background image

 

  

 

29

 
 

R24 WAITING DC BUS 

Warning  Rectifier is waiting DC BUS to raise for startup 

R25 BATTERY FAILURE 

Warning  Battery test failed 

R26 BATT TEMP SENSOR 

Warning  Battery temperature sensor is defected or not connected 

R27 BATT TEMP HIGH 

Warning  Battery ambient temperature is high 

R29 PFC RESET 

Warning  Rectifier module power on 

R30 PLEASE WAIT 

Warning  Rectifier waits as adjusted startup delay 

R31 RECTIFIER START 

Warning  Rectifier is in soft start stage 

 

Panel module alarm codes 

L01 TH1 TEMP HIGH 

Warning  TH1 temperature is high 

L02 TH2 TEMP HIGH 

Warning  TH2 temperature is high 

L03 TH1 TEMP LOW 

Warning  TH1 temperature is low 

L04 TH2 TEMP LOW 

Warning  TH2 temperature is low 

L05 FAN MAINT 

Warning  FAN maintenance time 

L06 BATTERY MAINT 

Warning  Battery maintenance time 

L07 OPT MAINTENANCE 

Warning  Optional maintenance time 

L08 TH1 SENSOR FAIL 

Warning  TH1 temperature sensor failure 

L09 TH2 SENSOR FAIL 

Warning  TH2 temperature sensor failure 

L10 ENTER FAULT RESET 

Warning  UPS is waiting fault reset for startup 

L11 BATT CB OPEN 

Warning  External interactive battery switch is off 

L12 GENERAL MAINT 

Warning  General maintenance time 

L13 PFC CAN COMM ERR 

Warning  PFC module CAN communication timeout 

L14 INV CAN COMM ERR 

Warning  INV module CAN communication timeout 

 
 

Inverter module alarm codes 

INV CODE = 0XXX 

 

Current inverter modüle status code 

A00 INV FAULT =   XXXX 

Hata 

XXXX fault occured at the inverter module 

CALL SERVICE ! 

A01 O/P OVERCURRENT 

Alarm 

IGBT saturation alarm on inverter module 

A02 OVERTEMP SHUT 

Alarm 

Overtemperature at inverter power module 

A03 BATT HIGH 

Alarm 

Inverter module measured battery voltage high 

A04 OUTPUT V.LOW 

Alarm 

Inverter output voltage is low 

A05 OUTPUT V.HIGH 

Alarm 

Inverter output voltage is high 

A06 OVERLOAD SHUT 

Alarm 

Overload at UPS output 

A07 SHORT CIRCUIT 

Alarm 

Short circuit at UPS output 

A08 ON MAINTENANCE 

Alarm 

Maintenance by-pass switch on 

A09 MANUAL BYPASS 

Alarm 

Load is transferred to by-pass from front panel 

A10 BATTERY LOW SHUT 

Alarm 

Inverter measured battery voltage is low (shutdown level) 

A11 REPO STOP 

Alarm 

External REPO input signal sensed 

A12 DC BALANCE BAD 

Alarm 

Before inverter start fitler capacitors dont discharged 

A13 PEAK CURRENT 

Alarm 

Very high current at the UPS output 

A14 INV NOT START 

Alarm 

Inverter module start failed 

A17 BYPASS FAILURE 

Warning  By-pass input voltage failure 

A18 BYPASS VOLT 

Warning  By-pass input voltage out of tolerance 

A19 BYP FREQ.TOLER 

Warning  By-pass input frequency out og tolerance 

A20 OVERLOAD 

Warning  Currently the load exceeded 100% capacity 

A21 OVERTEMP 

Warning  Currently inverter power modul heatsink temperature is high 

A22 OUTPUT OFF 

Warning  There is no UPS output voltage 

A23 ON BYPASS 

Warning  Load is on bypass 

A24 REVERSE CURRENT 

Warning  Regenerative backfeed to UPS output 

 
 
 
 
 
 
 

Содержание DS200 Series

Страница 1: ...DS200 SERIES DSP Controlled UPS DS210 DS215 DS220 DS230 3 Phase In 3 Phase Out USER MANUAL...

Страница 2: ......

Страница 3: ...scriptions 16 3 2 1 MEASUREMENTS menu 19 3 2 2 ALARM LOGS menu 22 3 2 3 INFORMATION menu 22 3 2 4 OPTIONS menu 22 3 2 5 COMMAND menu 26 3 2 6 TIME menu 26 3 2 7 SERVICE menu 27 3 2 8 ADJUST menu 27 3...

Страница 4: ...56 7 1 Scheduled maintenance 56 7 2 Daily checks 56 7 3 Weekly checks 56 7 4 Annual Maintenance 57 7 5 Storage conditions and transportation of ups 57 VIII FAULTS AND TROUBLESHOOTING 58 8 1 General Pr...

Страница 5: ...C power is disconnected To reduce the risk of electric shock disconnect the UPS from the mains supply before installing a computer interface signal cable Reconnect the power cables only after signalin...

Страница 6: ...ternal voltage and frequency regulating software which ensures that its output to the critical load is maintained within close tolerances independent of voltage and frequency variations on the mains p...

Страница 7: ...ble polarity battery with common terminal Automatic and manual battery test and battery temperature compensation features 3 separate maintenance clock counters Battery charge with current limiting Aut...

Страница 8: ...Switch S4 F7 F8 F9 Output Switch Fuse S5 F10 F11 F12 Battery Switch Fuse K1 Rectifier Input Contactor K2 Inverter Output Contactor Rectifier Charger 3 PHASE MAINS I P Battery Dual Polarity Maintenanc...

Страница 9: ...lack outs when it is connected to either static or maintenance bypass supply 1 2 2 OPERATING CONDITIONS OF UPS UPS may be in one of the following operating conditions A Normal Operation If Mains suppl...

Страница 10: ...B9 Female Relay Output Contacts and Inputs S7 On Off Switch S5 Battery Input F10 F11 F12 S1 AC Input F1 F2 F3 S3 Maintenance By pass S2 By Pass F4 F5 F6 S4 AC Output F7 F8 F9 SNMP Adapter Optional COM...

Страница 11: ...ntenance By pass S2 By Pass F4 F5 F6 S4 AC Output F7 F8 F9 COM1 RS232 Communication Socket DB9 Female S7 On Off Switch SNMP Adapter Optional COM2 RS232 Communication Socket DB9 Female Relay Output Con...

Страница 12: ...Efficiency 100 Load up to 94 Load Crest Factor 3 1 Output Voltage THD linear load 2 Overload 125 Load 10min 150 Load 1min BATTERY Total Number 60 blocks 12V 2x30 serial 60 batteries Float Charge Volta...

Страница 13: ...age is noted call the shipper immediately and retain the shipping carton and the UPS 2 Carefully open the carton and take the UPS out 3 Retain the carton and packing material for future use Unit packa...

Страница 14: ...0 2 x 16 10 16mm 2 terminal 16mm 2 terminal 30 16 3 x 16 16 16mm 2 terminal 16mm 2 terminal NOTES The neutral conductor should be sized for 1 5 times the output bypass phase current These recommendati...

Страница 15: ...shown on the power connection label of the UPS U1 V1 and W1 phase of the incoming 3 phase supply are used as the bypass inputs under normal conditions if there is not a separate bypass supply split b...

Страница 16: ...with a suitable load Any battery with terminal voltage less than 10 5V must be charged before installation 3 Please check the battery connecting hardware and documents cables trays connection diagram...

Страница 17: ...14 30x12V Batteries 30x12V Batteries 0 360V 360V 0 K1 K2 K3 K2 Figure 2 3 External Battery Connections 60x12V...

Страница 18: ...15 K3 K1 K2 K2 Figure 2 3 DS200 Series 10 15 20 30 KVA Internal Battery Connections 2x30 60x12V 7Ah...

Страница 19: ...or lamp L4 Rectifier run pilot lamp L5 Battery operation indicator lamp L6 Load on UPS indicator lamp L7 Output switch on indicator lamp There are 5 control buttons on the UPS Front panel ENTER button...

Страница 20: ...l measurements ENTER EXIT ALARM LOGS UPS LOG RECORD Page1 ENTER CLEAR LOG Page1 ENTER EXIT INFORMATION RS232 Comm 1 2 Page1 Maximum UPS power Page1 Nominal voltage and frequency Page1 Inverter firmwar...

Страница 21: ...ut command Page3 ENTER EXIT PASSWORD Getting service code Page1 Type service password Page1 Type user password Page1 ENTER EXIT ADJUST in English Group adjustments Automatic settings Inverter factory...

Страница 22: ...alarm messages Up previous page down next page MEASUREMENTS INPUT Page 3 Level 3 ENTER EXIT ENTER exit to upper menu Current alarm messages Up previous page down next page MEASUREMENTS BYPASS Level 2...

Страница 23: ...1 222 223 V Phase to neutral measured AC UPS output voltages Iout 00 0 00 0 00 0 A Measured AC RMS load currents Current alarm messages Up previous page down next page MEASUREMENTS OUTPUT Page 2 Level...

Страница 24: ...n next page MEASUREMENTS DC Page 3 Level 3 Backup time 0000 min Calculated remaining time Current alarm messages Up previous page down next page MEASUREMENTS DC Page 4 Level 3 ENTER EXIT ENTER exit to...

Страница 25: ...32 activity indicator for com1 and com2 MAX Power 60000 VA Maximum ups output power as VA Nom 220 050 220 050 Nominal input output voltage and frequency Current alarm messages Up previous page down ne...

Страница 26: ...adjust BL DELAY CLOSED Backlight delay BL DIM CLOSED Back light half option selection Current alarm messages Up upper line down next line or options ENTER select an option OPTIONS LCD OPTIONS Page 3 L...

Страница 27: ...PTIONS COMMUNICATION OPTIONS Page 4 Level 3 RELAY 7 Left and right buton relay function selection option RELAY 8 Left and right buton relay function selection option RELAY 9 Left and right buton relay...

Страница 28: ...PTIONS Page 3 Level 3 ENTER EXIT ENTER exit to upper menu Current alarm messages Up previous page down next page Level 3 Bypass options VAT transfer ON OFF Page1 Gen set bypass ON OFF Page1 Gen set sy...

Страница 29: ...ND ON OFF Left and right disable alarm buzzer MIMIC LED TEST ENTER lamp test Current alarm messages Up upper line down next line or options ENTER apply command COMMAND MENU Page 4 Level 2 ENTER EXIT E...

Страница 30: ...on recorded maximum power ENTER FAULT RESET ENTER fault reset Current alarm messages Up upper line down next line SERV CE MENU Page 2 Level 2 FAN MAINT 01000 Remaining hours to FAN maintenance BAT MAI...

Страница 31: ...0 or R00 Alarm is shown on the LCD panel we understand that there is a system fault at the related module We saw the message in the A00 INV FAULT XXXX or R00 PFC FAULT XXXX format Numbers shown in X d...

Страница 32: ...s INV CODE 0XXX Current inverter mod le status code A00 INV FAULT XXXX Hata XXXX fault occured at the inverter module CALL SERVICE A01 O P OVERCURRENT Alarm IGBT saturation alarm on inverter module A0...

Страница 33: ...upted A36 INV DC DOWN Warning DC BUS voltage is less then 120 volts DC A37 AC CURR LIMIT Warning Inverter output current limited A38 FUSE FAILURE Warning Any fuse in UPS is blowned A39 PSP FAILURE Ala...

Страница 34: ...time 369 Overcurrent occured on L3 phase longer then allowed time 170 On L1 phase momentary short circuit conditions occured but now inverter is running 270 On L2 phase momentary short circuit conditi...

Страница 35: ...ce at the UPS output 383 L3 phase by pass SCR must be on but there is only positive alternance at the UPS output 184 L1 phase by pass SCR must be on but there is only negative alternance at the UPS ou...

Страница 36: ...t at the UPS output there is no 3 phase AC voltage INV Control activity status codes 612 INV Over RS232 interface battery quantity updated 613 INV Over CAN1 interface battery quantity updated 614 INV...

Страница 37: ...eived 651 INV Over CAN1 interface generator mode start command received 652 INV Over RS232 interface start sleep mode command received 653 INV Over CAN1 interface start sleep mode command received 654...

Страница 38: ...ge is higher then R2131 adjustment 1401 PFC DC bus voltage is higher the R2131 adjustment 1402 PFC DC LEM current sensor error 1403 PFC module DC BUS voltage high alarm repeated 4 times within R2166 t...

Страница 39: ...received 1643 PFC over CAN1 interface cancel battery test command received 1644 PFC over RS232 interface start boost charge mode command received 1645 PFC over CAN1 interface start boost charge mode...

Страница 40: ...frequency is normal R06 OVERTEMPERATURE Overtemperature at rectifier module call service R07 BLACKOUT There is a short blackout at the AC input voltage of the UPS this is temporary wait until the AC...

Страница 41: ...if hot use air cooling system If batteries are internal check the UPS ambient temperature if normal call service L02 TH2 TEMP HIGH L04 TH2 TEMP LOW UPS TH2 cabinet inside temperature is out of tolera...

Страница 42: ...nt is normal A07 SHORT CIRCUIT There is short circuit at the output of the UPS check installation and loads A08 ON MAINTENANCE The maintenance by pas switch of the UPS is ON 1 position there is a lock...

Страница 43: ...ds the mesage will be cleared A26 BATTERY LOW The DC BUS or battery voltage of the UPS is low still UPS is running but DC voltage is going down If this alarm occures during mains failure it means that...

