TCW241_R4.17
–
October 2022
Page 27
7.4.3.
FW update
The
TCW241 can be updated via a WEB interface.
To update the device follow the steps below:
•
Go to www.teracomsystems.com and download the latest firmware;
•
From
Administration->FW update
select downloaded .co
d file and press “upload” button;
•
After the firmware update is completed, the Login page will appear.
Attention! Don’t turn off the power supply during the update. Turning off the power supply will
damage the device.
7.5.
Logout
The
TCW241 support multisession, but the good practice is to log out after finishing the work.
8.
Protocols and API
8.1.
SNMP
Simple Network Management Protocol (SNMP) is a standard internet protocol for managing devices
on IP networks. In typical uses of SNMP, one or more administrative computers, called managers,
monitor and control devices on LAN. Each controlled device, at all times, executes a software
component called an agent which reports information via SNMP to the manager.
The
TCW241 can be configured and monitored through SNMP.
This could be done using every SNMP v.2 compatible program. Parameters that can be changed, are
grouped according to their functions in the tables below. To obtain a valid OID number it is necessary
to replace the “x” symbol with ”1.3.6.1.4.1.38783”.
To save the changes
configurationSaved
(OID x.2.3.5.0) should be set to "1".
product
OID
Name
Access
Description
Syntax
x.3.1.1.0
name
read-only
Device name
DisplayString
x.3.1.2.0
version
read-only
Firmware version
DisplayString
x.3.1.3.0
date
read-only
Release date
DisplayString
setup -> network
OID
Name
Access
Description
Syntax
x.3.2.1.1.0
deviceID
read-only
Device ID (default MAC address)
MacAddress
x.3.2.1.2.0
hostName
read-only
Hostname
DisplayString
x.3.2.1.3.0
deviceIP
read-only
Device IP address
IpAddress
setup -> io -> sensorsSetup -> sensor1setup
OID
Name
Access
Description
Syntax
x.3.2.2.1.1.1.0
s1description
read-write
Sensor 1 description
DisplayString
x.3.2.2.1.1.2.1.0
s11MAXInt
read-write
S11 maximum value x1000 in Integer format
Integer32
x.3.2.2.1.1.2.2.0
s11MINInt
read-write
S11 minimum value x1000 in Integer format
Integer32
x.3.2.2.1.1.2.3.0
s11HYSTInt
read-write
S11 hysteresis value x1000 in Integer format
Integer32
x.3.2.2.1.1.3.1.0
s12MAXInt
read-write
S12 maximum value x1000 in Integer format
Integer32
x.3.2.2.1.1.3.2.0
s12MINInt
read-write
S12 minimum value x1000 in Integer format
Integer32
x.3.2.2.1.1.3.3.0
s12HYSTInt
read-write
S12 hysteresis value x1000 in Integer format
Integer32