10
II. UPS INSTALLATION
2.1
Introduction
WARNING!!!
•
Do not apply electrical power to the UPS equipment before the arrival of authorized service personnel.
•
The UPS equipment should be installed only by qualified service personnel.
•
The connection of the batteries and the maintenance should be done by qualified service personnel.
•
Do not make any short- circuit to the battery poles. Because of high voltage and high short-circuit
current, there is risk of electrical shock or burn.
•
Eye protection should be worn to prevent injury from accidental electrical arcs. Remove rings, watches
and all metal objects. Only use tools with insulated handles. Wear rubber gloves.
This chapter contains location installation information of the UPS and the batteries. All the establishments
have their own specialties and needs. So in this part, the installation procedure is not being explained step
by step. Instead, general procedure and the applications are explained for the technical personnel.
2.2 Unpacking
The UPS is packed and enclosed in a structural cardboard carton to protect it from damage.
1) Inspect for damage that may have occurred during the shipment If any damage is noted, call the
shipper immediately and retain the shipping carton and the UPS.
2) Carefully open the carton and take the UPS out.
3) Retain the carton and packing material for future use.
Unit package contents:
1) A user manual and Guarantee certificate.
2) Battery cabinet and/or shelf (Optional)
3) Battery connection cables.
2.3 Equipment Positioning
ATTENTION:
Units are designed to operate on the concrete floor.
1.
The equipment’s installation place must be an easy serving place.
2.
Install the UPS in a protected area with adequate air flow and free of excessive dust.
3.
You must therefore allow for a minimum gap of 250 mm behind the unit to allow adequate air flow
4.
Select a suitable place (temperature between 0
°
C and 40
°
C) and the relative humidity (%90 max)
5.
It is recommended to place the equipment in an air-conditioned the room (24
°
C)
6.
Temperature is a major factor in determining the battery life and capacity. Keep batteries away from
main heat sources or main air inlets etc.
7.
In case of an operating the UPS in a dusty place, clean the air with a suitable air filtration system.
8.
Keep out of your equipment from explosive and flammable items.
9.
Avoid direct sunlight, rain, and high humidity.
WARNING!!!
Check the capacity of the forklift if it is available for lifting.
DO NOT LEAN OR LIFT THE UPS CABINET AFTER THE BATTERIES HAVE BEEN
INSTALLED.
Содержание DS300SHA Series
Страница 1: ...DS300SHA SERIES DSP Controlled UPS Pf 0 8 10 15 20 30 kVA 3 Phase IN 3 Phase OUT USER MANUAL ...
Страница 2: ......
Страница 17: ...14 Figure 2 3 External Battery Connections 60x12V 30x12V Batteries 30x12V Batteries ...
Страница 18: ...15 Figure 2 3a DS300SHA Series 10 15 20 30 KVA Internal Battery Connections 60x12V 5Ah ...
Страница 19: ...16 Figure 2 3a DS300SHA Series 10 15 20 30 KVA Internal Battery Connections 60x12V 7 9Ah ...
Страница 56: ......
Страница 57: ...AGKK12611 10 2021 ...