CONDENSATE DRAIN
Push fit connections are widely available for the 7/8” (22mm) OD condensate drain and 3/4"(19mm) ID drain stub
adaptor. Alternatively 7/8” (22mm) bore plastic tubing may be fitted directly to the stub/adaptor with a hose clamp. Take
care not to over tighten hose clamps as this could damage the stub pipe.
ELECTRICAL CONNECTIONS
•
Cables are routed to the terminal block via the cable cord grips at the rear of the unit and then through the back of
the electrics box (see page 2).
•
Cables
MUST
be size compatible with the recommended system fuse.
FUSES
SYSTEM
COOL ONLY
WITH ELECTRIC
HEATER
1PH
3PH
1PH
3PH
CX(E)A30 + CKA35
16A
-
16A
-
CX(E)A50 + CKA35
20A
-
20A
-
CX(E)A50 + CKA50
20A
-
20A
-
CX(E)A70 + CKA70
20A
-
32A
-
ELECTRICAL DATA
Indoor CX(E)A
30
50
50
70
Outdoor CKA
35
35
50
70
Rated Current Cooling A
5.2
5.2
8.0
11.0
Maximum Running Current A
7.3
7.3
10.8
14.2
Starting Current A
26.0
26.0
40.0
61.0
UNIT ELECTRICAL LOADS [230V 50Hz 1Ph (A) or 400V 50Hz 3Ph (A/Ph)]
MODEL
FAN MOTOR HEATER
CX(E)A 30
0.8
13.0
CX(E)A 50
0.8
13.0
CX(E)A 70
0.8
13.0
INTERCONNECTING WIRING
2 CORE + EARTH 1.5mm
3 CORE + EARTH 1.5mm
ELECTRICAL DATA.
INTERCONNECTING INSTRUCTIONS FOR CX(E)A AND CKA SYSTEMS