temperzone’s - TZT-701 Installer Manual 

 

 

                                 Edition 1.2  (0608)

                                                                  Page 13 of 16 

Fan Coil sensor 

The TZT-701 fan coil sensor is responsible for warm start, residual heat / cool fan run on and indoor fan speed when the user has 
selected Auto Fan speed mode. 
 

Heating Indoor fan control Temperatures 

Increasing temperature / speeds 

Decreasing Temperature / speeds 

Fan turns ON in Low speed 33c 

Turns Off at 27c 

Fan speed increases to Medium Speed 39c 

Turns to low at 33c 

Fan increases to high speed 45c 

Turns to medium at 39c 

 

Cooling Indoor fan control Temperatures 

(Hysteresis not shown)

 

Low speed  

Set point  temp <1.5c away from 
Room  temperature 

Medium speed 

Set point  temp >1.5c <2.5c  away 
from Room  temperature 

High Speed 

Set point  temp >2.5c  away from 
Room  temperature 

0.5c Hysteresis has been provided to prevent rapid fan speed changes. 
 
 

Variable Capacity Unit operation 

The TZT-701 has two Analog output signals (One for Heating and one for Cooling) which can be used to indicate how far away 
from Set Point the Room temperature presently is. These signals can be used in temperzone’s Digital Scroll units. The wiring of 
these signals and details about their function is therefore not covered in this edition of  this document. The wiring of these Extra 
Low Voltage (0 – 10V DC) signals will be shown on the wiring diagrams of the Digital Scroll units which have the appropriate 
hardware fitted to make use of them. 
 

 
TZT-701 sensor resistance table – all sensors 

 

TEMPERATURE 

RESISTANCE 

 

TEMPERATURE 

RESISTANCE 

-20°C 

98.9 k 

 

35°C 

6.5 k 

-10°C 

56.05 k 

 

40°C 

5.3 k 

-5°C 

42.8 k 

 

45°C 

4.35k 

0°C 

32.95 k 

 

50°C 

3.6 k 

5°C 

25.6 k 

 

55°C 

2.95 k 

10°C 

20.0 k 

 

60°C 

2.45 k 

15°C 

15.35 k 

 

65°C 

2.05 k 

20°C 

12.5 k 

 

70°C 

1.75 k 

25°C 

10.0 k 

 

75°C 

1.45 k 

30°C 

8.05 k 

 

80°C 

1.25 k 

 
 

Commissioning hint. 

If commissioning a large apartment project, by keeping a wall controller with you and swapping it for the room wall controller 
fitted to the apartment you can easily activate heating / cooling and zone functions etc while you are at the main PCB to verify 
correct  equipment  operation.  Simply  swap  the  wiring  back  to  the  apartment  controller  at  the  completion  of  the  commissioning 
process. This eliminates the need for two people when commissioning or endless trips up and down ladders to change functions or 
fan speeds with the apartment fitted controller. 

 

Содержание TZT-701

Страница 1: ...TZT 701 Thermostat Installer Manual Edition 1 2 0608...

Страница 2: ...eed field adjustment Setting of DIP switches 6 to 8 are always up to the installer to set because they determine how the end user is going to operate the thermostat If retrofitting a TZT 701 the Insta...

Страница 3: ...events per day Wake Leave Return Sleep See User Manual page 8 Switch 8 Off Commercial Programming 2 events per day Start Stop See User Manual page 10 If Switch 6 OFF Manual thermostat mode Switch 8 On...

Страница 4: ...to the wall controller back plate and the Remote Temperature Sensor wires if applicable have been connected to the TT labelled terminals the wall controller can be assembled Ensure the fold down butto...

Страница 5: ...e 1 only Zone 2 only then both Zones You are not able to close both zones simultaneously Status LED s are provided on the main PCB to show which zones are open The zone damper relay contact rating is...

Страница 6: ...ressors run Fan running Cooling Economy is shown in the LCD Stage 2 Economy Outside air is least 6 C cooler than the inside air temperature Inside damper closed Outside damper open Compressors OFF Fan...

Страница 7: ...be able to re enter the Installer menu and the wall controller must be returned to temperzone or approved service centre to be unlocked There may be a fee for this service LC 00 Keyboard Lock The TZT...

Страница 8: ...flash indicating the minimum permitted cooling set temperature has been reached The range is 15 37c off SD 02 Stage Delays This value sets the temperature difference in deg C F between 1st 2nd stages...

Страница 9: ...mode Heating function and options disabled Fn H Heat only mode Cooling function and options disabled tC 12 Clock Mode The TZT 701 has both a 12 hour am pm or a 24 hour military style clock TC 12 AM P...

Страница 10: ...g of a voltage free dry contact when in the fault condition SW1 Fault Logic Select on the main PCB selects the logic of the fault input either a normal or fail safe fault input See the wiring example...

Страница 11: ...essed or a user control limit has been reached the padlock symbol will flash to remind the user the attempted operation is prohibited Main PCB Indicators Functions Reversing valve logic To minimise re...

Страница 12: ...runs satisfactorily and chilled air is produced This may or may not include testing the three indoor fan speeds in cooling mode Tip The TZT 701 LCD will change the word Heat or Cool to Heating or Cool...

Страница 13: ...sed in temperzone s Digital Scroll units The wiring of these signals and details about their function is therefore not covered in this edition of this document The wiring of these Extra Low Voltage 0...

Страница 14: ...N Return wall controller to temperzone or approved service agent for resetting Service Fee may apply This may not be a fault Check fan coil sensor temperature as fan coil may not be at correct tempera...

Страница 15: ...ostat s case is not weather proof this warranty does not cover rain moisture damage or using this equipment outside of the quoted specifications nor handling abuse temperzone Part Numbers Item Descrip...

Страница 16: ...perzone co nz temperzone ltd Australian Head Office 7A Bessemer Street Postal Address PO Box 6448 Blacktown Delivery Centre Blacktown Sydney NSW 2148 Australia Australia Ph 61 2 8822 5700 Fax 61 2 882...

Отзывы: