5.10
UPS communication port
This port has two inputs used to monitor and report UPS status.
Recommended mating terminal block connector:
Tyco Electronics
p/n 284507-4 or p/n 284509-4
Pin-out:
pin 1 – 0V(logic ground)
pin 2 – PCS200 Input #4 (Battery Low)
pin 3 – 0V (logic ground)
pin 4 – PCS200 input #3 (Power Failure)
Input #3 and #4 status and log can be viewed with web interface by clicking on “I/O Control” link.
Most smart UPS devices have standard serial port (female D-SUB 9) with status information.
See connection table for PCS200 interfacing to smart UPS serial port.
PCS200 UPS COMM.
UPS serial port
Notes
pins
(female D-SUB 9)
1
4
0V (logic ground)
2
5
Battery Low, open-collector output from UPS.
Normally low (0V), goes high when low battery.
3
4
0V (logic ground)
4
2
Power Failure, RS232 level output from UPS.
Normally RS232 low level (-12V), goes to
RS232 high level (+12V) when line power failure.
5.11
Digital opto-isolated inputs
There are two general purpose inputs.
Recommended mating terminal block connector:
Tyco Electronics
p/n 284507-4 or p/n 284509-4
Pin-out:
Pin 1 – Input #2 Low-side
Pin 2 – Input #2 High-side
Pin 3 – Input #1 Low-side
Pin 4 – Input #1 High-side
Nominal input port voltage difference is +12V (operational from +5V to +20V).
Input #1 and #2 status and log can be viewed with web interface by clicking on “I/O Control” link.
See sample interface diagram below.