18

Online Debugging

Note: Always operate this machine from a 220V 1 phase or 3-phase 380V, 50Hz power source, and the

fluctuation amplitude does not exceed 10%, the junction box capacity meets the equipment electrical using

requirements; Take reference to the internal electrical schematic diagram of the unit, connect the indoor unit and

outdoor unit, and ensure that the unit is effectively grounded.

1.) Power the machine.

2.) Set the operation mode, temperature and humidity (For setting methods, please check the operation section

of the controller in the user manual)

3.) Humidity setting value is 95% (higher than the ambient humidity) and temperature is set at 8

(lower than

the ambient temperature), the setting operation mode is auto. Then cooling, heating and humidification will be

calling automatically according to the setting value.

4.) Keep the machine running at least 30 minutes.

After the machine runs for 30 minutes:

1. Check the alarm record. If all functions work well, no alarm record will be generated.

2. Check the machine for leaks. In case of leakage, first check whether the drainage is smooth. If so, reduce the

opening of the ball valve to reduce the inlet water pressure. Run the machine for half an hour again and check

whether the leakage problem is solved.

3. Check whether the temperature is lower than that when the machine is started. Generally, the coil temperature

is reduced by 5-14

as the normal range.

4. Check whether the humidity is higher or the same as when the machine is turned on.

5. If the cooling, heating and humidification of the equipment can operate normally and there is no water leakage,

the debugging work is completed.

Note:

After transportation or moved, it needs to be allowed to stand for more than 24 hours before it can be

turned on.

Содержание HSN-J15-Z

Страница 1: ...gy Co Ltd Wine Cellar Cooling Units Self contained User Manual Thank you for purchasing this Thenow product Please read this manual carefully before attempting to install operate or service Please ret...

Страница 2: ...ore than 24 hours before it can be turned on The power cord must be plugged into a 3 prong grounding type wall receptacle Do not attempt to carry out any measurement device replacement or other mainte...

Страница 3: ...1 Product Introduction 4 2 Dimensions Technical Data 6 3 Installation Debugging 9 4 Introduction of Controller 19 5 Maintenance 23 6 Troubleshooting 24 7 Warranty 26 Table of Contents...

Страница 4: ...noise Optimal air distribution ensures the most uniform temperature in the wine cabinet space Commercial grade corrosion resistant components and spray painting frame for long term durability Build i...

Страница 5: ...ondensing heat generated from refrigeration can be exhausted to outside to achieve the purpose of adjusting the indoor temperature 2 Dehumidification Principle When the wet air flows through the evapo...

Страница 6: ...Dimensions HSN JC5 Dimensions Technical Data...

Страница 7: ...Dimensions HSN J15 Z...

Страница 8: ...97 310 1176 440 350 Drainage mm Self absorption 20 Cooling capacity on above sheet test conditions Cellar inside dry bulb t 12 60 Outside dry bulb t 35 wet bulb t 28 Note There are several factors suc...

Страница 9: ...dered C The appearance of the whole machine is intact D Check the below packing details HSN J15 Z Packing Details Item No Item Q ty Size Photo 1 Unit 1 set See the nameplate 2 User Manual 1 pc A5 3 Co...

Страница 10: ...tails Item No Item Q ty Size Photo 1 Unit 1 set Refer to the namplate 2 User Manual 1pc A5 3 Control Panel 1 pc 90 90mm 4 Controller Cable 3m Warning Our company is not responsible for any accident ca...

Страница 11: ...an extension cord However if you still elect to use an extension cord it is absolutely necessary that it will be a related national standard LISTED 3 wire grounding type appliance extension cord havin...

Страница 12: ...JC5 Installation II Wine Cabinet with Large Space Internal Fan with High Speed...

Страница 13: ...JC5 Installation III Wine Room...

Страница 14: ...2 HSN J15 Z Wine Cabinet Wine Room Installation J15 Z Installation I Wine Cabinet with Small Space Internal Fan with Low Speed...

Страница 15: ...J15 Z Installation II Wine Cabinet with Large Space Internal Fan with High Speed...

Страница 16: ...J15 Z Installation III Wine Room Installation...

Страница 17: ...ced in the bottom and side of the unit 7 Working environment Temperature 5 35 Humidity RH 80 8 Recommend air duct A Heat insulating phenolic board thickness 15 20mm B Stainless steel duct 20mm insulat...

Страница 18: ...ng automatically according to the setting value 4 Keep the machine running at least 30 minutes After the machine runs for 30 minutes 1 Check the alarm record If all functions work well no alarm record...

Страница 19: ...matic operation of the appropriate air flow speed comfortable energy saving accurate and reliable Functional features 1 With 4 inch capacitive full touch display clear picture and easy to operate 2 Re...

Страница 20: ...the plastic frame and screw from the packaging box and then install and fix the plastic frame to the 86 mounting box inside the wall after the wire is threaded out of the plastic frame 2 Correct wirin...

Страница 21: ...ature 4 Setting humidity 5 Running mode display Constant Temperature Constant Humidity Auto Ventilation 6 Coil temperature 7 Running Mode Setting 8 Fan running mode Manual Auto 9 Fan air flow setting...

Страница 22: ...nd Humidity click to enter and set humidity Set time 1 Touch icon Set 2 Find Time click to enter and set time Mode Touch icon Mode to choose the running mode default value is Auto Fan Running Mode Tou...

Страница 23: ...ture and high humidity environment if excess condensate may be generated in the wine cabinet this part of the condensate needs to be manually removed JC5 in this series of products are self absorbent...

Страница 24: ...5 C or lower 5 C 6 Setting higher than ambient temperature 7 Defrosting mode on 1 Check power at receptacle fuses 2 Plug in power cord plug 3 Contact an authorized electrician 4 Check all wirings and...

Страница 25: ...6 Add refrigerant Unit running too long or continually 1 The machine model choice is improper or improper room sealing 2 Ambient temperature to high 1 Check machine mode or check room tightness 2 Che...