D. Operation panel instruction
3. Parameter Setting:
Press “MODE” button for 5 seconds; enter the Parameter setting status, the main parameter code as
below sheet:
Type
Code
Parameter Name
Setting Range
Factory Setting
Unit
Remark
Temperature
Control
F11
Setting temperature
5-70
55
C
F12
Difference in Temp.
1 - 30
5
C
F13
Determine Heat pump stop
ambient temp.
-10 – 5
-7
C
F14
Highest temp. for heat pump
40 – 60
55
C
F15
Turn on or off electric
heater mode
0 - 1
1
-
F16
Ambient temp. for start electric
heating
-10 - 20
0
C
F17
Turn on or off electric heater
for sterilization function
0-1
1
F18
Sterilization cycle
1-990
336
hour
F19
Water thermal sensor
temp. amendment
-5 – 5
0
C
Compressor
F21
Compressor start delay
0 – 10
3
minute
F28
Econ mode turn on or off
electric heater
0 - 1
1
F29
Heat pumps working or not in
heater mode
0 - 1
1
Defrost
F31
Defrost start temp.
-20 – 20
-2
C
F32
Defrost finish temp.
0 – 50
25
C
F33
Defrost start time
1 – 999
30
minute
F34
Max. defrost time
Off, 1 – 99
5
minute
Alarm
F50
Low pressure alarm mode
0 - 2
2
-
F51
Auto resume times of low
pressure alarm
0 – 10
3
time
F52
Reset time of external alarm
auto resume times
0 – 999
60
minute
F54
Electric heater overheat
protection
0 - 2
2
-
F55
Overheat resume time
0-10
3
-
F56
Alarm resume time
0-999
60
C
F57
Exhaust temp. protection
mode
0 – 2
1
-
F58
Exhaust protect temp.
50 – 125
110
C
F59
Exhaust temp. protection
Return difference
1 – 30
10
C
F60
Condensate drain hole
blocked alarm
0-2
1
Function
F61
Memory status when power off
Yes/No
Yes
-