4.4 Diagnostics 

If  there  appears  a  failure  in  water  heater’s  performance,  it  will  be  signaled  by  displaying  the  proper  error  code  on  the 
control panel. Error codes are being displayed with the priority of their importance for the safety of use. 
If the symbols E1, E2, E3 or E6 flash, it is a signal that the water heater has been switched in safety mode. This lock status 
may be cancelled by turning on a water tap. If despite of this the water heater is still blocked it is necessary to contact service 
team. 

 

Error code 

Description 

 

 

Lack of flame 
If the Lack of flame is detected then gas Valle will be closed and water heater is Stopped for 30s (E1 is being displayed permanently). 
After  30  s  the  control  system  actuate  the  water  heater.  After  3  ignition  trials  (2  trials  for  LPG)  the  water  heater  will  be  blocked.  (It  is 
signalled with a flashing E1 error code displayed on LCD, what means that the water heater has been switched off in safety mode) 
 
Electric supply cables improperly connected 
The  control  of  the  water  heater  must  be  connect  to  a  power  source.  If  L  and  N  cables  are  improperly  connected,  the  control 
system is not able to detect a flame and it make an ignition trial until the water heater switches off in a safety mode. You will see 
E1 error code on the LCD. 
In such a case it s necessary to change L and N cobles in the socket. The water heater will switch on after it detects it is properly 
connected.

 

 

 

Water temperature In a heat exchanger exceeded 95

o

C. 

Gas valve is made closed – the heat process is stopped (You will see flashing  E2 error code on LCD, what means that the water heater 
has been switched off in safety mode)

 

 

 

Lack of pressure difference in a chimney system or there is a brake in differentia pressure switch’s circuit 
If a pressure difference between inlet air and outlet flue is not appropriate or there is no pressure difference, then: 

 

the gas valve is shut down, 

 

E3 error code is being displayed on LCD 

 

15 s – time needed to short contacts of a differential pressure switch 

 

If after 15 s the contacts are still open, the water heater will be switched off in safety mode. 

 

You will see flashing  E3 error code on LCD 

 

 

Damage In NTC temperature sensor’s circuit: 

 

the gas valve is shut down and a heat process is stopped 

 

E4 error code is being displayed permanently on LCD 

 

After removing the error reason the water heater will automatically return to its normal operation 

 

 

Damage in an electric system of control unit: 
(You will see flashing  E6 error code on LCD, what means that the water heater has been switched off in safety mode) 

 

 

Fault in gas unit’s modulator system

 

 

The water heater operates at its minimal output 

 

E7 error code is being displayed permanently on LCD 

 

After removing the error reason the water heater will automatically return to its normal operation

 

 

4.5 Switching off the heater 

In case of an anticipated long break in the heater operation disconnect the water heater from electric supply and close 
gas valve on the heater or on a gas cylinder (if applicable) 
If a room where the water heater is installed is exposed to temperatures below 0ºC, it is necessary to drain the heater 
out of water. 
In order to do this, cut off cold water supply, then undone a nut on the pipe supplying the water into the water unit and 
turn on the hot water tap. 

 
 

5. ADAPTING THE WATER HEATER TO COMBUSTING DIFFERENT TYPE OF GAS 

 

Adaptation of heater to another type of gas can be performed  

only by AUTHORIZED SERVICE COMPANY. 

NOTE!  

Heater supplied by the manufacturer, is suitable for gas shown on the nameplate. 
If you need to connect the device to a different type of gas than the type for which the device has been pre-equipped, check what type of gas can be 
adapted. 

 

Gases to which you can adjust the heater, are given on the nameplate-in the category of the device: 
Category:                                               II 

2E 3P

 

 

                                               II 

2E 3B/P

 

                                               II 

2H 3P 

                                               II 

2H 3B/P

 

                                               II 

2H 3B 

                                                                       

II 

2H 3+

                                                     

 
 
 

 
 
 
 

Family 2 – natural gases: 

 

2E-G20-13mbar 
2E-G20-20mba 
2H-G20-20mbar 
2H-G20-25mbar 

Family 3 – liquefied gases: 

 

3P-G31-37mbar 
3P-G31-50mbar 
3B/P-G30-30mbar 
3B/P-G30-37mbar 
3B/P-G30-50mbar 
3B-G30-28-30mbar 
3B-G30-50mbar 
3+-G30/G31-28-30/37mbar 

water heater is designed to 
combustion of gas from two 
families 

Содержание GT-19-03

Страница 1: ... przep ywowe ogrzewacze wody Instantaneous gas water heater Gas Durchlaufwassererhitzer INSTRUKCJA INSTALOWANIA I OBS UGI INSTALLATION AND OPERATION MANUAL INSTALLIERUNG UND BEDIENUNGANLEITUNG TA 1450 012 12 ...

