting this way the air inside the structure will circulate through the Ultra Aire XT150H to be filtered and dehumidified Avoid discharging all the air from the dehumidifier in one...

Страница 8: ...ir Refer to Section 5 4 2 Humidity Control Adjustment Set the humidity control to the desired humidity level for the home Turning the knob clockwise results in a drier setting See the back of the cont...

Страница 9: ...the week for this program You can choose Mon Sun Mon Fri Sat Sun or any single day of the week The days chosen are shown along the top of the display on the ventilation timer Next press the h button...

Страница 10: ...e lead from the unit or damage to the transformers will result Do not direct connect the white lead on the unit to the violet lead on the ventilation control or damage to the transformer will result H...

Страница 11: ...ty Range Accuracy 10 95 RH 5 Auxillary Relay Capacity 5 Amps 24VAC Temp Range Accuracy 30 90 F 2 Size 4 95 L x 1 06 W x 4 19 H Major Operations n Digital control of Relative Humidity Digital Set Point...

Страница 12: ...heck and clean the screen on the outdoor fresh air return seasonally The screen may become plugged during the seasons when there are many particles in the outdoor air 7 Service 7 1 Warranty A warranty...

Страница 13: ...uch as expected 1 Air temperature and or humidity have dropped 2 Humidity meter and or thermometer used are out of calibration 3 Unit has entered defrost cycle Sec 5 8 4 Air filter dirty Sec 4 1 4 2 5...

Страница 14: ...capacitor Plug in and turn on the unit If the compressor fails to start replace the run capacitor 11 If the unit still does not start adding a hard start kit relay capacitor will provide greater start...

Страница 15: ...and bring in fresh air from outside The ventilation timer should be set for the required ventilation of the residence The home should be ventilated with fresh air as suggested by applicable codes and...

Страница 16: ...Aire XT150H to the blue 5 lead on the control panel If the pump fails this switch opens the compressor control circuit and stops water production before the reservoir overflows The Ultra Aire XT150H...

Страница 17: ...FOR HVAC INSTALLER ONLY 17 Pictorial Electrical Diagrams of Ultra Aire XT150H Ultra Aire XT150H Installer s Owner s Manual...

Страница 18: ...t No Qty Description 12 4026687 1 45mFd CAPACITOR COMPRESSOR 13 4022487 1 TRANSFORMER 14 4022484 1 RELAY COMPRESSOR 15 4017021 1 15mFd CAPACITOR IMPELLER 16 4026932 1 COLLAR 10 INCH 17 4026947 1 COLLA...

Страница 19: ...Electrically Actuated not shown 32 4024153 1 Cover for Items 28 29 not shown 33 4021495 1 Knob Black 25 shaft 34 4024150 1 Instructions Humidity Fan not shown 35 4024122 1 Instructions Ventilation Ti...

Страница 20: ...ng door shut Once the door is shut release the door latch Collar Install Remove the 2 round ducts 3 seals and small bag of mounting hardware from inside the rectangle opening Adhere seals onto the bac...

Страница 21: ...costs related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsib...

Страница 22: ...any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2007 Therma Stor LLC All rights reserved PO Box 8680 Madison WI 53708 Phone...

Отзывы: