COOLING OPERATION
Zone Sensor Control
If a zone sensor controls the unit, the unit controller shall maintain the zone temperature
setpoint. This setpoint is user selectable at the user interface.
When a zone sensor is used for control, the unit controller will monitor the temperature
within the space and control the unit accordingly. A closed-loop staging algorithm is used
to stage compressors up and down as required to maintain the desired zone temperature
setpoint. If the unit is equipped with an economizer, outside air conditions are continu
-
ously monitored by the control to determine if conditions are suitable for economizing. If
conditions are suitable for economizing, the unit controller will modulate the OA damper in
addition to staging compressors up and down to maintain the zone temperature setpoint.
HEATING OPERATION
Zone Sensor Control
If a zone sensor controls the unit, the unit controller shall maintain all zone temperature
setpoints. These setpoints are user selectable at the user interface.
When a zone sensor is used for control, the unit controller will monitor the temperature
within the space and control the unit accordingly. A closed-loop staging algorithm is used
to stage heating steps up and down as required to maintain the desired zone temperature
setpoint. If the unit is equipped with an economizer, outside air conditions are continu
-
ously monitored by the control to determine if conditions are suitable for economizing. If
conditions are suitable for economizing, the unit controller will modulate the OA damper in
addition to staging heating steps up and down to maintain the zone temperature setpoint.
TABLE 28 -
THREE-PHASE POWER SUPPLY CONDUCTOR SIZE RANGE
120–150 TON UNIT
SUPPLY VOLTAGE
SINGLE POINT
TERMINAL BLOCK
SINGLE POINT
DISCONNECT
DUAL POINT TERMINAL BLOCK
TERMINAL BLOCK 1 TERMINAL BLOCK 2
460V
6 AWG thru 500 kcmil
(2 per phase)
3/0 thru 500 kcmil
(2 per phase)
2 AWG thru 300 kcmil
(2 per phase)
14 AWG thru 2/0
(1 per phase)
575V
6 AWG thru 500 kcmil
(2 per phase)
3/0 thru 500 kcmil
(2 per phase)
2 AWG thru 300 kcmil
(2 per phase)
14 AWG thru 2/0
(1 per phase)
Controls (Cont'd)