Страница 2: ...y throughout the whole operational lifetime of the water heater We hope you will be satisfied with our product ÓÂÀÆÀÅÌÛÉ ÏÎÊÓÏÀÒÅËÜ Ïîçäðàâëÿåì ñ âûáîðîì âîäîíàãðåâàòåëÿ ïðîèçâîäñòâà ôèðìû Ïðåäëàãàåì Âàì ñîâðåìåííîå ýêîíîìíîå è ýêîëîãè åñêîå óñòðîéñòâî êîòîðîå ñîîòâåòñòâóåò âûñîêèì êà åñòâåííûì òðåáîâàíèÿì åâðîïåéñêèõ ñòàíäàðòîâ Ïåðåä íà àëîì ýêñïëóàòàöèè ïðîñèì âíèìàòåëüíî îçíàêîìèòñÿ ñ íàñòîÿùåé...

Страница 3: ...TSTART UP 10 4 2STARTING UPTHE HEATER 10 4 3WATERTEMPERATURE REGULATION 11 4 4DIAGNOSTICS 12 4 5SWITCHING OFFTHEHEATER 12 5 ADAPTING THE WATER HEATER TO COMBUSTING DIFFERENT TYPE OF GAS 12 6 MAINTENANCE 15 6 1CLEANING AHEAT EXCHANGER REMOVING DEPOSITS ANDSCALE 15 6 2BURNER MAINTENANCE 15 6 3CLEANING AWATER FILTER 15 6 4CLEANING A GASFILTER 15 6 5 CLEANING AWATER FLOW LIMITER 15 6 6CHECKING UP THEP...

Страница 4: ...take holes covering blanking off etc or uptake and flue ducts in a room and in the appliance Do not keep any containers with inflammable aggressive or strongly corrosive chemicals close to a water heater It is forbidden to keep or dry clothes or other inflammable objects on or nearby the appliance and flue ducts The service and maintenance operations of the water heater can be only performed by an...

Страница 5: ...keeps required tap water temperature Each water heater is destined to combust only one type of gas for example 2H G20 and the water heater must be fed only with this type of gas The water heater s type the group and type of gas as well as the service line pressure which the heater was designed for are marked on the packaging in the instruction manual and on the marking plate It is possible to adap...

Страница 6: ... voltage V 230 Protection degree IP44 Mounting dimensions Overall dimensions height width depth mm 585 360 220 Weight kg 16 5 Connecting ends spacing mm Fig 3 6 1 Gas coupling inch G Cold water coupling inch G Hot water coupling inch G Connector with a flue system see table 3 6 and table 7 1 mm 60 100 or 80 125 Or 2 separate systems 60x 60 lub 80x 80 Destination country GR 2 3 Protection equipment...

Страница 7: ...ty pin If you connect the heater to a permanent power supply electrical installation should be equipped with the heater disconnected from the power source Note The control of the water heater must be connect to a power source If L and N cables are improperly connected the control system is not able to detect a flame and it make an ignition trial until the water heater switches off in a safety mode...

Страница 8: ...h could disturb the proper operation of the heater e g increase the resistance of water flow in the system Fig 3 2 1 Taking off a front cover 3 3 Mounting the heater on the wall Maximal temperature of the appliance s surface does not exceed 85 C so it is not necessary to take a speci al care of inflammable build materials In case of building the heater over in a furniture system air supply necessa...

Страница 9: ... offtake 2 The ways of connecting C type water heaters to flue systems are presented on Fig 3 6 The ways of connecting C type water heaters with heat output 19 2 kW to flue systems in multistoreyed buildings are presented in separate section In such buildings it is possible to connect a water heater to common flue system that consists of separate common pipes with a diameter 120 mm such a system w...

