24

23

THE FOLLOWING SETTINGS ARE OPTIONAL AND IN MOST CASES
NEED NOT BE ADJUSTED

Feature 01 – Pairing To therM hub: This function is used to connect the thermostat to the 
therM hub.
Feature 02 - Switching Differential: This function allows you to increase the switching 
differential of the thermostat. The default is 1°C which means that with a set temperature 
of 20°C, the thermostat will switch the heating on at 19°C and off at 20°C. With a 2°C 
differential, the heating will switch on at 18°C and off at 20°C.
Feature 03 - Frost Protect Temperature: This is the temperature maintained when the 
thermostat is in Frost Mode. The range is 07 - 17°C. The default is 12°C and is suitable for 
most applications.
Feature 04 – Output Delay: To prevent rapid switching, an output delay can be entered. 
This can be set from 00 - 15 minutes. The default is 00 which means there is no delay.
Feature 05 – Temperature Up/Down Limit: This function allows you to limit the use of the 
up and down temperature arrow keys. This limit is also applicable when the thermostat is 
locked and so allows you to give others limited control over the heating system.
Feature 06 – Sensor Selection: On this therM stat, you can select which sensor should be 
used. You can select between air temperature only, floor temperature, or both. When you 
enable both sensors, the floor sensor is used as a floor limiting sensor and is designed to 
prevent the floor from overheating.

Feature 07 – Floor Temp Limit: This function is available when mode 07 is 
set to 03 or 04. You can set a floor limiting temperature between 20-45°C                                  
(28°C is the default setting).
Note: Air Sensor only MUST NOT be used to control electric under-floor heating.
Floor Sensor or Both should be used.
Feature 08 – Optimum Start: 

Optimum start will delay the start up of the heating 

system to the latest possible moment to avoid unnecessary heating and ensure 
the building is warm at the programmed time. The thermostat uses the rate of 
change information to calculate how long the heating needs to raise the building 
temperature 1°C (with a rate of change of 20, the thermostat has calculated the 
heating needs 20 minutes to raise the building temperature 1°C) and starts the 
heating accordingly.

Feature 09 - Rate of Change: Number of minutes for 1°C temperature rise.
Feature 10 – Cool Enable: This function is used to enable/disable cooling mode.
Feature 11 – Cool Set Temperature: This is the set temperature that the thermostat will 
start cooling.
Feature 12 – Program Mode: Non-Programmable, Weekday/Weekend (5/2),
7 Day Programming or 24 Hour. The thermostat offers three programming modes and 
the option of configuring it to work as a non-programmable thermostat.

Weekday/ Weekend - Allows you to program 4 comfort levels for the weekday and 
4 different comfort levels for the weekend. 
7 Day Program Mode - Each day has 4 comfort levels that can be programmed 
independently. 
24 Hour Mode - All days are programmed the same and repeat continuously.

Feature 13 - Temperature Format: This function allows you to select between °C and °F.

Optional Features Explained

Содержание Stat

Страница 1: ...1...

Страница 2: ...ing Times Timer Override Optional Features Optional Features Table Time Clock Mode Wiring Diagram Mode 2 Time Clock LCD Display Temperature Display Setting the Clock Setting the Comfort Levels Setting...

Страница 3: ...room cools down Setting a programmable room thermostat to a lower temperature will result in the room being controlled at a lower temperature and saves energy The way to set and use your programmable...

Страница 4: ...rams on pages 28 31 of this booklet Note For time clock wiring connections terminate as shown on page 38 Step 3 Screw the thermostat back plate securely into the back box Step 4 Clip the front of the...

Страница 5: ...two minutes to join the therM stat to the therM hub On the therM stat use the Left Right keys to select SETUP and press Tick Feature 01 is displayed on screen Press the Tick key to pair the therM sta...

Страница 6: ...oling control feature option Cooling mode must be initially enabled within the thermostat feature menu Cooling can only be activated from the therM app or therM chill When in cooling mode the therM st...

Страница 7: ...urrent sensor mode 8 Set Displayed when changes are being made to the program schedule or current set point 9 Key Lock Indicator Displayed when the KeyLock is Locked 10 Program Indicator Displayed dur...

Страница 8: ...rrent floor temperature press and hold the Left and Right arrow keys for 5 seconds the floor temperature will then be displayed To set the clock follow these steps Use the Left Right keys to scroll to...

Страница 9: ...g each day of the week can have four different comfort levels In 24 Hour mode all days are programmed with the same comfort levels To program the comfort levels use the Left Right keys to scroll to ED...

Страница 10: ...selection Use the Up Down keys to set the desired Hold period Press Tick to confirm selection Use the Up Down keys to set the desired Hold temperature Press Tick to confirm selection You will see the...

Страница 11: ...show 00 00 and you will need to enter the four digit pin number you set previously Use the Up Down and Tick keys to enter the first two digits Use the Up Down and Tick keys to enter the second two di...

Страница 12: ...see page 23 In time clock mode the holiday function maintains the timed output as OFF The thermostat will maintain this temperature for the duration of the holiday and will then automatically return...

Страница 13: ...ture 07 Floor Temp Limit This function is available when mode 07 is set to 03 or 04 You can set a floor limiting temperature between 20 45 C 28 C is the default setting Note Air Sensor only MUST NOT b...

Страница 14: ...l Set Temperature Program Mode Temperature Format DESCRIPTION Used to add zone to the therM hub 00 0 5o C 01 1 0o C Default 02 2 0o C 03 3 0o C 07o 17o C 12o C Default 00 15 Minutes 00 Default 00o 10o...

Страница 15: ...ed a fault E1 The remote FLOOR probe has not been connected The remote FLOOR probe has not been wired correctly The remote FLOOR probe is faulty E2 The remote AIR probe has not been connected The remo...

Страница 16: ...LR LS LR ARE NORMALLY THE ROOM THERMOSTAT CONNECTIONS TO BOILER HEATING VALVE NEUTRAL NEUTRAL LIVE 230V SUPPLY IN A1 A2 L N 230VAC RT1 RT2 This product must only be installed by a qualified electricia...

Страница 17: ...e Clock Press the Tick key to confirm selection The thermostat will revert to the main display screen for the selected mode Note Factory reset will cancel all parameters that were entered during the s...

Страница 18: ...or current set point 5 Program Indicator Displayed during programming to show which period is being altered 6 Main Menu Displays which option is currently selected 7 Timer Status Displays the current...

Страница 19: ...e the Up Down keys to select the OFF time HOURS and press Tick Use the Up Down keys to select the OFF time MINUTES Press Tick to confirm selection Press the Right arrow key 2 will now flash and the cu...

Страница 20: ...lows you to program 4 on off switching times for the weekdays and 4 on off switching times for the weekend 7 Day Program Mode Each day has 4 on off switching times that can be programmed independently...

Страница 21: ...to help call us now on 0845 890 5685 www thermcontrols com technical thermcontrols com info thermcontrols com therM is a registered Trademark of Plumb Partners Group Ltd All rights reserved Specificat...

Отзывы: