Operating time
Current
200%
2.5
0.1
1000%
Ramp characteristic curve
(“L” or “R” characteristic)
I
sd
t
sd
6
Over-current Releases (OCRs)
The AGR series of over-current releases (OCRs) featuring high reliability and multiple protection capabilities is available for
TemPower2
. Controlled by an internal 16-bit microprocessor, the OCR provides reliable protection against overcurrent.
The OCR range is divided into three groups: L-characteristic, R-characteristic (both for general feeder) and S-characteristic (for
generator protection).
Each group consists of:
Type AGR-11B: Standard OCR with adjustment dial
Type AGR-21B,22B: Standard OCR with L.C.D.
Type AGR-31B: Enhanced OCR with backlit L.C.D.
Optional protection functions of the OCR include those against ground fault, earth leakage, undervoltage and reverse power.
Pre-trip alarm function can also be installed.
Protective functions
q
Adjustable long time-delay trip function LT
RMS sensing is used to accurately read through distorted wave-
forms.
In addition to the standard L and S-characteristics, the R-char-
acteristic is available in five types for long time-delay trip.
The R-characteristic can be used to give selectivity with e.g.
fuses. (See P. 8).
HOT start mode (applicable to L-characteristic of AGR-
21B,31B)
HOT or COLD start mode is user-selectable.
In HOT start mode, the OCR operates faster than in COLD
start mode in response to an overload. The HOT start mode
gives protection, taking account of the behavior of loads under
heat stress.
w
Adjustable short time-delay trip function ST
The ST delay trip function has a “definite time delay character-
istic” and a “ramp characteristic”. These characteristics are
switch-selectable.
The ramp characteristic provides close selectivity with down-
stream circuit breakers or fuses.
The group AGR-L and AGR-R OCRs come in operation with
the definite time characteristic when the load current reaches
1000% or more of the rated current [
I
n
] (500% or more of the
rated current [
I
n
] for AGR-S).
The ST trip function is factory set to the definite time charac-
teristic.
e
Adjustable instantaneous trip function INST/MCR
The INST trip function trips the ACB when the short circuit cur-
rent exceeds the pickup current setting, irrespective of the state
of the ACB.
The making current release (MCR) trips the ACB when the
short circuit current exceeds the pickup current setting during
closing operation. After the ACB is closed, the MCR is locked
and kept inoperative.
The INST and MCR are switch-selectable for AGR-21B, 22B
and 31B. (AGR-11B is INST only , MCR is not selectable)
Note) The MCR needs the control power. If the control power
is lost, the MCR provides the INST trip function only.
Specifications
4
Undervoltage trip device (UVT)
The undervoltage trip device (UVT) trips the ACB when the
control voltage drops below the opening voltage. When the
control voltage is restored to the pick-up voltage, the ACB can
be closed. The pick-up voltage is fixed to 85% of the rated
voltage.
The UVT consists of a tripping mechanism and an undervoltage
trip control device. The trip control device is available in two
types: AUR-ICS and AUR-ICD.
Type AUR-ICS provides an instantaneous trip to the ACB when
the control voltage drops below the opening voltage. Type AUR-
ICD provides a delayed trip to the ACB when the control volt-
age remains below the opening voltage for at least 500 ms.
Adding a pushbutton switch (with normally opened contacts)
between terminals 24 and 30 allows the ACB to be tripped
remotely.
Undervoltage trip control circuit (for AC)
¶
1 Tripping signal is 48 VDC/5 mA.
Apply tripping signal for at least 80 ms. If a constant
tripping signal is applied a n/o auxiliary switch must be
used in series with the PB.
• Ratings
Type of UVT
RatedVoltage
Opening
Pick-up
Coil Excitation
Power Consumption (VA)
Control Device
50/60Hz (V)
Voltage (V)
Voltage (V)
Current (A)
Normal
Reset
AUR-1CS
AC
100
35 – 70
85
AUR-1CD
110
38.5 – 77
93.5
120
42 – 84
102
200
70 – 140
170
220
77 – 154
187
240
84 – 168
204
380
133 – 266
323
415
145 – 290
352
440
154 – 308
374
DC
24
¶
2
8.4 – 16.8
20.4
48
¶
2
16.8 – 33.6
40.8
100
¶
2
35 – 70
85
¶
1
PB(OPEN) or OCRy etc.
08
09
18 28
24
30
AC power supply
Control circuit
UVT
coil
0.1
8
10
¶
2: Soon to be available. Contact TERASAKI for the details.