background image

5

Resetting the time switch

 

†

Press the 4 buttons simultaneously.

 

You can choose between KEEP PROGRAM and DELETE 
PROGRAM.

6. 

Technical data

Operating voltage: 

230 V AC, +10 % / –15 %

Frequency: 

50 Hz

Standby:

0,9 W

Max switching capacity: 

16 A (at 250 V, cos 

ϕ

 = 1)

Switching capacity: 

10 A (at 250 V,  cos 

ϕ

 = 0,6)

Min. switching capacity:

10 mA/230 V AC

Shortest switching time: 

1 min

Switching accuracy:

accurate to the second

Protection rating: 

IP 20 in accordance with  

EN 60529

Protection class: 

II (housing), I (plug system) in 

accordance with EN 60730-1

Mode of operation:

type 1 BSTU

Operating temperature:

–10 °C … +40 °C

Power reserve: 

6 years at +20 °C (without Blue-

tooth OBELISK top3)

Time accuracy (typical):

± 0,25 s/day (25 °C)

Glow lamp load:

2600 W

Halogen lamp load: 

2600 W

Fluorescent lamp load:  

uncorrected/series corrected:  

parallel-corrected: 

2600 VA 

600 VA (72 µF)

Compact fluorescent tubes (EVG): 

1100 W

LED lamps (< 2 W): 

30 W

LED lamps (> 2 W):

300 W

Resistive switching load:

3680 W

Rated impulse withstand voltage: 

2,5 kV

Pollution degree: 

2

Software class:

A

Bluetooth OBELISK top3:

– Protection rating:

– Temperature:

– Range:

IP 40

–30 °C to +55 °C

15 m on open air test site

 

L

The time switch display is only fully functional at temperatures 

from +5 °C ... +40 °C.

 

Cleaning and service

 

†

Only use a dry, soft cloth to clean the device surface.

 

†

Do not use any cleaning agents or solvents.

Disposal

 

†

Dispose of device in environmentally sound manner  

(electronic waste).

Dimensional drawings

7.  Contact

Theben AG

Hohenbergstr. 32

72401 Haigerloch

GERMANY

Tel. +49 7474 692-0

Fax +49 7474 692-150

Hotline

Tel. +49 7474 692-369

[email protected]

Addresses, telephone numbers etc. 

www.theben.de

Отзывы: