Panel Operation
Enabling the front panel buttons.
Before being able to access the Reset, Silence, Evacuate and Test
functions, the key switch in the top left of the panel must be turned
through 90° to the ON position.
Performing a lamp test.
If the panel is in its normal condition, pressing the Reset button will
cause the panel to perform a lamp test.
Resetting the panel after a fire is detected.
To reset the panel after a fire condition, press the Silence button
followed by the Reset button.
Resetting the panel.
If any of the panel functions have been activated, pressing the Reset
button will return the panel to its normal condition.
Silencing the alarms.
If a fire is detected, the panel will automatically activate the alarm
circuits. To silence the alarms, press the Silence button. The internal
buzzer will continue to sound until the Reset button is pressed.
Silencing the internal buzzer.
If a fault is detected by the panel, the internal buzzer will sound. To
silence the buzzer press the Silence button. The buzzer will continue to
bleep every 25 seconds. A CPU Fault cannot be silenced.
Manually sounding the alarms.
Pressing the Evacuate button will sound the alarms. To silence the
alarms after the Evacuate button has been pressed, press the Reset
button.
Using the one man test function.
To put a zone into test mode, press the Test button once. Zone 1 fault
lamp will be flashing. If zone 1 is to be put into test mode press the
Silence button once. Press the Test button again to move to zone 2.
Zone 2 fault lamp will be flashing, and if zone 1 was put into test mode,
zone 1 fault lamp will be lit. The Test button cycles through the zones
and the Silence button places the selected zone in test mode.