Страница 44: ...very high higher then 150 the UPS limited the output current This status is temporary but if continues call service A38 FUSE FAILURE Call service A39 PSP FAILURE Call service A43 USER LOGIN User logg...

Страница 45: ...n ATTENTION BYPASS VOLTAGE WILL BE CONNECTED TO THE OUTPUT TERMINALS OF UPS WHEN THE ON OFF SWITCH S7 IS SWITCHED ON 4 Turn on S7 On Off switch to 1 position LCD panel activates and INV RESET or PFC R...

Страница 46: ...n this case bypass voltage is connected directly to the output of UPS and the critical load is supplied via maintenance bypass switch No AC or DC supply is connected to the inside and the circuits of...

Страница 47: ...the Ah capacity charge status age of the batteries actual load percentage of UPS and the ambient temperature Otherwise critical loads will be out of power at the end of battery autonomy time A26 BATT...

Страница 48: ...llel therefore provides increased reliability for the critical load connected to the parallel system output If power demand increases in a certain UPS application exceeding the power rating of an alre...

Страница 49: ...LLEL mode This mode is used for operation of at least two 1 1 configuration UPS units connected in parallel for increased reliability If this mode is selected the load is shared equally by each UPS av...

Страница 50: ...in UPSs Figure 4 2 a 2 units in parallel if port2 jumper is Parallel Port 1 Parallel Port 2 Parallel Port 1 Parallel Port 2 Figure 4 2 DS200 Series Parallel UPS Signal Cable PCC06 Connections Figure...

Страница 51: ...ion panel must be of the same size and length for proper load sharing during parallel operation Figure 4 3 DS200 Series Parallel UPS Power Connections BATTERIES U V W N LOAD FUSES AC BYPASS AC INPUT M...

Страница 52: ...art Install parallel communication board and Restart UPS again Returning to fault Directly fault 804 Status code Status Inverter system fault Description Parallel communication connector disconnected...

Страница 53: ...eturning to fault Fault code 821 Status code Status Inverter alarm Description MASTER syncron failed while SLAVE UPS inverter stopped Restart Wait until UPS provide MASTER synchronization Returning to...

Страница 54: ...tart f mains input voltage is okay automatic Returning to fault Check the followings Check the mains input power of the UPS Check the battery status of this UPS Call service 826 Status code Status Inv...

Страница 55: ...is status code Check L1 phase UPS output fuse Check L1 phase output switch LEG Check the SLAVE UPS L1 phase output terminal for bad connection Check the SLAVE UPS L1 phase output cable to load L1 phas...

Страница 56: ...nter to MASTER mode command received from parallel system Restart Returning to fault 856 Status code Status Inverter warning Description UPS is currently in SLAVE mode MASTER function transferred to a...

Страница 57: ...3 Turn on S7 On Off switch to 1 position LCD panel activates and INV RESET or PFC RESET message appears on the display meaning that the rectifier starts to operate 4 Turn ON S4 AC Output switch switc...

Страница 58: ...this case bypass voltage is connected directly to the output of UPSs and the critical load is supplied via maintenance bypass switch No AC or DC supply is connected to the inside and the circuits of U...

Страница 59: ...ANCE counter BATTERY MAINTENANCE counter GENERAL MAINTENANCE counter This type of protective maintenance prevents small problems turning up to big failures DS200 Series UPS has been designed to requir...

Страница 60: ...one at least two times a year in order to provide safe and efficient operation your UPS and battery group UPS generates a warning message when the maintenance time has expired 7 5 Storage Conditions a...

Страница 61: ...wed while trying to indicate the error Fault determination First step is to record the messages indicator panel LEDs operating parameter values and last status of switches This must be done before Fix...

Страница 62: ...Y TEST until battery low alarm CANCEL battery test Turn off UPS output voltage immediately SHUTDOWN Turn off UPS output voltage after delay WAITING SHUTDOWN Turn off UPS output voltage SHUTDOWN and tu...

Страница 63: ...e set by connecting a PC 9 3 2 Functioning Principle The remote operator by means of a PC and a modem device and using the remote connection function of the control software calls the UPS through the...

Страница 64: ...16 Function programmable relay contact output 4 ATTENTION Maximum 42Vac or 60Vac voltage may be applied to the dry contacts of the interface Dry contact relay outputs are NO Normally Open type ie the...

Страница 65: ...its economically as well as supporting to create a cleaner environment and protecting our world sources 2 Every electric powered device is designed appropriate to a defined power level Device capacity...

Страница 66: ......

Страница 67: ...AGKK12001 09 2021...

Отзывы: