28
Connection of the RS232 serial port and TCP/IP network
Figure no. 18
The STS Manager software supports both RS232 serial connections and TCP/IP Ethernet network
connections.
OPTIONAL POWER INPUT
An external power source is required to power the system logic in the event that both input sources are not
available simultaneously; this enables access to the mimic display panel and event log. This isolated input
supplies the control logic of the system, and the minimum power that will be drawn will be 150W
The external power supply connector is located on the panel behind the door of the STS and is an IEC320 C14
plug type.