Page 7
The TERRA heat pump must be installed in a frost
protected room by a certified Installation company.
The room temperature should be in between 5°C
and 35°C.
The installation in wet rooms or rooms that are at
high risk of dust or explosives is prohibited
The TERRA heat pump should be installed on a leve-
led, straight and capable ground (e.g. concrete) to
avoid noise conduction. If floor screed is used, the
screed and floor insulation have to be omit to ensure
a silent operation.
A minimum distance of 60cm is required in front of
and next to the heat pump. (See illustration on by)
The appropriated laws, regulations and Norms have
to be taken into notice, specially the EN 378 Part 1..
To avoid noise conduction via the piping, the enclo-
sed flexible connection pipes for the flow and return,
as well as for the brine in- and outlet resp. the
groundwater in- and outlet have to be used.
For a leveled installation of the TERRA heat pump
there are adjustable feet provided.
The en-
closed connection pipes must not be kinked!
2.8 Installation
min. 600
750
850
TERRA
min.
600
The minimum distances have to be provided!
The minimum size of the boiler room has to be
provided!
The connection pipes have to be used!
Adjustable feed