TCG140_R1.1 – May 2018
Page 35
The structure of one row (record) of the log is as follows:
ID
Time
Type of record
Inputs value
Relays
Alarm
conditions
ID
32-bit unique number for every row (record).
Time
a time stamp of record, in format yyyy.mm.dd, hh:mm:ss.
Type of record
following types of records are available:
"Time"
for periodical record;
"Event"
for record initiated by alarm condition;
"Type"
for header record;
"Start"
after power-up condition;
"Restart"
after reset condition;
"Power Down"
after power-down condition;
"Bad"
for a problematic record.
Inputs value
in orders – sensors, analog inputs and digital inputs.
Relays
the relays conditions.
Alarm conditions
show condition for every input, “1” means an active alarm.
An example of the log file:
1131901;15.10.2017,01:02:23;Type;S11/°C;S12;S21/°C;S22;S31/°C;S32;S41/°C;S42;S51/°C;S52;S61/°C;S62;S71/°C;S72;S81/°C;S82;A1/V;A2/V;D1;D2;R1;R2;S1
1/°C;S12;S21/°C;S22;S31/°C;S32;S41/°C;S42;S51/°C;S52;S61/°C;S62;S71/°C;S72;S81/°C;S82;A1/V;A2/V;D1;D2;
1131902;15.10.2017,01:02:23;Time;18.250;;18.375;;18.125;;18.500;;18.188;;18.125;;18.375;;18.375;;11.352;0.065;1;0;1;0;1;;1;;1;;1;;1;;1;;1;;1;;1;0;1;0;
1131903;15.10.2017,01:02:23;Event;18.250;;18.438;;18.125;;18.500;;18.188;;18.125;;18.313;;18.375;;11.352;0.066;0;1;0;1;1;;1;;1;;1;;1;;1;;1;;1;;1;0;0;1;
1131904;15.10.2017,01:02:24;Time;18.250;;18.438;;18.125;;18.500;;18.188;;18.125;;18.313;;18.375;;11.352;0.066;0;1;0;1;1;;1;;1;;1;;1;;1;;1;;1;;1;0;0;1;
1131905;15.10.2017,01:02:25;Time;18.250;;18.375;;18.125;;18.500;;18.188;;18.125;;18.313;;18.375;;11.352;0.066;0;1;0;1;1;;1;;1;;1;;1;;1;;1;;1;;1;0;0;1;
1131906;15.10.2017,01:02:26;Time;18.250;;18.375;;18.125;;18.500;;18.188;;18.125;;18.313;;18.313;;11.352;0.066;0;1;0;1;1;;1;;1;;1;;1;;1;;1;;1;;1;0;0;1;
1131907;15.10.2017,01:02:27;Time;18.250;;18.375;;18.125;;18.438;;18.188;;18.125;;18.313;;18.313;;11.352;0.066;0;1;0;1;1;;1;;1;;1;;1;;1;;1;;1;;1;0;0;1;
1131908;15.10.2017,01:02:27;Event;18.250;;18.375;;18.125;;18.438;;18.188;;18.125;;18.313;;18.313;;2.198;9.092;0;1;0;1;1;;1;;1;;1;;1;;1;;1;;1;;0;0;0;1;
11.
Firmware update
TCG140
supports firmware update over the WEB interface and over the air.
For firmware update over the WEB interface please see 7.4.3. FW update.
For firmware update over the air (GPRS) please follow the steps below:
Upload the update file (.cod extension) on public HTTP server ;
Send firmware update command
(the syntax of the SMS message is described in 8. Setup
via SMS).
Please note that only the Master can send this message.
The firmware will be downloaded and verified. The download via GPRS takes around 3 minutes. If
the file is correct, the Master will receive confirmation SMS message. The update procedure takes
around 2 minutes. Once the firmware update is complete (about 5 minutes), TCG140
will restart.
Attention! Don’t turn off the power supply during the update. Turning off the power supply will
damage the device.