background image

484 01 3905 04

5

Specifications subject to change without notice.

A170282

Figure 6 

 

Condensate Pan Extension Cork Tape Location

A170283

Figure 7 

 

Condensate Pan Extension Mounting Screws

Horizontal Left Installation

1. Unbend the 4 tabs at the right side of the casing. (See

Figure 8

)

2. Connect furnace snugly against coil casing.
3. Use self

tapping screws to attach furnace. (See

Figure 9

)

4. Seal joint between coil casing and furnace to create air

tight seal using locally approved materials.

5. If coil is wider than furnace, use 4

in. Minimum transition

and self tapping screws to attach furnace. (See 

Figure 2

)

Unbend tab as 
shown, 4 places.

A13064

Figure 8 

 

Horizontal Left Installation

Self-Tapping Screws

A13066

Figure 9 

 

Horizontal Left Installation

REFRIGERANT LINE CONNECTIONS

!

WARNING

PERSONAL INJURY HAZARD

Failure to follow this warning could result in personal injury.
Wear eye protection.

Coil is factory charged with 15 psi nitrogen. The coil is under

pressure and TXV screen is in place behind liquid line plug. DO

NOT remove liquid line plug first, always remove the suction

line plug first to depressurize the coil.

NOTE:

 Factory nitrogen charge may escape past rubber plugs

during storage. This does not indicate a leaking coil nor warrant

return of the coil.
Size and install refrigerant lines according to information provided

with outdoor unit. Coil connection tube sizes are shown in

Table 1

. Route refrigerant lines to the coil in a manner that will not

obstruct service access to the unit or removal of the filter.
Do not use damaged, dirty, or contaminated tubing because it

may plug refrigerant flow

control device. ALWAYS evacuate

the coil and field

supplied tubing before opening outdoor unit

service valves.

CONNECT REFRIGERANT, LIQUID, and

SUCTION LINES

For matched and mismatched systems, use line sizes

recommended in outdoor unit Installation Instructions.

Содержание EAM4X Series

Страница 1: ...personal injury Understand the signal words DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and pro...

Страница 2: ... EAM4X36L21A 3 21 533 3 8 3 4 EAM4X37L17A 3 17 1 2 445 3 8 3 4 EAM4X37L21A 3 21 533 3 8 7 8 EAM4X42L21A 3 1 2 21 533 3 8 7 8 EAM4X42L24A 3 1 2 24 1 2 622 3 8 7 8 EAM4X43L21A 3 1 2 21 533 3 8 7 8 EAM4X48L17A 4 17 1 2 445 3 8 7 8 EAM4X48L21A 4 21 533 3 8 7 8 EAM4X48L24A 4 24 1 2 622 3 8 7 8 EAM4X60L21A 5 21 533 3 8 7 8 EAM4X61L21A 5 21 533 3 8 7 8 EAM4X60L24A 5 24 1 2 622 3 8 7 8 EAM4X61L24A 5 24 1 ...

Страница 3: ...rapped around the outside of coil casing and supply duct contact point NOTE Consult the furnace installation instructions for any special requirements when installing the coil to the furnace Horizontal Right Left Installation A170281 Vertical Upflow Downflow Installation A170280 Figure 2 Adapter s Installation When Coil Overhangs Furnace Downflow Coil Installation IMPORTANT Installing A coils rota...

Страница 4: ... and depth of coil cabinet in the direction of drain pan connection Horizontal Right Installation 1 Use field fabricated attachment plates to secure coil to furnace See Figure 4 2 Use self tapping screws to mount attachment plates to coil casing Self Tapping Screws A13065 Figure 4 Horizontal Right Installation 3 Connect furnace snugly against coil casing 4 Use self tapping screws to attach furnace...

Страница 5: ...ing could result in personal injury Wear eye protection Coil is factory charged with 15 psi nitrogen The coil is under pressure and TXV screen is in place behind liquid line plug DO NOT remove liquid line plug first always remove the suction line plug first to depressurize the coil NOTE Factory nitrogen charge may escape past rubber plugs during storage This does not indicate a leaking coil nor wa...

Страница 6: ... a factory installed hard shut off TXV designed only for use with R 410A refrigerant Use only with outdoor units designed for R 410A NOTE ALL TXV S HAVE PRESET SUPERHEAT SETTINGS AND ARE FIELD NON ADJUSTABLE UNIT DAMAGE HAZARD Failure to follow this caution may result in product damage DO NOT BURY MORE THAN 36 IN OF REFRIGERANT TUBING IN GROUND If any section of tubing is buried there must be a 6 ...

Страница 7: ... off if the water in the secondary pan gets too high Condensate Line Trap Sewer Line Air Gap Above Liquid Level A10216 Figure 11 Condensate Drain to Waste Line WASTE LINE CONNECTION If the condensate line is to be connected to a waste sewer line an open trap must be installed ahead of the waste line to prevent escape of sewer gases See Figure 11 CARE AND MAINTENANCE To continue high performance an...

Отзывы: