Theben theLuxa S360 WH Скачать руководство пользователя страница 3

3

0

2

Sec

2 sec

Test

Min

Align motion detector with sensor head

The sensor head can be turned by 45° downwards and 90° 

upwards and by 90 ° to the left and right.

90°

45°

90°

90°

6.  Use screens

†

†

Use supplied screen to adjust the motion detector to  

desired detection area.

†

†

Remove the required section from the screen using pliers.

†

†

Then place on the lens and screw in.

7.  Setting 

The motion detector has 3 potentiometers underneath 

for setting the time (Min), brightness (Lux) and sensitivity 

(Meter).

Meter

Min

Lux

Set brightness (lux)

You can set different brightness values (lux) with the  

potentiometer.

If you want to change the preset brightness (15 lux default)

†

†

Set potentiometer to desired brightness (5 – 1000 lux).

teach-in

1000 Lux

5 Lux

500 Lux

7 Lux

100 Lux

10 Lux

15 Lux

50 Lux

15 Lux

or want a specific brightness value to be learned using the 

teach-in function

†

†

At the desired brightness set the potentiometer to  

The value will be learned after 15 s.

†

†

Leave potentiometer at position 

.

Set time (min)

If the motion detector detects no further movement, it swit-

ches off after the set time.

If you want to change the preset time (2 min default)

†

†

Set potentiometer to desired time (1 s – 20 min). 

Min

test

20 min

1 s

15 min

30 s

10 min

1 min

2 min

5 min

2 min

If you want to use the pulse function (e.g. for a staircase light 

time switch)

†

†

Set potentiometer to position  

Min

 . The motion detector 

is switched on for < 1 s, then off for 9 s. If it detects a 

movement again, it switches on again for 1 s. 

Set sensitivity (Meter)

You can reduce the sensitivity; this also reduces the detection 

range.

 

†

†

Set Potentiometer Meter to the desired sensitivity. 

Meter

Max. sensitivity

Содержание theLuxa S360 WH

Страница 1: ...he motion detector in an environmentally sound manner electronic waste 2 Description 3 potentiometers for setting time min and bright ness lux and sensitivity Meter Motion detector with sensor head 3 Connection WARNING Danger of death through electric shock Disconnect power source Cover or shield any adjacent live components Ensure device cannot be switched on again Check power supply is disconnec...

Страница 2: ...ors at objects with highly reflec tive surfaces such as mirrors etc Do not install motion detectors near heat sources such as heating outlets air conditioning systems lamps etc Do not direct the motion detector at objects that turn in the wind such as curtains large plants etc Take account of motion direction during test run 10 20 30 40 40 10 20 30 40 40 10 20 30 40 40 5 m 1 6 m 360 Recommended in...

Страница 3: ... Lux 500 Lux 7 Lux 100 Lux 10 Lux 15 Lux 50 Lux 15 Lux or want a specific brightness value to be learned using the teach in function At the desired brightness set the potentiometer to The value will be learned after 15 s Leave potentiometer at position Set time min If the motion detector detects no further movement it swit ches off after the set time If you want to change the preset time 2 min def...

Страница 4: ...0 3 Min switching capacity 10 mA Switching contact μ Contact 230 V AC LED lamps 2 W 25 W LED lamps 2 W 8 W 90 W LED lamps 8 W 100 W Incandescent and halogen lamp load 2300 W Low voltage halogen lamps 2300 VA Fluorescent lamps low loss series devices uncorrected 400 VA Series corrected 400 VA Parallel corrected 400 VA 42 μF Fluorescent lamps electronic ballast 600 W Compact fluorescent tubes electr...

Отзывы: