Terofire Plus Instruction Manual
7
CPU Fault lamp lit, internal buzzer sounding.
The processor has stopped running its program.
If no problems are found then reset the processor. Inside the panel on
the main circuit board are two push buttons marked CPU RESET
(SW1) and W/D RESET (SW2). Press CPU RESET followed by W/D
RESET.
Panel does not indicate fire when a call point or detector is tested.
Either a faulty call point/detector or wiring not as shown in diagrams.
Check the firing resistance of the device is 510 ± 200 ohms and ensure
end of line monitor is a 3k3 resistor or active end of line device.
Head removal not working.
Check compatible base is being used and is wired correctly. Either a
zener clamp base with a 3k3 end of line resistor or a schottky diode
base with an active end of line device must be used. If an active end of
line device is being used, check that the capacitor is fitted at the sense
zone terminals.