Страница 10: ...protection against external factors NOTE Before connection the flue system to the heater remove the cap from the fan 3 6 1 Horizontal outlet of air flue system over a wall or over a roof H max acc to table 7 1 elbow 3 52 Connecting Adapter acc to table 7 1 max H 3 585 acc to table 7 1 with access eye concentric tee 90 acc to TERMET catalogue Scutcheon with a rubber gasket Minimal dimension of a ho...

Страница 11: ...m Fig 3 6 2 1 Hmax H1 H2 Lmax 1m loss on elbow 1m loss on tee Lmax max flue pipe length 3 6 3 Connecting to a common chimney system consisting of a air supply pipe and a flue pipe H 2 min 140 min 140 H1 min 140 to drain out condensate Floor drain with an access eye Concentric tee 90 drain board or an adapter with a drain board acc to table 7 1 Adapter 185 Chimney duct dimensions acc to table 7 1 F...

Страница 12: ...tem Fig 3 6 4 1 Fig 3 6 4 2 Note Horizontal air flue pipe should be installed with a slope 3º Fig 3 6 4 1 and Fig 3 6 4 2 so that the raining water coming into pipes will not flood the boiler and flow out the building It is not necessary to install draining board if the slope has been made The hose for condensate drain must be properly siphoned Calculation formula for a flue system Fig 3 6 4 1 Hma...

Страница 13: ...ith output GT 19 03 13 l min for the water heater with output GT 23 03 If hot water tap is set for maximum water flow and the set water temperature is high and the supplying water temperature is low in winter it is possible that the water heater because its parameters of output 19 2 kW 275 kcal or 23kW 330 kcal will not reach the set tap water temperature Because the minimum output of the water he...

Страница 14: ...contacts of a differential pressure switch If after 15 s the contacts are still open the water heater will be switched off in safety mode You will see flashing E3 error code on LCD Damage In NTC temperature sensor s circuit the gas valve is shut down and a heat process is stopped E4 error code is being displayed permanently on LCD After removing the error reason the water heater will automatically...

Страница 15: ... 01 130 10 12 2E G20 20mbar Z0082 01 00 01 120 2H G20 20mbar 2H G20 25mbar 3P G31 37mbar Z3524 01 00 01 85 3P G31 50mbar 3B P G30 30mbar Z3525 01 00 01 80 3B P G30 37mbar 3B P G30 50mbar 3B G30 28 30mbar 3B G30 50mbar 3 G30 G31 28 30 37mbar 5 2 Changing the parameters of the controller Parameters r1 starting power range of changes 0 99 r2 maximum power range of changes 0 99 factory setting 99 r3 t...

Страница 16: ...ease of the minimum pressure of the gas outlet After you complete the regulation connect the wires supplying the coil of modulator z After completing the adjustment check the minimum and maximum pressures If necessary readjust the pressure fit the protective cap k Check the electrical connections to the modulator coil Check and carefully seal the pressure control points by tightening the threaded ...

Страница 17: ... 5 Cleaning a water flow limiter The water heater is equipped with a water flow limiter which is shown in the Fig 4 3 2 The water flow limiter provides the maximal flow 11 l min for water heater with output 19 2kW 13 l min for water heater with output 23kW Pollutions in a water flow limiter can cause a lower water flow In order to clean a water flow limiter unscrew a nut situated on an inlet pipe ...

Страница 18: ...241 60 1 Vertical draining board OKP 241 60 1 System elements acc with system design acc to TERMET catalogue 1set Zestaw spalinowo powietrzny Concentric system 60 100 Fig 3 6 3 1 11 Concentric adapter ADK 505 60 1 Concentric tee 90 with access eye TKR 222 60 1 Flue elbow 90 with a bracket KSW 122 60 1 Vertical draining board OSP 151 60 1 System elements acc with system design acc to TERMET catalog...

Страница 19: ......

Страница 20: ...St 13 58 160 Œwiebodzice Polska Poland Export Department tel 48 74 854 68 90 Marketing Department tel 48 74 854 25 49 D uga Str 13 58 160 Œwiebodzice Polska Polen Exportabteilung Tel 48 74 854 68 90 Marketingabteilung Tel 48 74 854 25 49 www termet com pl export termet com pl termet termet com pl serwis termet com pl sprzedaz termet com pl market termet com pl 58 160 Ïîëüøà Îòäåë ýêñïîðòà 48 74 85...

Отзывы: