Line coupler S
Device technology
Status: March 16 (Subject to change) Page
14
of
29
2.4
Assembly and installation
The Line coupler S is a modular installation device for quick installation in the distribution board on 35 mm
mounting rails to EN 60 715.
The Line coupler S mounting position can be selected as required.
The connection to the bus is established using the supplied bus connection terminals.
Accessibility to the Line coupler S for the purpose of operation, testing, visual inspection, maintenance and
repair must be provided compliant to VDE 0100-520.
Commissioning requirements
In order to commission the Line coupler S, a PC with ETS and a KNX interface, e.g. USB or IP, are
required. The Line coupler S is ready for operation, after bus voltage is connected to the main line.
For programming the Line Coupler, it is necessary to at least connect the primary line. If the secondary
subline is also connected, the Line coupler S can also be programmed from the secondary subline.
The installation and commissioning may only be carried out by electrical specialists. The appropriate
norms, guidelines, regulations and specifications for your country should be observed when planning and
setting up electrical installations and security systems for intrusion and fire detection.
Protect the device from damp, dirt and damage during transport, storage and operation.
Only operate the device within the specified technical data limits!
The device should only be operated in an enclosed housing (distribution board)!
Supplied state
The Line coupler S is supplied with the physical address 15.15.0.
Assignment of the physical address
The assignment and programming of the physical address is carried out in the ETS.
Button
on the Line coupler S is pressed to assign the physical address. The red LED lights up. It
switches off, as soon as the ETS has assigned the physical address or button
has been pressed
again. The selection of the physical address is dependent on the required device function (coupler or
repeater).
For further information see:
Product and functional overview
Cleaning
If devices become dirty, they can be cleaned using a dry cloth or a cloth dampened with a soapy solution.
Corrosive agents or solutions should never be used.
Maintenance
The Line coupler S is maintenance-free. No repairs should be carried out by unauthorised personnel if
damage occurs, e.g. during transport and/or storage.