background image

 

  

 

54

 
 

V.  PARALLEL OPERATING INSTRUCTIONS 

 

 
 
 

After all the electrical connections of UPS have been made and while all the circuit breakers and switchtes 
of the device are turned OFF (at “0” position);  

 

1. 

Check the polarities of battery connections: 

 

K1           :  + V (nominal v360V, float charge v405V) 
K2-K2     :  0 V  (common terminal for ‘’+’’ and ‘’-‘’ battery groups) 
K3           :  - V  (nominal voltage -360V, float charge voltage -405V) 

 

2. 

Check 3-phase AC input and neutral connections (care should be taken fort he phase order). 

 

ATTENTION!!!

    TWO  CABLES  FOR  EACH  BATTERY  GROUP  SHOULD  BE  USED  FOR  EXTERNAL 

BATTERY  CONNECTION,  AND  THE  COMMON  POINT  CONNECTION  SHOULD  BE  MADE  ON  K2 
TERM

İ

NAL BLOCK! 

 

WARNING ! :

 UPS should never be operated without neutral connection. 

 
 

3. 

Check the output load connections of UPS. 

 
 
 
 

5.2.1 Starting UPSs from a completely shut down position: 

 

1. 

Turn ON S1 (AC Input) switch (switch to ‘’1’’ position) 

 

2. 

Turn ON S2  (Bypass) switch (switch to ‘’1’’ position)  

 

3. 

Turn on S7 (On/Off)  switch (to ‘’1’’ position). LCD panel activates, and ‘’INV RESET” or “PFC RESET’’ 
message appears on the display meaning that the rectifier starts to operate.  

 

4. 

Turn ON S4  (AC Output) switch (switch to ‘’1’’ position)  

 

5. 

A few seconds later red bypass light (L2) on front panel turns off and gren inverter light (L6) turns on.  
L6 light indicates that the UPS has started normal operation and generating uninterruptable power for 
the critical load.  

 

6. 

Turn on S5 switch (to “1” position) to connect the battery group to UPS.  

 

7. 

UPS is ready and in normal operation now.  

 
 

5.2.2 Shutting down the UPS  

 

After closing all the critical loads supplied by the UPSs output:  
 

1. 

Turn off S4 (AC Output) switch (to ‘’0’’ position). 

2. 

Turn off S7 (On/Off) switch (to ‘’0’’ position).  

3. 

Turn off S5 (Battery) switch (to ‘’0’’ position).  

4. 

Turn off S2 (Bypass) switch (to ‘’0’’ position).  

5. 

Turn off S1 (AC Input) switch (to ‘’0’’ position).  

 
After  performing  the  above  procedure,  UPSs  is  completetely  shut-down.  In  this  case  PFC  rectifier  and 
inverter is not operating and the batteries are not being charged.  
 

5.1 INTRODUCTION  

5.2 OPERATING INSTRUCTIONS FOR PARALLEL CONNECTED UPSs. 

Содержание DS300H Series

Страница 1: ...DS300H SERIES DSP Controlled UPS 40 60 80 kVA 3 Phase In 3 Phase Out USER MANUAL...

Страница 2: ......

Страница 3: ...iption of Connection Terminals of the UPS 13 2 7 Battery Installation 14 III FRONT PANEL 18 3 1 Introduction 18 3 2 Front Panel Menu Descriptions 18 3 2 1 MEASUREMENTS menu 21 3 2 2 ALARM LOGS menu 24...

Страница 4: ...Maintenance Bypass Condition to Normal Operation 57 6 2 UPS Behavior During Mains Outage 57 VII MAINTENANCE 58 7 1 Scheduled maintenance 58 7 2 Daily checks 58 7 3 Weekly checks 58 7 4 Annual Mainten...

Страница 5: ...C power is disconnected To reduce the risk of electric shock disconnect the UPS from the mains supply before installing a computer interface signal cable Reconnect the power cables only after signalin...

Страница 6: ...internal voltage and frequency regulating software which ensures that its output to the critical load is maintained within close tolerances independent of voltage and frequency variations on the mains...

Страница 7: ...CF 3 1 Double polarity battery with common terminal Automatic and manual battery test and battery temperature compensation features 3 separate maintenance clock counters Battery charge with current l...

Страница 8: ...Switch S4 F7 F8 F9 Output Switch Fuse S5 F10 F11 F12 Battery Switch Fuse K1 Rectifier Input Contactor K2 Inverter Output Contactor Rectifier Charger 3 PHASE MAINS I P Battery Dual Polarity Maintenanc...

Страница 9: ...nd black outs when it is connected to either static or maintenance bypass supply 1 2 2 Operating Conditions of UPS UPS may be in one of the following operating conditions A Normal Operation If Mains s...

Страница 10: ...le Relay Output contacts Batt circuit breaker output and input Generator input Temperature sensor Relay 2 S7 On off switch S5 Batt input F10 F11 F12 S1 AC input F1 F2 F3 S3 Maintenance BY PASS S2 By P...

Страница 11: ...top Relay 4 COM1 RS232 Communation Socket DB9 female SNMP COM2 RS232 Communation Socket DB9 female Figure 1 3 b 80 kVA switches fuses and interface connections PARALLEL PORT 2 PARALLEL PORT 1 S7 On of...

Страница 12: ...mode Efficiency 100 Load up to 94 Load Crest Factor 3 1 Output Voltage THD linear load 2 Overload 125 Load 10min 150 Load 1min BATTERY Total Number 60 blocks 12V 2x30 serial 60 batteries Float Charge...

Страница 13: ...age is noted call the shipper immediately and retain the shipping carton and the UPS 2 Carefully open the carton and take the UPS out 3 Retain the carton and packing material for future use Unit packa...

Страница 14: ...2 terminal block NOTES The neutral conductor should be sized for 1 5 times the output bypass phase current These recommendations are for guideline purposes only and are superceded by local regulation...

Страница 15: ...r earth bus to the safety earth of the mains distribution panel NOTE The earth and the neutral connections must be in accordance with the local rules WARNING Note that the Input Neutral N1 MUST also b...

Страница 16: ...obtain efficient battery operation In general a minimum space of 10 mm must be left on all vertical sides of the battery block A minimum clearance of 20 mm should be allowed between the cell surface a...

Страница 17: ...15 30x12V Batteries 30x12V Batteries 0 360V 360V 0 K1 K2 K3 K2 Figure 2 3 External Battery Connections 60x12V...

Страница 18: ...16 Figure 2 3a DS300H Series 40 60 80 KVA Internal Battery Connections 2x30 60x12V 7Ah...

Страница 19: ...17 Figure 2 3b DS300H Series 40 60 80 KVA Internal Battery Connections 2x60 120x12V 7Ah two groups of batteries with common point in parallel...

Страница 20: ...2 Load on bypass indicator lamp L3 Input voltage indicator lamp L4 Rectifier run pilot lamp L5 Battery operation indicator lamp L6 Load on UPS indicator lamp L7 Output switch on indicator lamp There a...

Страница 21: ...l measurements ENTER EXIT ALARM LOGS UPS LOG RECORD Page1 ENTER CLEAR LOG Page1 ENTER EXIT INFORMATION RS232 Comm 1 2 Page1 Maximum UPS power Page1 Nominal voltage and frequency Page1 Inverter firmwar...

Страница 22: ...ut command Page3 ENTER EXIT PASSWORD Getting service code Page1 Type service password Page1 Type user password Page1 ENTER EXIT ADJUST in English Group adjustments Automatic settings Inverter factory...

Страница 23: ...alarm messages Up previous page down next page MEASUREMENTS INPUT Page 3 Level 3 ENTER EXIT ENTER exit to upper menu Current alarm messages Up previous page down next page MEASUREMENTS BYPASS Level 2...

Страница 24: ...1 222 223 V Phase to neutral measured AC UPS output voltages Iout 00 0 00 0 00 0 A Measured AC RMS load currents Current alarm messages Up previous page down next page MEASUREMENTS OUTPUT Page 2 Level...

Страница 25: ...n next page MEASUREMENTS DC Page 3 Level 3 Backup time 0000 min Calculated remaining time Current alarm messages Up previous page down next page MEASUREMENTS DC Page 4 Level 3 ENTER EXIT ENTER exit to...

Страница 26: ...32 activity indicator for com1 and com2 MAX Power 60000 VA Maximum ups output power as VA Nom 220 050 220 050 Nominal input output voltage and frequency Current alarm messages Up previous page down ne...

Страница 27: ...adjust BL DELAY CLOSED Backlight delay BL DIM CLOSED Back light half option selection Current alarm messages Up upper line down next line or options ENTER select an option OPTIONS LCD OPTIONS Page 3 L...

Страница 28: ...PTIONS COMMUNICATION OPTIONS Page 4 Level 3 RELAY 7 Left and right buton relay function selection option RELAY 8 Left and right buton relay function selection option RELAY 9 Left and right buton relay...

Страница 29: ...PTIONS Page 3 Level 3 ENTER EXIT ENTER exit to upper menu Current alarm messages Up previous page down next page Level 3 Bypass options VAT transfer ON OFF Page1 Gen set bypass ON OFF Page1 Gen set sy...

Страница 30: ...ND ON OFF Left and right disable alarm buzzer MIMIC LED TEST ENTER lamp test Current alarm messages Up upper line down next line or options ENTER apply command COMMAND MENU Page 4 Level 2 ENTER EXIT E...

Страница 31: ...on recorded maximum power ENTER FAULT RESET ENTER fault reset Current alarm messages Up upper line down next line SERV CE MENU Page 2 Level 2 FAN MAINT 01000 Remaining hours to FAN maintenance BAT MAI...

Страница 32: ...00 or R00 Alarm is shown on the LCD panel we understand that there is a system fault at the related module We saw the message in the A00 INV FAULT XXXX or R00 PFC FAULT XXXX format Numbers shown in X...

Страница 33: ...s INV CODE 0XXX Current inverter mod le status code A00 INV FAULT XXXX Hata XXXX fault occured at the inverter module CALL SERVICE A01 O P OVERCURRENT Alarm IGBT saturation alarm on inverter module A0...

Страница 34: ...upted A36 INV DC DOWN Warning DC BUS voltage is less then 120 volts DC A37 AC CURR LIMIT Warning Inverter output current limited A38 FUSE FAILURE Warning Any fuse in UPS is blowned A39 PSP FAILURE Ala...

Страница 35: ...time 369 Overcurrent occured on L3 phase longer then allowed time 170 On L1 phase momentary short circuit conditions occured but now inverter is running 270 On L2 phase momentary short circuit conditi...

Страница 36: ...ce at the UPS output 383 L3 phase by pass SCR must be on but there is only positive alternance at the UPS output 184 L1 phase by pass SCR must be on but there is only negative alternance at the UPS ou...

Страница 37: ...t at the UPS output there is no 3 phase AC voltage INV Control activity status codes 612 INV Over RS232 interface battery quantity updated 613 INV Over CAN1 interface battery quantity updated 614 INV...

Страница 38: ...eived 651 INV Over CAN1 interface generator mode start command received 652 INV Over RS232 interface start sleep mode command received 653 INV Over CAN1 interface start sleep mode command received 654...

Страница 39: ...ge is higher then R2131 adjustment 1401 PFC DC bus voltage is higher the R2131 adjustment 1402 PFC DC LEM current sensor error 1403 PFC module DC BUS voltage high alarm repeated 4 times within R2166 t...

Страница 40: ...received 1643 PFC over CAN1 interface cancel battery test command received 1644 PFC over RS232 interface start boost charge mode command received 1645 PFC over CAN1 interface start boost charge mode...

Страница 41: ...frequency is normal R06 OVERTEMPERATURE Overtemperature at rectifier module call service R07 BLACKOUT There is a short blackout at the AC input voltage of the UPS this is temporary wait until the AC...

Страница 42: ...if hot use air cooling system If batteries are internal check the UPS ambient temperature if normal call service L02 TH2 TEMP HIGH L04 TH2 TEMP LOW UPS TH2 cabinet inside temperature is out of tolera...

Страница 43: ...nt is normal A07 SHORT CIRCUIT There is short circuit at the output of the UPS check installation and loads A08 ON MAINTENANCE The maintenance by pas switch of the UPS is ON 1 position there is a lock...

Страница 44: ...ds the mesage will be cleared A26 BATTERY LOW The DC BUS or battery voltage of the UPS is low still UPS is running but DC voltage is going down If this alarm occures during mains failure it means that...

Страница 45: ...very high higher then 150 the UPS limited the output current This status is temporary but if continues call service A38 FUSE FAILURE Call service A39 PSP FAILURE Call service A43 USER LOGIN User logg...

