background image

quest

quest

1-866-933-7486 

Quest PowerDry 4000 Pro 

Installation, Operation and Maintenance Instructions  

8

www.QuestProtect.com

[email protected]

4.2 Technical Description

The Quest PowerDry 4000 

Pro

 uses a refrigeration system similar to an air conditioner’s to remove heat and moisture 

from incoming air, and to add heat to the air that is discharged (see Fig. 2).

Hot, high pressure refrigerant gas is routed from the compressor to the condenser coil (see Figure 2). The refrigerant 
is cooled and condensed by giving up its heat to the air that is about to be discharged from the unit. The refrigerant 
liquid then passes through a filter/drier and capillary tubing which cause the refrigerant pressure and temperature to 
drop. It next enters the evaporator coil where it absorbs heat from the incoming air and evaporates.

The evaporator operates in a flooded condition, which means that all the evaporator tubes contain liquid refrigerant 
during normal operation. A flooded evaporator should maintain constant pressure and temperature across the entire 
coil, from inlet to outlet.

The mixture of gas and liquid refrigerant enter the accumulator after leaving the evaporator coil. The accumulator 
prevents any liquid refrigerant from reaching the compressor. The compressor evacuates the cool refrigerant gas from 
the accumulator and compresses it to a high pressure and temperature to repeat the process.

4.3 Troubleshooting

No dehumidification, neither hour meter display nor compressor run and POWER button does not turn ON.

1.   Unit unplugged or no power to outlet

2.   Defective control board

3.   Loose connection in internal wiring

No dehumidification, neither hour meter display nor compressor run with POWER button ON.

1.   Defective control board

2.   Loose connection in internal wiring

Some dehumidification, air mover runs continuously but compressor only runs sporadically.

1.   Unit is in defrost cycle, DEFROST light on

2.  Check to make sure humidistat is set high enough

3.   Defrost thermistor defective or loose

4.   Loose connection in compressor circuit

5.   Defective compressor overload

6.   Defective compressor

7.   Defective relay

8.   Low refrigerant charge

No dehumidification, air mover runs but compressor 
does not.

1.   Bad connection in compressor circuit

Figure 2: Refrigeration system of Quest

Содержание Quest PowerDry 4000 Pro

Страница 1: ...53704 Toll Free 1 866 933 7486 www QuestProtect com sales QuestProtect com Read and Save These Instructions TS 760 11 14 quest quest 1 Quest PowerDry 4000 Pro High capacity 176 pints day AHAM 22 Gall...

Страница 2: ...nsate Removal 5 2 5 Ducting 5 2 6 POWER Button 5 2 7 PURGE Button 5 2 8 Humidistat 6 2 9 HOURS Button 6 2 10 DEFROST Light 6 2 11 Defrost Cycle 6 2 12 Low Pressure Control 6 3 Maintenance 7 3 1 Air Fi...

Страница 3: ...s for maintenance and service DO NOT INSTALL UNIT WITH THE SERVICE PANELS INACCESSIBLE Avoid directing the discharge air at people or over the water in pool areas If used near a pool or spa be certain...

Страница 4: ...d refrigeration system Dimensions Width 20 Depth 23 Height 40 Weight 135 lbs 2 Operation Place dehumidifier inside structure place condensate hose into a drain or a very large container and turn on To...

Страница 5: ...mped more than 20 feet above the unit a second pump must be added to relay the condensate 2 5 Ducting A detachable rectangular exhaust collar is supplied that will allow 10 round lay flat duct to be a...

Страница 6: ...w the defrost set point due to excessive frost formation the thermistor activates the solid state control and the defrost light The control cycles the compressor off and on by monitoring thermistor te...

Страница 7: ...much as possible before storage 1 Use the pump purge switch see Sec 2 7 and Fig 4 to reduce the water level in the reservoir 2 Stretch the hose flat to drain it completely If the unit will not be expo...

Страница 8: ...s the entire coil from inlet to outlet The mixture of gas and liquid refrigerant enter the accumulator after leaving the evaporator coil The accumulator prevents any liquid refrigerant from reaching t...

Страница 9: ...control board Unit removes some water but not as much as expected 1 Air temperature and or humidity have dropped 2 Check to make sure humidistat is set high enough 3 Humidity meter and or thermometer...

Страница 10: ...rnal thermal overload protection If defective the complete assembly must be replaced 1 Unplug power cord 2 Remove the front cover 3 Remove the 5 screws attaching blower inlet ring 4 Remove the 4 screw...

Страница 11: ...Gravity Drain Option If the condensate pump fails and cannot be replaced immediately the Quest PowerDry 4000 Pro can be used by draining by gravity 1 Unplug the unit and remove the front cover 2 Push...

Страница 12: ...IED OB T STOR ENGRG DEPT 3 PROOFS TO BE APPROVED BY T STOR ENGRG DEPT 4 COLORS BLACK LINES LETTERS ON WHITE BACKGROUND PART NO SHEET REV TITLE DRAWN BY CHECKED BY SIGNATURES DATE SCALE A 1 OF 1 INCHES...

Страница 13: ...ompressor 55mfd 370V 1 4029606 13 Capacitor Impeller 15mfd 371V 1 4033031 07 14 Thermistor 1 4032644 15 Cord 1 4032315 16 Compressor 11 9KBTU R410a 1 4029186 17 Overload Compressor 1 4029177 18 Evapor...

Страница 14: ...reliable means The end user is responsible for normal care This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modifica...

Отзывы: