13
NEOLINE
PRO
�
1/1
�
1-3 kVA
�
ONLINE UPS
USER MANUAL
test/mute test
operation
second. UPS gets to self-test mode and tests its status. It will exit automatically
after finishing test.
When UPS is in BAT Mode, press the self-test/mute key for more than 1
second, the buzzer stops beeping. If you press the self-test/mute key for one
more second, it will restart to beep again.
UPS Setting
Enter Setup interface. Press and hold the function setting key
for more
than 2 seconds, then come to Setup interface, press and hold the inquiring key
(
,
) for more than half a second (less than 2 seconds), select the
function setting, choose the setup interface, at the moment, the letters flash.
Enter the setup interface. Press and hold the function setting key
for
more than half a second (less than 2 seconds), then come to the setup
interface, at this time, the letters
doesn’t
flash any more, the numerical value
flash. Press and hold the inquiring key (
,
) for more than half a
second (less than 2 seconds), select the numerical value in accordance with
the function.
Confirm the setup interface. After selecting numerical value, press and hold
the function setting
for more than half a second (less than 2 seconds).
Now, the setting function is completed and the numerical value illuminates
without flashing.
Exit from the setup interface. Press and hold function setting key
for
more than half a second (less than 2 seconds), exit from the setup interface
and return to the main interface.
Note:
UPS could not be set until it is connected to the battery and it is turned off and
switched to Stdby mode (standby mode).
Disconnect mains power after setting.
The LCD display screen will automatically extinguish in about 1 min, and the
setting will be configured normally.
5.4 UPS Settings
Output voltage setting
LCD display
Settings
For 208/220/230/240 VAC models, you may choose the
following output voltage:
208:
output voltage is 208Vac
220:
output voltage is 220Vac
230
(default)
:
output voltage is 230Vac
240:
output voltage is 240Vac