3
Connection
•
Power supply plug (a)
•
Plug for lamp (b)
b
GST
L‘
N
a
WINSTA
N
L
a
GST
N
L
b
WINSTA
L‘
N
7. Switching
The presence detectors can be operated as a master in indivi-
dual switching.
Several push buttons can connected to one control input.
Illuminated push buttons can only be used with neutral con-
ductor connection.
Individual switching
In individual switching, the presence detector as master
detects presence and brightness and controls lighting.
L’
a
b
CAUTION
Push button input S is not led to the plugs. If a push button is
required, please wire separately.
8. Settings
The presence detectors were supplied with basic settings
ready for operation. The reference values for the basic
settings are optimised for typical applications. The „Sendo
-
Pro 868-A“ and „theSenda P“ remote controls are optionally
available for start-up. They enable remote adjustment of all
required settings.
Settings Channel A light
Potentiometer brightness switching value „Lux“
The required brightness switching value can be set via the lux
potentiometer. The setting range is around 30 to 1000 lux.
The factory presetting is
ca.
300 lux.
Brightness switching values from 30 to 3000 lux can be set
via the management remote control „SendoPro 868-A“.
Teach-in:
When the LUX potentiometer is moved to the
teach-in position, the LED starts flashing for 20 seconds. As
soon as the LED stops flashing, the measured brightness
value is accepted as the new brightness switching value.
When the teach-in position is exited, the set value on the LUX
potentiometer is accepted as the new brightness switching
value.
Teach-in can also be carried out using the „SendoPro 868-A“
and „theSenda P“ remote controls. In this case, the currently
measured brightness value is immediately accepted as the
brightness switching value.
The brightness measurement is deactivated at potentiometer
setting „on“. The channel light then switches only depending
on presence.
Potentiometer lighting time delay
The following guidance values have proved themselves in
practice and are recommended as settings:
•
Transit zones (no work area) approx. 5 min
•
Classroom approx. 10 min
•
Work areas (office, meeting room) approx. 10 min
•
„Pulse“: Control staircase light time switch (0.5 s „on“
/ 10 s „off“)
•
„test“: Test presence
Parameters via remote control
The following parameters can be queried or changed via
the remote control for support during installation as well as
servicing:
Parameter
Description
Can be
queried
SendoPro
868-A
Can be
changed
SendoPro
868-A
Can be
changed
theSenda
P
Brightness
switching value
Channel A light
Value range in lux x
x
x
Measurement off
x
x