TCW241_R4.17
–
October 2022
Page 51
The data address received in the query is not an allowable address for the slave.
More specifically, the combination of the reference number and the transfer
length is invalid. For a controller with 100 registers, a request with offset 96 and
length 4 would succeed, a request with offset 96 and length 5 will generate
exception 02.
8.3.2.
Address table
Parameter
FC
PDU
decimal
address
Data size
Data
Relay 1
÷4
01,05,15 100
Discrete
Digital input 1
÷4
02
100
Discrete
Relay 1
÷4
description
03,06,16 15000
64 bytes UTF-8
Relay 1
÷4
pulse width
03,06,16 15200
32-bit Float
Relay 1
÷4
activated from
03,06,16 15300
16-bit unsign int
manual(0),
sensor11(1), sensor12(2),
sensor21(3), sensor22(4),
sensor31(5), sensor32(6),
sensor41(7), sensor42(8),
sensor51(9), sensor52(10),
sensor61(11), sensor62(12),
sensor71(13), sensor72(14),
sensor81(15), sensor82(16),
analog1(17), analog2(18),
analog3(19), analog4(20),
digital1(21), digital2(22),
digital3(23), digital4(24),
anyAlarm(25),
anySensor(26),
anyAnalog(27),
anyDigital(28),
func1(29), func2(30),
func3(31), func4(32),
shedule1(33), shedule2(34),
shedule3(35), shedule4(36),
virtual1(37), virtual2(38),
virtual3(39), virtual4(40)
Relay 1
÷
4 action on alarm
03,06,16 15400
16-bit unsign int
on (0), pulse (2)
Relays state after restart
03,06
15500
16-bit unsign int
off (0), on (1), last state (2)
Digital input 1
÷
4 description
03,06,16 16000
64 bytes UTF-8
Digital input 1
÷
4 alarm state
03
16200
16-bit unsign int
Analog input 1
÷
4 description
03,06,16 17000
64 bytes UTF-8
Analog input 1
÷
4 max
03,06,16 17200
32-bit Float
Analog input 1
÷
4 min
03,06,16 17300
32-bit Float
Analog input 1
÷
4 hysteresis
03,06,16 17400
32-bit Float
Analog input 1
÷
4 value
03
17500
32-bit Float
Sensor 1
÷
8 description
03,06,16 18100
64 bytes UTF-8