Teleport Integration Unit. Configuration Manual
34
5.3.12 Configuring Modbus
Inputs/Outputs → Outputs
Figure 5.3.12.1. Configuring outputs
The Teleport integration unit can be a Modbus client. Only the Modbus TCP
mode is supported. By default, Modbus is enabled. Use the Modbus protocol to read
the state of inputs and outputs and manage the outputs.
Address space for the Modbus protocol
address
value
00001-00009
(00001)
The state of digital outputs for Teleport-1
(Teleport-2)
10001-10003
(10001-10005)
The state of digital inputs for Teleport-1
(Teleport-2)
The integration unit supports the following protocol functions:
(0x01) Read Coil Status – read the digital input
(0x02) Read Discrete Inputs — read the digital output
(0x05) Write SingleCoil Status — write a single output
(0x0F) Write Coil Status — write the group of outputs