© temperzone limited 2018
04/18 Pamphlet No. 3961
APRVD
DATE
ECN
MODIFICATION
ISSUE
Revision
Drawn
Title
Aprvd
Drawing
No.
2012
temperzone
ltd
C
A.F.C.
Client
wiring
25-10-12
291-000-308
date
Drawn
Visit:
www.temperzone.biz
for
client
wiring
diagrams
OPA
201RKTYGH
WIRING
SCHEMATIC
Temperature
Sensor
Sensor
Color
DL
Discharge
Red
IC
I/D
Coil
Yellow
AMB
Ambient
Black
DEI
Deice
Blue
OC
O/D
Coil
Yellow
UC7
Dip
switch
settings
DIP
switch
On/Off
1,2,4
&
6
On
3,5,7,8,9,
10,11,12,13,14,15
&
16
Off
TFC
SW2
(DIP
S/W)
settings
DIP
On/Off
1,2,3
&
4
Off
Cooling
-
Electrical
Input
Electrical Supply
required
3Ph
380-415V
~
50Hz
Indoor
fan
motor
(1Ph)
Outdoor
fan
motor
(1Ph)
Full
load
amps
Running
amps
(Total)
Heating
- Reverse
Cycle
Compressor
(3Ph)
run
amps
rated
conditions
Cooling
-
Heating
- Reverse
Cycle
Indoor
fan
motor
(1Ph)
Full
load
amps
Capacities
- Net
to
AS/NZS
3823
E.E.R.
(Cooling)
Compressor
type
: Scroll
CM
A.E.E.R.
(Cooling)
Oil
type
: Polyolester
(P.O.E.)
IFM
Control
circuit
breaker
CCB
Max
running
amps
(Total)
Base
charge
unit
Unit
Weight
- Nett
OFM
kW
kW
A
kW
12
MFD
kW
kW
A
1.25 8
16
kW/kW kW/kW
A
A/Ph
19.76 18.08
6.12 5.42 3.140 3.126
A/Ph
8.6
A
24
3.0
x
1
13.0/8.6/8.6
Kg
265
Kg
6.3
OPA201RKTGYH
G
Outdoor
motor
capacitor
CM
Compressor
Motor
RV
Reversing
Valve
CMC
Compressor
Contactor
CAP
Capacitor
PRC
Phase
Rotation
Control
PRR
Phase
Rotation
Relay
CCH
CrankCase
Heater
HP
High
Pressure
Control
CCB
Control
Circuit
Breaker
OFM
Outdoor
Fan
Motor
FRB
TFC UC7
LP
Low
Pressure
Control
Fault
Relay
Board
Unit
Controller
7
Triac
Fan
Controller
IFM
Indoor
Fan
Motor
M
V
Modulating
Valve
MV
CMC
RV
CCH
HP
Modbus
slave
port
for
BMS
(monitoring
or
control)
A
B
SL
DL
DEI
IC
OC
DIP
Switches
AMB
LPT
HPT
N/C COM N/O
FRB
Refer
to
DIP
S/W
settings
UC7
0-10V
input
Temp
sensors
(Refer
to
table)
Pressure sensors
LP
ELECTRIC
FILTER
BK
R
BK
R
Modbus
master
port
for
optional
Temperzone
approved
T/stat
(TZT100
SAT
3)
Remote On/Off option
24C A B 24
If
Remote
On/Off
option
fitted
remove
this
link.
E
W
U
V
SR-
SR+
FR-
MO
FR+
0V
+12V
0-10V
ACL
E
Motor
Driver
PE
ACN
PE
FAN
N
N
L3
L2
L1
ACTIVE/230V
N2/230V
CMC
T1
CCB
T2
T3
N3/230V
230V MAINS
TFC
FAN output
For
SW2
(DIP
switch)
settings-
Refer
table
A
B
M
3 ~
PRR
PRC
L2
L3
L1
T2
T3
T1
N1/230V
CM
PRR
TB1
TB2
TB3
TB4
TB5
TB6
TB7
TB8
C
D
C
D
External
Quiet
Mode
activation
External
Dry
Mode
activation
See
UC7
Manual
for
DIP
switch
settings
M 1~
BLU
BLK
OFM
CAP
U1
U2
Z1
Z2
BRN
ORG
IFM
Yellow
Black
or
Brown
Red
Black
White
Black
or
Brown
Yellow
ACTIVE1/230V
N4/230V
TB9
Fan Speed & Range Settings
Min RPM
Max RPM
Min Volts
(Low)
Max Volts
(High)
825
1125
5.5
7.5
900
1200
6.0
8.0
975
1275
6.5
8.5
1050
1350
7.0
9.0
Shaded Area = Default Settings
Refer Installation Instructions for Adjustment
SW3
G
N4074
9-02-18
M.A.K.
Refer
I&M
for
Alternative T/Stat
or
BMS
0V
COM
P 0-10V
IN
Heatsink
TB10
Optional
External
Compressor
Capacity
Control
Ferrite
- Coil
wires
3
turns
around
ferrite
core.
Separate
these
3
wires
from
others.
ECC
Changed
to
Motor
Driver.
Changed
wire
colour
to
red
from
white
Client Protection &Isolation Switch
G
Disconnect
0-10V
Compressor
capacity
board
when
connecting
TZT-100
Thermostat
F
N3992
18-07-17
D.J.S
Updated
the
earth
Symbol
Label
. Replaced
6A
Electric
Filter
with
10
A Electric
Filter
G