temperzone’s - TZT-701 Installer Manual
Edition 1.2 (0608)
Page 3 of 16
In
st
a
ll
er
S
el
ec
ta
b
le
SW6 - Thermostat Mode
Switch On = Programmable (See “User Manual” page 7 for Residential, or page 10 for Commercial)
Switch Off = Manual (See “User Manual” page 12)
SW7 - Zoning Mode
(See “User Manual” page 6 regarding Common zoning features,
Switch On = Zoning enabled
pages 7 and 9 regarding Residential zoning,
Switch Off = Zoning disabled
pages 10 and 12 regarding Commercial zoning,
and
page 14 regarding Zone Control generally.)
SW8 – Daily Events
If Switch 6 =ON (Programmable thermostat mode)
Switch 8 On = Residential Programming. 4 events per day (Wake / Leave / Return / Sleep)
(See “User Manual” page 8)
Switch 8 Off = Commercial Programming. 2 events per day (Start / Stop)
(See “User Manual” page 10)
If Switch 6 =OFF (Manual thermostat mode)
Switch 8 On = 2 Individual set point groups (Day & Night Manual Mode)
(See “User Manual” page 13 – “Day / Night Set points”)
Switch 8 Off = 1 event Manual Mode
(See “User Manual” page 13 – “Day / Night Set points”)
Wiring
An overall view of the TZT-701BB input and output wiring has been provided below.
Backup battery.
A backup battery is provided inside the Wall Controller. The ONLY function of this battery is to keep the clock running during a
power outage. The battery life is typically 8-10 years in normal service. Replacement batteries can be obtained from most battery
suppliers. The battery is a - Lithium 3V Coin cell, type CR1220.