Страница 46: ...allel therefore provides increased reliability for the critical load connected to the parallel system output If power demand increases in a certain UPS application exceeding the power rating of an alr...

Страница 47: ...LLEL mode This mode is used for operation of at least two 1 1 configuration UPS units connected in parallel for increased reliability If this mode is selected the load is shared equally by each UPS av...

Страница 48: ...llel Port 2 Parallel Port 1 Parallel Port 2 Parallel Port 1 Parallel Port 2 Figure 4 2 c 4 units in parallel All the units must be set for the same operation mode and must have a different UPS number...

Страница 49: ...tribution board Figure 4 3 DS300H Series Parallel UPS Power Connections BATTERIES U V W N LOAD FUSES AC BYPASS AC INPUT MAIN AC INPUT AC DISTRIBUTION U1 V1 W1 N1 U2 V2 W2 N2 UPS1 K3 K2 K2 K4 K5 K6 K7...

Страница 50: ...m Restart Change operating mode and Restart UPS again Returning to fault Directly fault In parallel UPS system master and slave UPS operating modes must be same 803 Status code Status Inverter system...

Страница 51: ...allel system and restart again If the code is still showned call service 820 Status code Status Inverter alarm Description In parallel system while in slave mode MASTER communication lost for 8 period...

Страница 52: ...ystem if the same A H rating batteries are used at each UPS the battery discharge timebe same for each UPS If the other UPS is continue to run check the batteries of this UPS Call service 825 Status c...

Страница 53: ...E UPS L2 phase output is not connected to load Restart 831 Status code causes are valid for L2 phase 833 Status code Status Inverter warning Description SLAVE UPS L3 phase output is not connected to l...

Страница 54: ...verter warning Description MASTER UPS send transfer the load to UPS command Restart Returning to fault 852 Status code Status Inverter warning Description Enter to sleep mode command received from par...

Страница 55: ...kages output switch turned on after 2 seconds MASTER mode started Restart Returning to fault 858 Status code Status Inverter warning Description In parallel system there is no MASTER communication pac...

Страница 56: ...3 Turn on S7 On Off switch to 1 position LCD panel activates and INV RESET or PFC RESET message appears on the display meaning that the rectifier starts to operate 4 Turn ON S4 AC Output switch switc...

Страница 57: ...this case bypass voltage is connected directly to the output of UPSs and the critical load is supplied via maintenance bypass switch No AC or DC supply is connected to the inside and the circuits of U...

Страница 58: ...urn off S7 On Off switch to 0 position 3 Turn off S5 Battery switch to 0 position 4 Turn off S2 Bypass switch to 0 position 5 Turn off S1 AC Input switch to 0 position After performing the above proce...

Страница 59: ...nt But do not turn on these loads again during battery operation After a short period of time when the line voltage is available again UPS returns to normal operation automatically and the alarm messa...

Страница 60: ...ANCE counter BATTERY MAINTENANCE counter GENERAL MAINTENANCE counter This type of protective maintenance prevents small problems turning up to big failures DS300H Series UPS has been designed to requi...

Страница 61: ...one at least two times a year in order to provide safe and efficient operation your UPS and battery group UPS generates a warning message when the maintenance time has expired 7 5 Storage Conditions a...

Страница 62: ...60...

Страница 63: ...wed while trying to indicate the error Fault determination First step is to record the messages indicator panel LEDs operating parameter values and last status of switches This must be done before Fix...

Страница 64: ...RY TEST until battery low alarm CANCEL battery test Turn off UPS output voltage immediately SHUTDOWN Turn off UPS output voltage after delay WAITING SHUTDOWN Turn off UPS output voltage SHUTDOWN and t...

Страница 65: ...phone and listen the modem sound NOTE Not all the modems are compatible with the command set on UPS In such a case modem should be set by connecting a PC 9 3 2 Functioning Principle The remote operato...

Страница 66: ...emperature sensor input 11 12 Function programmable relay contact output 2 13 14 Function programmable relay contact output 3 15 16 Function programmable relay contact output 4 ATTENTION Maximum 42Vac...

Страница 67: ...its economically as well as supporting to create a cleaner environment and protecting our world sources 2 Every electric powered device is designed appropriate to a defined power level Device capacity...

Страница 68: ......

Страница 69: ...AGKK12881 09 2021...

Отзывы: