MOUNTING 

 

Whether floor or wall mounted, it is essential that the mounting surface is capable of supporting the unit 
weight

Leave space around the unit for air circulation and access for installation and maintenance. 

 
 
 
 
 
 
 
 
 

 

 
 
 

 
 
NOTE: Please check this before installation.  
MAXIMUM EQUIVALENT PIPE LENGTHS 15m 
1. 

Performance is based on 7.5m pipe runs. Correctly sized pipes for each installation will result in no 
significant loss of capacity on extended pipe runs up to 15m. 

 

2.

   

In calculating equivalent lengths of pipe runs, the effect of bends and fittings must be taken into 
account. The table below covers the fittings most likely to be encountered in this installation.  

 
 

 

The equivalent lengths of all the fittings in a pipe run should be added together and the total added to 
the actual pipe length in order to calculate the total equivalent length. 

 

3.

   

Use the shortest possible route, avoiding sharp bends. 

 
4.

   

Completely insulate the suction line, fully over the indoor unit drain tray.

 

 

 

 

FITTING LOSSES, in equivalent straight lengths of pipe (m). 

FITTING 

Pipe Size OD 

 
 
To calculate the total equivalent 
length, the equivalent lengths of all 
fittings in a pipe run must be added to 
the actual length of pipe in the run: 
these are the fittings most likely to be 
used. 
  
R = Radius of bend 
d = Diameter of tube   
C = Centres of bend 
 
   

3/8" 

1/2" 

5/8" 

45° Bend 

0.12 

0.15 

0.18 

90° Bend R/d = 1 

0.37 

0.43 

0.49 

90° Bend R/d = 1.5 

0.24 

0.27 

0.30 

180° Bend R/d = 1.5 

0.73 

0.91 

1.10 

180° Bend C/d = 2.5 

0.46 

0.55 

0.64 

90° Elbow 

0.67 

0.85 

1.04 

 

A. SUCTION AND LIQUID/EXPANSION LINES:

 

The expansion capillary is located in the outdoor unit and the equivalent pipe run is 15m maximum, including 
a maximum lift of 7.5m. Fully insulate the suction and liquid/expansion line. Ensure the suction pipe is 
insulated well over the drain tray at the indoor unit. Liquid lines should be routed to avoid hot areas. This 
prevents flash gas forming, which may result in erratic control of liquid refrigerant to the evaporator

 

  

MAXIMUM EQUIVALENT LENGTH 

OF SUCTION LINE PIPE SIZES 

(m) 

LIQUID/EXPANSION LINE 

TOTAL CHARGE 

(kgs) for 7.5m 
supplied in 17 

series units only 

 

SYSTEM 

1/2" 

5/8" 

1/4" 

3/8" 

CX(E)A30 + CKA 35 

15 

-  

15 

 - 

0.724 

CX(E)A50 + CKA 35 

15 

-  

15 

 - 

0.856 

CX(E)A50 + CKA 50 

15 

 - 

15 

 - 

1.306 

CX(E)A70 + CKA 70 

 - 

15 

 - 

15 

 1.882 

 

CKA PIPEWORK 

1500 min air off

100 min

100 min

600 min

CKA INSTALLATION 

Содержание Marstair 56500002

Страница 1: ...Safe Working practices 2 These units contain live electrical components moving parts and refrigerant under pressure Always site out of reach of children and protect from vandalism 3 The data plate on...

Страница 2: ...17 5 17 5 39 39 124 422 5 70 845 888 124 888 Fixing centres Fixing centres 320 96 MIN 500 FOR SIDE ACCESS 483 20 X Interconnecting Wiring Z1 Suction Z2 Liquid Expansion SIDE VIEW Wall mounted X Z1 Z2...

Страница 3: ...50 CKA 70 A 760 760 860 B 256 256 307 C 552 552 660 D 330 330 370 E 290 290 340 F 510 510 630 G 50 50 50 H 85 85 85 J 70 70 70 WEIGHT 35Kg 42Kg 56Kg Valve Size LIQUID upper 1 4 1 4 3 8 Valve Size SUC...

Страница 4: ...uring that it is square and level 6 Remove the drain tray then fit the drain stub nut gasket Refit the drain tray NITROGEN CHARGE The unit contains a small charge of dry nitrogen which should be disch...

Страница 5: ...ipe Size OD To calculate the total equivalent length the equivalent lengths of all fittings in a pipe run must be added to the actual length of pipe in the run these are the fittings most likely to be...

Страница 6: ...mating surfaces e Sight glasses and filter driers are not necessary but if required should be fitted between the outdoor unit liquid shut off valve and the expansion device EVACUATING DO NOT RELEASE...

Страница 7: ...ee page 2 Cables MUST be size compatible with the recommended system fuse FUSES SYSTEM COOL ONLY WITH ELECTRIC HEATER 1PH 3PH 1PH 3PH CX E A30 CKA35 16A 16A CX E A50 CKA35 20A 20A CX E A50 CKA50 20A 2...

Страница 8: ...5 2 83 2 15 3 25 3 0 CX E A 50 CKA 50 3 50 2 45 3 25 3 0 CX E A 70 CKA 70 4 62 3 24 3 25 3 0 OPTIONAL KITS PART NUMBER DESCRIPTION 55900700 3kW heater CXA only 55900701 Digital temperature display CXA...

Страница 9: ...dd 1dBA or 1NC for high level wall mounted units TEMPERATURE CONTROL Do not set the controller below 8 C The SET temperature is factory set at 12 C The digital display normally displays the return air...

Отзывы: