52
842 Status code
Status
Inverter warning
Description
MASTER UPS L2 phase output is not connected to load
Restart
--
841 Status code causes are valid for L2 phase
843 Status code
Status
Inverter warning
Description
MASTER UPS L3 phase output is not connected to load
Restart
--
841 Status code causes are valid for L3 phase
850 Status code
Status
Inverter warning
Description
MASTER UPS send by-pass transfer command
Restart
--
Returning to fault
--
851 Status code
Status
Inverter warning
Description
MASTER UPS send transfer the load to UPS command
Restart
--
Returning to fault
--
852 Status code
Status
Inverter warning
Description
Enter to sleep mode command received from parallel system
Restart
--
Returning to fault
--
853 Status code
Status
Inverter warning
Description
Exit from sleep mode command received from parallel system
Restart
--
Returning to fault
--
854 Status code
Status
Inverter warning
Description
REPO (remote emergency power off) command received from parallel system
Restart
--
Returning to fault
--
855 Status code
Status
Inverter warning
Description
Enter to MASTER mode command received from parallel system
Restart
--
Returning to fault
--
Содержание DS300H Series
Страница 1: ...DS300H SERIES DSP Controlled UPS 40 60 80 kVA 3 Phase In 3 Phase Out USER MANUAL...
Страница 2: ......
Страница 17: ...15 30x12V Batteries 30x12V Batteries 0 360V 360V 0 K1 K2 K3 K2 Figure 2 3 External Battery Connections 60x12V...
Страница 18: ...16 Figure 2 3a DS300H Series 40 60 80 KVA Internal Battery Connections 2x30 60x12V 7Ah...
Страница 62: ...60...
Страница 68: ......
Страница 69: ...AGKK12881 09 2021...