 1/1 

 1-3 kVA 

 ONLINE UPS

USER MANUAL

test/mute test 

operation 

second. UPS gets to self-test mode and tests its status. It will exit automatically 
after finishing test. 
When UPS is in BAT Mode, press the self-test/mute key for more than 1 
second, the buzzer stops beeping. If you press the self-test/mute key for one 
more second, it will restart to beep again. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS Setting 

Enter Setup interface. Press and hold the function setting key

 

for more 

than 2 seconds, then come to Setup interface, press and hold the inquiring key 

   

 

) for more than half a second (less than 2 seconds), select the 

function setting, choose the setup interface, at the moment, the letters flash. 
Enter the setup interface. Press and hold the function setting key

  

for 

more than half a second (less than 2 seconds), then come to the setup 
interface, at this time, the letters 

doesn’t

 flash any more, the numerical value 

flash. Press and hold the inquiring key ( 

  

   

) for more than half a 

second (less than 2 seconds), select the numerical value in accordance with 
the function. 
Confirm the setup interface. After selecting numerical value, press and hold 
the function setting

for more than half a second (less than 2 seconds). 

Now, the setting function is completed and the numerical value illuminates 
without flashing. 
Exit from  the setup  interface. Press and hold function setting key 

for 

more than half a second (less than 2 seconds), exit from the setup interface 
and return to the main interface. 

Note: 

UPS could not be set until it is connected to the battery and it is turned off and 
switched to Stdby mode (standby mode). 
Disconnect mains power after setting. 
The LCD display screen will automatically extinguish in about 1 min, and the 
setting will be configured normally. 

 

5.4  UPS Settings 

Output voltage setting 

 

LCD display 

 

Settings 

 

 

 

For 208/220/230/240 VAC models, you may choose the 
following output voltage: 

208: 

output voltage is 208Vac 

220: 

output voltage is 220Vac 

230 

(default)

output voltage is 230Vac 

240: 

output voltage is 240Vac 

Содержание NEOLINE PRO 1KVA ST

Страница 1: ...ONLINE UPS 1 3 kVA Uninterruptible Power Supply System User Manual 1 phase In 1 phase Out NEOLINE PRO 7 183 46 Volou 7 18 346 Moschato Greece 30 210 9590080 info tescom ups gr www tescom ups gr...

Страница 2: ...5 3 Installation 7 3 1 Unpacking inspection 7 3 2 Installation information 7 3 3 Installation and output connection 8 4 Network Functions 8 4 1 Communication port 8 4 2 EPO port optional 9 4 3 Intelli...

Страница 3: ...it by yourself If any questions please contact local service center or dealer 1 2 Battery safety information Environmental factors impact battery life Elevated ambient temperatures poor quality utilit...

Страница 4: ...directly otherwise it will cause electric shocks or will be on fire The battery circuit is not isolated from the input voltage high voltage may occur between the battery terminals and ground check if...

Страница 5: ...50 Input frequency range 40 70 Hz PFC 0 99 THDI 6 Bypass voltage range 25 15 settable Output Output voltage 208 Vac 220 Vac 230 Vac 240 Vac settable Voltage accuracy 1 Output PF 0 9 Inverter overload...

Страница 6: ...rotection Output short circuit protection Battery discharge protection Communication port Standard RS232 Options USB SNMP card dry contacts Display LCD Environmental Operating humidity 0 90 RH 0 40 C...

Страница 7: ...5 NEOLINE PRO 1 1 1 3 kVA ONLINE UPS USER MANUAL 2 2 Rear panel features a 1 VA S T DC24V b 2 VA S T DC24V...

Страница 8: ...3 VA S T DC24V AC input socket EPO Emergency Power Off port Battery connector RS232 port Fan Intelligent slot USB port Output sockets Note The figure is for reference only Due to the technology upgrad...

Страница 9: ...that front and side panel air intake hole rear panel air outtake hole will be unobstructed The ambient temperature around the UPS should be within 0 40 non condensing If dismantling the machine at lo...

Страница 10: ...e switch please install it on output cable 3 3 Installation and output connection Normally output connection of 1 3kVA series is configured with power outlets or terminal blocks users can plug the loa...

Страница 11: ...UPS it s for SNMP card and dry contacts Users can insert any type intelligent card from those three into it to monitor and manage the UPS And users don t have to turn off the UPS when install the int...

Страница 12: ...battery mode UPS runs the mute function INQUIRING key Not in setting mode Press or for more than half a second less than 2 seconds display the items orderly Press for more than 2 seconds Circularly an...

Страница 13: ...oad icon will flash Mute icon Indicates the audible alarm is disabled mute Press the mute key in the battery mode the mute icon flash Fan icon Indicates fan working status When the fan normally runs t...

Страница 14: ...its output is same as the input voltage within the input range If there is no need of output voltage when mains power connected you can set up bPS to OFF Default bPS is ON it means there is bypass ou...

Страница 15: ...ess and hold the inquiring key for more than half a second less than 2 seconds select the numerical value in accordance with the function Confirm the setup interface After selecting numerical value pr...

Страница 16: ...splay Settings Enable or disable Bypass function You may choose the following two options ON Bypass enable OFF default Bypass disable AUO setting LCD display Setting AUO setting only can be set in Std...

Страница 17: ...non to show a small numerical value of WATT and VA Version and Temperature Indicate firmware version of UPS and display the highest temperature of UPS components As the following graphics shows the fi...

Страница 18: ...ad in line mode Note When UPS is working in bypass mode it has no back up function Line mode Being in line mode are as following When input mains corresponding to the working conditions UPS will work...

Страница 19: ...splays CUCF In CUCF mode the loading capacity will drop to 70 of the original capacity The output frequency is fixed at the setting value it doesn t vary with utility change And the UPS cannot be set...

Страница 20: ...splays bAT One beep 4 sec One flash 4 sec One flash sec Warning for abnormal voltage of battery Working mode displays bAT Bat flash One beep sec One flash sec One flash sec 3 Bypass mode Mains power n...

Страница 21: ...alarm code will be displayed in four digital tubes on the right of the numerical part of the LCD screen red mark as shown below Alarm icon Alarm code The alarm truth table during operations is shown...

Страница 22: ...F Display Overcharging Mains Start up Charger fault value warnings reverse abnormal 0 1 2 3 4 5 The second 6 digital tube 7 from right to left 8 9 A B C D E F The third digital tube Display value EEP...

Страница 23: ...ght to left Display value Over load fault Mains lost Bypass abnormal 0 1 2 3 4 5 6 7 Example If the alarm code 2000 appears on the LCD screen it indicates loss of mains power 7 Troubleshooting When th...

Страница 24: ...e loads And then restart the UPS If the problem persists contact the supplier Fault icon display audible buzzer alarm continually the fault code is 50 54 Overload Check the load level and disconnect t...

Страница 25: ...scend Replace with new batteries contact the supplier to get the new batteries and spare parts UPS doesn t have any power going through even mains power on UPS input breaker disconnected Reset the cir...

Страница 26: ...www tescom ups gr NEOLINE PRO 1 1 1 3 kVA ONLINE UPS USER MANUAL 7 183 46 Volou 7 18 346 Moschato Greece 30 210 9590080 www tescom ups gr info tescom ups gr...

Отзывы: