11

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Input and Output Terminal Block wiring diagram of 

NEOLINE 210XL/215XL/220XL 

 
 
 

5.3 Operating procedure for connecting the long backup time model UPS with the external battery 
 

1. The nominal DC voltage of external battery pack is 192VDC. Each battery pack consists of 16 pieces of 12V 
maintenance free batteries in series. To achieve longer backup time, it is possible to connect multi-battery 
packs, but the principle of “same voltage, same type” should be strictly followed. 
 
2. For NEOLINE 106XL/110XL/210XL/215XL/220XL, The procedure of installing battery bank should be omplied 
with strictly. Otherwise you may encounter the hazardous of electric shock.. 
 
 
 
1) A DC breaker must be connected between the battery pack and the UPS. The capacity of breaker must be 
not less than the data specified in the general specification as follow. 
 
 

Model 

NEOLINE 

106 

NEOLINE 

106XL 

NEOLINE 

110 

NEOLINE 

110XL 

NEOLINE 

210 

NEOLINE 

210XL 

NEOLINE 

215XL 

NEOLINE 

220XL 

Battery 

voltage 

192VDC 

192VDC 

192VDC 

192VDC 

192VDC 

192VDC 

192VDC 

192VDC 

Battery 
current 

34A max 

34A max 

56A max 

56A max 

46A max 

46A max 

70A max. 

102A max 

 
 

Note:

 240VDC battery voltage can be choose for NEOLINE 106XL/101XL/210XL/215XL/220XL also   

 
2) Set the battery pack breaker in “OFF” position and connect the 16 pieces of batteries in series. 
 
3. To complete the connection by plugging the connector of the external battery cable into the external battery 
socket of the UPS. Do not attempt to connect any loads to the UPS now. You should connect the input power 
wire to the right position first. And then set the breaker of the battery pack in the “ON” position. After that 
set the input breaker in the “ON” position. The UPS begins to charge the battery packs at the time. 
 

 
 
 
 
 
 

 

Содержание NEOLINE 6-20KVA UPS

Страница 1: ...NEOLINE 6 20KVA UPS High Frequency Online UPS Uninterruptible Power System USER MANUAL...

Страница 2: ...th all warnings and operating instructions in this manual and on the unit strictly Save this manual properly Do not operate this unit before reading through all safety information and operating instru...

Страница 3: ...packing and inspection 9 4 2 Input and output power cords and protective earth groundins tallation 9 4 2 1 Notes for installation 9 4 2 2 Installation 9 4 3 Opertaing procedure for connecting the lon...

Страница 4: ......

Страница 5: ...nts further supply to the load by the UPS in any mode of operation should be provided in the building wiring installation An appropriate disconnect device as short circuit backup protection should be...

Страница 6: ...Verify that no voltage is present before servicing Batteries have a high short circuit current and pose a risk of shock Take all precautionary measures specified below and any other measures necessar...

Страница 7: ...IEC EN 62040 2 Category C3 EMS ESD IEC EN 61000 4 2 Level 4 RS IEC EN 61000 4 3 Level 3 EFT IEC EN 61000 4 4 Level 4 SURGE IEC EN 61000 4 Level 4 Low Frequency Signals IEC EN 61000 2 2 Warning This is...

Страница 8: ...4 2 Description of commonly used symbols Some or all of the following symbols may be used in this manual It is advisable to familiarize yourself with them and understand their meaning...

Страница 9: ...E 106 Single phase inbuilt 10KVA NEOLINE 110 Single phase inbuilt Long back up time 10KVA NEOLINE 210 Three phase inbuilt 6KVA NEOLINE 106XL Single phase External battery bank 10KVA NEOLINE 110XL Sing...

Страница 10: ...0 8 Synchronized 46 54Hz in Line mode AC mode 1 of normal frequency in Battery mode THD 2 Full load Linear load 105 125 load transfers to bypass mode after 1minutes 130 load transfers to bypass mode a...

Страница 11: ...Select Button if the ups system is in bypass mode or self test mode the output frequency could be selected by pressing Select button and confirmed by pressing Enter button Enter Button if the ups sys...

Страница 12: ...and the OVER LOAD lighting with warning it means ups in overload Indicates ups input voltage value output voltage value output frequency value which could be displayed from 0 to 999VAC The four items...

Страница 13: ...and wiring must be performed in accordance with the local electric code and the following instructions by Professional personnel or safety please cut off the mains power switch before installation Th...

Страница 14: ...onnection and finally turn on the loads one by one 10 No matter the UPS is connected to the utility power or not the output of the UPS may have electricity The parts inside the unit may still have haz...

Страница 15: ...be not less than the data specified in the general specification as follow Model NEOLINE 106 NEOLINE 106XL NEOLINE 110 NEOLINE 110XL NEOLINE 210 NEOLINE 210XL NEOLINE 215XL NEOLINE 220XL Battery volta...

Страница 16: ...equipped with battery individually 5 Please refer the figure followed to see the wiring of parallel operation The capacity of the breaker must be not less than the specification as follow Model No Ca...

Страница 17: ...13 Parallel Installation Diagram 4 To perform the maintenance follow the stand alone requirement...

Страница 18: ...14...

Страница 19: ...15...

Страница 20: ...OFF button continuously for more than 1 second and the buzzer will beep once The UPS will turn into Bypass mode 2 Upon completion of the above to turn it off output of electric current of the UPS is...

Страница 21: ...ry to replace any connection cables please purchase the original materials from the authorized distributors or service centers so as to avoid overheat or spark resulting in fire due to insufficient ca...

Страница 22: ...t of the input range of the UPS The UPS is running in Battery mode To save your data and close the application program Make sure the utility power is within the input voltage or frequency range permit...

Страница 23: ...ss mode Bypass mode 10 2 Line mode The LCD display in Line mode is shown in the following diagram The information about the utility power the battery the temperature and load could be displayed The op...

Страница 24: ...S is running in Battery mode the buzzer beeps once every 4 seconds If the ENTER button on the front panel is pressed for more than 1 second again the buzzer will stop beeping in silence mode Battery m...

Страница 25: ...the following diagram When the UPS operating in parallel mode the operating mode code of the UPS is P2 Parallel mode 10 6 Warning mode The LCD display in warning mode is shown in the following diagra...

Страница 26: ...n fault is shown in the following diagram The symbol MODE not be shown and the symbol FAULT is shown instead in code display Fault mode Bus Fault 10 8 Set Mode The LCD display in voltage set is shown...

Страница 27: ...ollowing diagram 10 9 Battery Low voltage warning The LCD display in Battery Low voltage warning is shown in the following diagram Notice When Battery low voltage or short back up time both low voltag...

Страница 28: ...y Low voltage warning is shown in the following diagram Note The above all diagrams temperature battery voltage Input voltage input frequency output voltage output frequency would alternately displaye...

Страница 29: ...for further information 11 3 AS400 Interface Option Except for the communication protocol as mentioned above this series UPS has AS400 card an optional accessory for AS400 communication protocol Plea...

Страница 30: ...onitoring software which provides userfriendly interface to monitor and control your UPS This unique software provides safely auto shutdown for multi computer systems while power failure With this sof...

Страница 31: ...27 Appendix1 Rear Panel BACK VIEW of NEOLINE 106 NEOLINE 110...

Страница 32: ...VIEW of NEOLINE 210XL NEOLINE 215XL NEOLINE 220XL BACK VIEW of NEOLINE 210 1 RS232 2 Inteligent Solt 3 Fan 4 Parallel Port 5 Input Breaker 6 Maintain Switch 7 Terminal Block Cover 8 Cable Rack 9 EPO...

Страница 33: ...29 192321142002001...

Страница 34: ...30 AGKK10360 10 2019...

Отзывы: