28
TIME MENU Page 4 (Level 2)
ENTER <UPDATE>
ENTER apply new time and date settings
……………………………..
Current alarm messages
Up previous page ,down next page ,ENTER apply new time and date settings
TIME MENU Page 5 (Level 2)
ENTER - EXIT
ENTER exit to upper menu
……………………………..
Current alarm messages
Up previous page ,down next page
3.2.7 SERVICE MENU
This menu contains some helpfull service information and some commands.
Use up and down buttons to move cursor on submenu at the end of page you move to next page.
SERV
İ
CE MENU Page 1 (Level 2)
>HOURMETER:00075
Total operating hour of the UPS
MAXLOAD:015 020 025 %
From power on recorded maximum power
ENTER<FAULT RESET>
ENTER fault reset
……………………………..
Current alarm messages
Up upper line ,down next line
SERV
İ
CE MENU Page 2 (Level 2)
FAN MAINT: 01000
Remaining hours to FAN maintenance
BAT MAINT :01200
Remaining hours to battery maintenance
GEN.MAINT: 00500
Remaining hours to general maintenance
……………………………..
Current alarm messages
If maintenance counters are disabled CANCEL word is shown.
SERV
İ
CE MENU Page 3 (Level 2)
>LOGOUT: --
ENTER Exit from service login status
……………………………..
Current alarm messages
Up previous page ,down next page ,ENTER Logout from login status
SERV
İ
CE MENU Page 4 (Level 2)
ENTER - EXIT
ENTER to EXIT from menu and
return to upper level
……………………………..
current alarms appears sequentially
3.2.8 ADJUST MENU
This menu is prepared for service purposes there is no user adjustable parameter in this menu.