Temperature Control Unit : VTO Series with G500 Series Instrument
Page: 16
TEMPTEK, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-6352 Fax: 317-881-1277
Email: [email protected]
3.
In general, the cooling capacity of the standard 3.5 sq ft heat exchanger is 6,000
Bth/hr (2 kW) for every 20°F difference between the cooling water temperature
and the fluid temperature.
C.
CAUTION: The unit must never be operated with a closed drain line valve. A closed
drain line valve prevents adequate system cooling and will lead to unit overheating.
Overheating of the unit may lead to unit damage and/or serious personal injury.
2.5 ELECTRICAL CONNECTION
A.
Standard Models
1.
Electrical power supply requirements for standard units are identified on the
equipment data tag. Verify that available voltage supply is the same as the unit’s
voltage requirements.
WARNING: DO NOT CONNECT THE UNIT TO A VOLTAGE SUPPLY SOURCE
NOT EQUAL TO THE UNIT’S VOLTAGE REQUIREMENTS AS SPECIFIED ON
THE UNIT’S DATA PLATE.
Use of incorrect voltage will void the unit’s warranty and cause a significant
hazard that may result in serious personal injury and/or unit damage.
2.
For standard units with 12 kW heaters and up to 3 horsepower pumps, a four
conductor cable, 10 foot in length, is provided for connection to an operator
supplied fused disconnect.
3.
For units with 16 kW to 48 kW heaters, the owner must provide a four conductor
power cable and the fused disconnect.
4.
The owner supplied fused disconnect must be sized and installed according to
the unit’s power supply requirements and local electrical codes.
B.
Models With Factory Included Disconnect Switch and Other Custom Features
1.
Some units may be customized and include a factory supplied power disconnect
switch and/or higher specification electrical enclosure. Electrical power supply
requirements are identified on the equipment data tag. Verify that available
voltage supply is the same as the unit’s voltage requirements.
WARNING: Never operate the Temperature Control Unit with a closed water drain.
WARNING: Do not connect the unit to a voltage supply not equal to the unit’s voltage
requirements as specified on the unit’s data plate. Use of incorrect voltage will void the unit’s
warranty and cause a significant hazard that may result in serious personal injury and unit
damage.
Содержание G-500 Series
Страница 2: ......
Страница 6: ...Page 6 THIS PAGE INTENTIONALLY BLANK ...
Страница 12: ...Page 12 THIS PAGE INTENTIONALLY BLANK ...
Страница 34: ...Page 34 THIS PAGE INTENTIONALLY BLANK ...
Страница 40: ...Page 40 THIS PAGE INTENTIONALLY BLANK ...
Страница 52: ...Page 52 THIS PAGE INTENTIONALLY BLANK ...
Страница 58: ...Page 58 THIS PAGE INTENTIONALLY BLANK ...
Страница 63: ...END 2018 Temptek Inc RE 05102018 ...
Страница 64: ......