Santa Fe ULTRAMD33 Installation & Operation Instructions

Santa-Fe-Products.com | 800.533.7533

Step 12.

 If the drain access cover was removed, 

reinstall it by routing the drain hose through the  

appropriate knock out and reattach the screw.  

Route the grommet over the drain hose and snap 

into place at the knock out.
Use 1

/

4" hex nut screwdriver to apply hose  

clamp to the drain hose and secure onto the  

drain port hose barb.

12.

Step 14.

 Tuck the electrical wires in and reinstall 

electrical cover with its two screws using 1

/

4" hex 

nut screwdriver. Be sure none of the electrical  

wires are pinched.

Step 15.

 Turn breaker / power back on.

Step 16.

 Set the digital controller to desired  

RH. See Controls Section on page 12.

Step 17.

 Install diffuser cover by aligning 

the lower tabs first, then setting the cover 

back against the wall. Insert the included 

four tamper resistant or phillips screws to 

secure the diffuser cover.

DEHUMIDIFIER INSTALLATION

14.

17.

Step 13.

 Complete electrical connections: 

• white to white 
• green to green 
• black to black 
Screw wire nuts back onto each electrical 

connection.
Then tighten clamp screws on non-metallic 

cable clamp.

Power Board

Non-Metallic Cable Clamp

13.

Hose

Hose Clamp

Grommet for

Drain Hose

Make sure drain hose is routed to the appropriate  

location before turning on the unit.

Содержание Santa Fe UltraMD33

Страница 1: ...e UltraMD33 is a built in dehumidification solution that can be conveniently installed inside standard wall framing The Santa Fe UltraMD33 provides the ultimate in Comfort Health Property Protection U...

Страница 2: ...lation 7 Maintenance 11 Air Flow 11 Controls 12 Service 14 Warranty 16 TABLE OF CONTENTS Santa Fe is committed to manufacturing quality products To maintain our standards product specifications may ch...

Страница 3: ...NG SHEET METAL ALL STATE AND NATIONAL ELECTRICAL AND PLUMBING CODES MUST BE ADHERED TO FOR PROPER UNIT OPERATION AND WARRANTY COMPLIANCE IMPROPER INSTALLATION MAY CAUSE PROPERTY DAMAGE OR INJURY INSTA...

Страница 4: ...T NATIONALE ET D TAT DOIVENT TRE RESPECT S POUR UNE UTILISATION AD QUATE DE CETTE UNIT ET UNE VALIDIT DE LA GARANTIE UNE INSTALLATION NON CONFORME PEUT CAUSER DES DOMMAGES MAT RIELS OU DES BLESSURES T...

Страница 5: ...e unit on or inside of an interior wall and with direct connection to building electrical service A 15 Amp circuit must be provided Install the unit in a location that is near a power supply Electrica...

Страница 6: ...0 Hz AC only 15 amp fused and grounded electrical supply A visible circuit breaker or disconnect switch near the unit is required for maintenance and service A dedicated circuit is recommended Use of...

Страница 7: ...ipping Bracket AVERTISSEMENT AVERTISSEMENT FERMEZ LE DISJONCTEUR ALIMENTATION AVANT DE COMMENCER L INSTALLATION Items Included in Box Santa Fe UltraMD33 Dehumidifier Diffuser Cover with Filter Santa F...

Страница 8: ...Step 3 There are three electrical knock outs one on the back and two on the bottom of the unit Remove appropriate knock out and install non metallic cable clamp with clamp screws inside of unit orient...

Страница 9: ...oth sides Additional insulation or sound dampening material not provided may be required if the dehumidifier cabinet contacts the studs especially in applications involving metal studs Fasten the unit...

Страница 10: ...none of the electrical wires are pinched Step 15 Turn breaker power back on Step 16 Set the digital controller to desired RH See Controls Section on page 12 Step 17 Install diffuser cover by aligning...

Страница 11: ...CORD IS DAMAGED IT MUST BE REPLACED BY THE MANUFACTURER ITS SERVICE AGENT OR SIMILARLY QUALIFIED PERSONS IN ORDER TO AVOID A HAZARD AVERTISSEMENT AVERTISSEMENT ASSUREZ VOUS QUE L UNIT EST FERM E OU D...

Страница 12: ...isplay will show 00 for a couple of seconds and then it will display the RH level of the room and the dehumidifier blower will turn on to start sampling the air for one minute Indicator LED located ab...

Страница 13: ...tart after an hour Evaporator Temperature Mode To enter evaporator temperature mode press and hold both arrow buttons for 5 seconds and the LED will change to Blue The display will flash at twice the...

Страница 14: ...ERTISSEMENT RISQUE DE D CHARGE LECTRIQUE UNE ALIMENTATION LECTRIQUE DOIT TRE UTILIS E POUR EFFECTUER CERTAINES V RIFICATIONS CES V RIFICATIONS DOIVENT TRE EFFECTU ES PAR UN PERSONNEL D ENTRETIEN QUALI...

Страница 15: ...d from installation Blower is running and compressor is cycling on and off while ambient humidity is high 1 Unit is defrosting 2 Ambient temperature is too low 3 Defrost sensor malfunction 4 Poor airf...

Страница 16: ...er any costs related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Res...

Страница 17: ...Santa Fe Products com 1 800 533 7533...

Отзывы: