3.8 Damper Operation and Ventilation,  
Manual (Hold) Mode

The 

“VENT”

 setting controls the ventilation function of the 

system. It has no control over the dehumidification function. In 
order to provide ventilation, the motorized damper must be open 
and the fan must be running. The controller takes care of these 
two functions automatically so that whenever the damper is 
open, the fan is running.

The ventilation indicator 

“O”

 will be displayed whenever the 

unit is ventilating. The fan operation indicator 

“O”

 will also be lit.

There are three damper operation modes:

1.  

“OPEN”

 – hold mode: The damper will be open and the 

dehumidifier fan will be continuously operating to introduce 
fresh air into the space. Use this mode for continuous fresh 
air ventilation. The fan is always on when the damper is open.

2.  

“CLOSED”

 – hold mode: The damper will never open, and 

the dehumidifier will not ventilate. The fan will still operate 
normally for recirculation and dehumidification.

3.  

“PROGRAMMED”

 mode: The DEH 3000R will operate the 

motorized damper and the dehumidifier fan according to the 
programmed ventilation schedule (Section 3.9). 

The factory preset for the 

“VENT”

 setting is 

“CLOSED”

.

To set “OPEN” – hold or “CLOSED” – hold ventilation 
operation:

1.  Press the 

“VENT”

 button. The current setting will begin to 

flash on the display. Release the button.

2.  Press the

 “VENT”

 button again to switch between

 “OPEN” 

and 

“CLOSED”

.

3.  Leave the control alone for 10 seconds and your settings will 

be saved.

3.9 Damper Operation and Ventilation, 
Programmed Ventilation

This example shows the system in program mode (denoted by 
the schedule 15 minutes on, 5 minutes off and the word RUN in 
the lower right corner of the display).

The DEH 3000R will operate fresh air ventilation according to 
your ventilation program. The control needs to be programmed 
to turn the ventilation function ON and OFF at the desired 
intervals. This is done by programming the ventilation timer.

There are two programs available for ventilation:

1. Monday through Sunday
2. Monday through Friday & Saturday/Sunday 

Each block of days has a morning schedule and a night 
schedule. Morning is the first 12 hours of the day and night is 
the second 12 hours.

Each schedule has: 

• A 

“START”

 time when the ventilation schedule begins,

•  An 

“OPEN FOR” 

duration for the amount of time the damper 

stays open in 5 minute intervals, from 0 to 60,

•  And 

“CLOSED FOR”

 duration which closes the damper for a 

specified time in 5 minute intervals from 0 to 60. 

Setting the Ventilation Program:

1.  Press the

 “PROGRAM ENTER”

 button until the following 

menu appears:

2.  Using the up/down 

“RH” 

buttons, highlight 

“PROGRAM”

 

and select it by pressing the 

“PROGRAM ENTER” 

button. 

The following menu appears:

8

DEH 3000R Dehumidifier & Ventilation System Controller

 Installation, Operation & Service Manual

Содержание Ultra-Aire DEH 3000R

Страница 1: ...ASE LEAVE MANUAL FOR HOMEOWNER Dehumidifier Ventilation System Controller 2008 Therma Stor LLC Manual P N TS 506b P O Box 8680 Madison WI 53708 TOLL FREE 1 800 533 7533 www thermastor com sales therma...

Страница 2: ...95 RH 5 Auxillary Relay Capacity 5 Amps 24VAC Temp Range Accuracy 30 90 F 2 Size 4 95 L x 1 06 W x 4 19 H 2 Installation Install the DEH 3000R control panel in a central area of the structure where it...

Страница 3: ...e optional motorized damper that can be installed into a fresh air duct This damper provides the ability to control fresh air ventilation using the ventilation timer function of the DEH 3000R and the...

Страница 4: ...C transformer that reads 0 volts between it and the Yellow air conditioning call for cooling wire The incorrect wire will give a 20 to 28 volt reading 2 Another Yellow wire must be added to the thermo...

Страница 5: ...t again to switch the fan to the ON setting c Confirm that the Ultra Aire fan is ON Ultra Aire compressor must be OFF Ventilation damper if used should be CLOSED 6 Verify optional VENT operation if el...

Страница 6: ...A flashing O before the SET POINT VENT OR FAN indicates the unit is in wait mode 3 2 Setting During the set up process if you make a mistake simply continue You can always go back to adjust the settin...

Страница 7: ...an Setting and Operation Use the FAN button to change the fan operation There are 2 choices for fan operation ON or AUTO The factory preset is AUTO ON The fan in the Ultra Aire dehumidifier will run c...

Страница 8: ...he display Release the button 2 Press the VENT button again to switch between OPEN and CLOSED 3 Leave the control alone for 10 seconds and your settings will be saved 3 9 Damper Operation and Ventilat...

Страница 9: ...schedule Repeat the steps listed above for this and the SAT SUN day and night schedules When you have finished programming your schedule either the 7 day version or the weekday weekend split version u...

Страница 10: ...splice connectors provided Avoid routing parallel to high voltage wiring Maintain a distance of 2 ft or more from high voltage lines 2 Sensor connection The sensor can be mounted to a wall or ceiling...

Страница 11: ...ome effective after initial purchase of the Product by Customer Customer Responsibilities As a further condition to obtaining warranty coverage hereunder the Customer must send a valid warranty claim...

Страница 12: ...t to change without notice No part of this document may be reproduced or transmitted in any form or by any means electronic or mechanical for any purpose without the express written permission of Ther...

Отзывы: