Note2:
1
、
For 30K(single -phase),according to sub-clause 4 of the standard IEC
61000-3-11:2000, we choose to declare that the EUT complies the
standard IEC 61000-3-11:2000 provided that the EUT is connected only
to a supply of impedance equal to or less than the Z(Z= 0.092 Ohm +
j 0.058 Ohm)calculated . The Zmax values shall be declared in the
equipment instruction manual, which shall also instruct to determine
in consultation with the supply authority if necessary.
2
、
For 36K(single -phase),according to sub-clause 4 of the standard
IEC 61000-3-11:2000, we choose to declare that the EUT complies the
standard IEC 61000-3-11:2000 provided that the EUT is connected only
to a supply of impedance equal to or less than the Z(Z = 0.074 Ohm +
j 0.046 Ohm )calculated . The Zmax values shall be declared in the
equipment instruction manual, which shall also instruct to determine
in consultation with the supply authority if necessary.