FWR/FWT 10
Page
17
Temtrol, Inc
.
®
Manufacturers of ….. Customized Air Handling Units
(F) MAINTENANCE (Con’t)
Fan Wheel/Cone Alignment
(1) To align fan wheel/cone, first disconnect
power to the FWR/FWT at the main
control panel.
(2) Remove all tek screws on the inlet side of the airflow
straightener panel frame.
(3) Remove airflow straightener frame and panel
for access to fan wheel/cone.
(4) Gently rotate the fan wheel to verify location of adjustment.
(5) To make adjustment, loosen (
do not
remove
)
all the cone retaining fasteners.
Fan Cartridge
Framing
Inlet Side View
Always disconnect power to the fan control
panel before maintenance. Follow all
lockout and tag out procedures.
Rotating equipment. Always disconnect
power to the fan motor before
maintenance.
Screws
Airflow
Straightener
Panel Fame
Airflow Straightener
Panel
Airflow Straightener
Panel Frame
Airflow
Straightener
Panel Fame
And Panel
Fan Wheel/Cone
Gently Rotate Fan
Wheel
Cone Retaining
Fasteners
Inlet Side View
FWR
FWT
Step - 2
Step - 3
Step - 4
Step - 5
Backdraft damper furnished – reverse instruction on pages 19-23.
Then continue with #2 of this section
Содержание SERIES ITF
Страница 3: ......
Страница 5: ......
Страница 6: ......
Страница 7: ......
Страница 8: ......
Страница 9: ......
Страница 29: ...Temtrol Inc Phone 405 263 7286 Fax 405 263 4924 Trouble Shooting ...
Страница 56: ...FWR FWT 10 Page 8 Temtrol Inc Manufacturers of Customized Air Handling Units FWR Fanwall Retrofit FWR ...
Страница 78: ...FWT FWR 09 Page 30 Temtrol Inc Manufacturers of Customized Air Handling Units FWT FWR Trouble Shooting FWR FWT ...