Dimensions (mm) 

      OPA 201RKTYG

PROJECTION

Not to Scale

 

POINT LOADS (kg) WEIGHT

 

W X  Y  Z  (kg)

 

50 60 88 72  270

2.  Check for correct rotation of the 

compressor. If rotation is incorrect the 

compressor will not pump, be noisy, and 

will draw minimal current. To correct 

motor rotation, change the phasing at 

the main power terminal. 

3.  Check the supply voltage.

4.  Measure the current draw on the 

compressor motor and on each fan 

motor. Check all readings against the 

specified values - particularly the indoor 

fan amps if the unit is installed in a free 

blow application.

5.  Fit R410A compatible gauges and 

measure the suction and discharge 

pressures.

6.  In cooling mode, test the operation 

of the high pressure safety control by 

safely disconnecting the outdoor air fan.

7.  Test the operation of the reversing valve 

by running the unit in both the heating 

and cooling mode.

8.  Check that the motors are running 

smoothly.

9.  Check the supply air flow at each outlet.

10. Touch up any outdoor unit paintwork 

damage to prevent corrosion.

UNIT CONTROLLER (UC7)   

The Unit Controller provides system 

protection functions such as coil frost 

protection, de-icing, high head pressure and 

low suction pressure cut-out. It also protects 

against rapid cycling of the compressor(s) 

and loss of refrigerant. Various methods 

of head pressure control (or limiting) 

are employed in temperzone units. The 

particular method used varies from model 

to model, but is also handled by the Unit 

Controller. In combination, these features 

deliver optimised performance across a 

wide operating temperature range.
As a result of the UC’s control of these 

inter-related functions, the outdoor fans may 

take some time to start rotating after each 

compressor start. They may also run on 

when the compressor stops. The fans will 

stop during a de-ice cycle. The speed will 

vary either smoothly, or in steps, in order to 

protect against excessively low or high head 

pressure.
Refer to UC7 Controller label on the unit or 

www.temperzone.biz for operation & fault 

diagnostics information; model search 'UC7'.

MAINTENANCE
Weekly For First Four Weeks

1.  Check indoor air filters (if fitted) and 

vacuum or wash clean as necessary.

2.  Check condensate drain for free 

drainage.

3.  Check compressor compartment for oil 

stains indicating refrigerant leaks.

SUPPLY

AIR

RETURN

AIR

1158

MOUNTING CENTRES

1230

OVERALL

1200

 OVERALL

OUTDOOR

AIR FLOW

500 MIN.

 CLEARANCE

1000 MIN. CLEARANCE

X

Y

Z

W

OUTDOOR

AIR FLOW

ELECTRICAL

ACCESS

PANEL

60

440

35

100

ACCESS

PANEL

2000 MIN. CLEARANCE

1175

 OVERALL

95

1032

800

MOUNTING CENTRES

12 DIA.  HOLES

DRAIN

15 BSPF

11

ELECTRICAL

HOLES

25 DIA.

187

256

205

95

1032

 500 MIN. CLEARANCE

4.  Check tightness of electrical 

connections.

Six Monthly

1.  Check the tightness of all fan and motor 

mountings.

2.  Check tightness of electrical 

connections.

3.  Check suction and discharge operating 

pressures.

4.  Replace indoor unit air filters (if fitted).

5.  Check condensate drain for free 

drainage.

Yearly

1.  Check all refrigerant piping for chafing 

and vibration.

2.  Check the operation of electric heaters, 

if fitted.

3.  Check air supply at all diffusers.

4.  Check for excessive noise and vibration 

and correct as necessary.

5.  Check for insulation and duct damage 

and repair as necessary.

6.  Remove lint and dust accumulation 

from outdoor coil fins. 

7.  Touch up any outdoor unit paintwork 

damage to prevent corrosion.

NOTE

Specifications are subject to change without 

notice due to the manufacturer's ongoing 

research and development programme.