INSTALLATION INSTRUCTIONS
R
−
410A Split System Air Conditioner
10
421 01 5103 00
ELECTRICAL WIRING
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to turn off the main (remote) electrical dis-
connect device could result in personal injury or
death.
Before installing, modifying or servicing system,
turn OFF the main (remote) electrical disconnect
device. There may be more than one disconnect
device.
The supply voltage must be 208/230 volts (197 volt
minimum to 253 volts maximum) 60 Hz single phase.
Outdoor units are approved for use with copper
conductors only. Do not use aluminum wire.
Refer to unit rating plate for minimum circuit ampacity
and circuit protection requirements.
Grounding
Permanently ground unit in accordance with the National
Electrical Code and local codes or ordinances. Use a
copper conductor of the correct size from the grounding
lug in control box to a grounded connection in the service
panel or a properly driven and electrically grounded
ground rod.
Wiring Connections
Make all outdoor electrical supply (Line Voltage)
connections with raintight conduit and fittings. Most
codes require a disconnect switch outdoors within sight
of the unit. Consult local codes for special requirements.
Route electrical supply (Line Voltage) wiring through
knockout hole in bottom of Control Box. Connect wires to
Contactor and Ground Lug according to Wiring Diagram
on unit. Refer to Figure 10.
Route thermostat wiring through rubber grommet in
bottom of Control Box. Low voltage lead wires are
provided in the control box for connection to thermostat
wires (use wire nuts). Refer to Wiring Diagram on unit
and Figure 11 for low voltage wiring examples.
NOTE:
Use No. 18 AWG (American Wire Gage)
color
−
coded, insulated (35
°
C minimum) wire. If
thermostat is located more than 100 feet (31 m) from unit
as measured along the control voltage wires, use No. 16
AWG color
−
coded wires to avoid excessive voltage
drop.
NOTE:
Some models are factory equipped with Comfort
Alert
t
Diagnostics device. If Comfort Alert is used as a
field installed option, then a hot bundle must be run for
proper connection.
Figure 10
Electrical Supply (Line Voltage) Connections
DISCONNECT
PER NEC AND/OR
LOCAL CODES
CONTACTOR
GROUND
LUG
FIELD GROUND
WIRING
FIELD POWER
WIRING
11
23 or 13
L1
L2