48
Note:
As seen in the figure, the outputs of parallel UPS units should be connected to each other
using an AC distribution board.
ATTENTION!!!
The cables from input distrubution panel to the UPS by-pass input must be of the same size and
length for proper bypass load sharing.
The cables from each UPS output to the load distribution panel must be of the same size and length
for proper load sharing during parallel operation.
Figure 4.3
DS200 Series Parallel UPS Power Connections
BATTERIES
U V W N
LOAD
FUSES
AC
BYPASS AC INPUT
MAIN AC INPUT
AC DISTRIBUTION
U1
V1
W1
N1
U2
V2
W2
N2
+
-
+
-
UPS1
K3
K2
K2
K
4
K
5
K
6
K
7
K
8
K
9
K
1
0
K
1
1
K12 K13 K14
K1
U V W N
AC OUTPUT1
+
-
+
-
BATTERIES
UPS2
K3
K2
K2
K
4
K
5
K
6
K
7
K
8
K
9
K
1
0
K
1
1
K12 K13 K14
K1
U V W N
AC OUTPUT2
FUSES
+
-
+
-
BATTERIES
UPS3
K3
K2
K2
K
4
K
5
K
6
K
7
K
8
K
9
K
1
0
K
1
1
K12 K13 K14
K1
U V W N
AC OUTPUT3
FUSES
LOAD BRAKE
SWITCH
Содержание DS200 Series
Страница 1: ...DS200 SERIES DSP Controlled UPS DS210 DS215 DS220 DS230 3 Phase In 3 Phase Out USER MANUAL...
Страница 2: ......
Страница 17: ...14 30x12V Batteries 30x12V Batteries 0 360V 360V 0 K1 K2 K3 K2 Figure 2 3 External Battery Connections 60x12V...
Страница 18: ...15 K3 K1 K2 K2 Figure 2 3 DS200 Series 10 15 20 30 KVA Internal Battery Connections 2x30 60x12V 7Ah...
Страница 66: ......
Страница 67: ...AGKK12001 09 2021...