background image

- 5 -

It is recommended that control is by Enthalpy (or by a 

combination of dry and wet bulb temperatures) so that 

free cooling is used without adding any heat load to the 

building. This is a requirement of Australian NCC and NZ 

Building Code. Control by dry bulb temperature alone is not 

recommended as often, even though the outdoor dry bulb 

temperature may be lower than that of the space, the total 

heat content of the air can be higher thereby adding heat 

load in the form of moisture content to the space.
If dry bulb temperature is used as the control method the 

temperature must be set several degrees lower than the 

space temperature to reduce the possibility of extra heat 

load being introduced.
Air Quality (CO

2

) sensors can be used to proportionally 

control the fresh and return air dampers (via the control 

system).
In all situations the UC8 Unit Controller will allow the 

compressors to operate with the economiser fresh air 

damper open providing the refrigeration system is not 

compromised. 
The compressor(s) could be stopped from operating by 

normal protection devices such as low suction temperature/

pressure or indoor coil frost protection and too many trips 

of either fault could lead to a lock out of the compressor(s) 

operation. Should this occur then a review of the control 

settings may be necessary. 

5.   START-UP PROCEDURE

5.1  Before starting the compressor

1.  Before working on the unit remove mains power from 

the unit by opening the mains isolating switch.

2.  Remove the shipping blocks from beneath each 

compressor. Check that each compressor is securely 

mounted.

3.  Check the thermostat and/or other controls are 

correctly wired to the unit.

4.  Check tightness of electrical connections.
5.  Check the air filters have been correctly installed, if 

present.

6.  Check that all indoor fan motors can freely rotate.
7.  Apply mains power to the unit by closing the mains 

isolating switch.

8.  Check the supply voltage between each phase and 

neutral.

9.  Check air diffusers are open.
10.  Before starting the compressors a four hour delay 

period is required to allow the crankcase heaters to 

drive any liquid refrigerant out of the compressor oil. 

Mains power must be switched on during this four hour 

delay period.

5.2  Commissioning

After the four hour delay period has expired (see step 10 in 

section 5.1) complete the following procedure. You can use 

the Commissioning Sheet (refer back page) to help you.
1.  Place the UC8 controller in commissioning mode by 

pressing and holding the SW3 push button (see Fig. 4) 

until the display shows:   

‘0’ [release]   ‘1’ [long press]   ‘t’;  [short press] repeat 

to find ‘c’, then [long press] to select.  

This Commissioning mode ‘c’ reduces the waiting 

times at start-up and between cycles.for the next 

half hour, or until the controller is reset by removing 

power.

2.  Start compressor in Cooling mode.

3.  Check the outdoor fan motor runs smoothly.

 

Note: The outdoor fan does not necessarily start rotating 

immediately after the compressor is started. The fans 

may run-on for a short period after the compressor 

stops.

 

Outdoor fan stops during outdoor coil de-ice cycles.

4.  Measure the current draw on each phase to the 

compressor motor and to each fan motor. Check the 

readings against the specified values in the wiring 

diagram or specification sheet.

5.  The display and pushbutton on the UC8 can be used 

to check temperatures and pressures. Short presses 

on the pushbutton cycles through the available 

options. Table 1 on page 8 shows, in sequence, what 

information is available – with examples.

 

Alternatively use a set of pressure gauges suitable for 

R32 refrigerant.

 

!

 WARNING 

 

Under no circumstances shall potential sources of 

ignition be used in the searching for or detection of 

refrigerant leaks. If a leak is suspected, all naked flames 

shall be removed/extinguished. 

 

If a leakage of refrigerant is found which requires 

brazing, all of the refrigerant shall be recovered from the 

system, or isolated (by means of shut-off valves) in a 

part of the system remote from the leak.

6.  Repeat steps 2 to 5 for each compressor.
7.  Test operation of the compressors when operating in 

heating mode.

8.  Check for desired supply air flow rate at each outlet. 
9.  Touch up any outdoor unit paintwork damage to prevent 

corrosion.

10.  Sign the check label.

5.3  Commissioning of variable speed (EC) indoor plug 

 fan

A unit equipped with variable speed (EC) indoor plug fan 

allows adjustment of the fan speeds to obtain the desired 

indoor supply airflows.
Using TZT-100 option

If the unit is controlled with a temperzone TZT-100 wall 

thermostat then adjustments are made as follows:
i.   Ensure the compressor is off and the thermostat or BMS 

does not request for the compressor to start. The UC8 

display should show a flashing dot (●).

ii.  To adjust the fan High speed press and hold down the 

SW3 push button on the UC8 circuit board until the 

display shows:  

‘0’ [release]   ‘1’ [long press]   ‘t’; [short press] repeat 

to find ‘H’, then [long press] to select. 

iii.  The fan will start and run at High speed. The display 

shows the fan control voltage for the High 

speed setting; factory default value is 8.0V.

iv.  Each following press on the SW3 push 

button increases the indoor fan control voltage in steps 

of 0.5V, up to a maximum of 10.0V. Pressing the push 

button again when value 10.0 is shown returns the fan 

control voltage down to the minimum value of 3.0V and 

back up again.

v.  When the desired setting for high fan speed is displayed, 

[long press] to select and save. The controller then exits 

the menu and the fan stops.

vi.  To adjust the fan Low speed hold down the SW3 push 

button on the circuit board until the display shows:  

‘0’ [release]   ‘1’ [long press]   ‘t’; [short press] repeat 

to find ‘L’, then [long press] to select. 

  The fan will start and run at the Low speed setting. The 

factory default value is 5.0V.

Содержание Econex OPA 250RLTFP

Страница 1: ...well ventilated space If the refrigerant gas comes into contact with fire a poisonous gas may occur Be aware that R32 does not contain an odour If indoors the appliance shall be stored in a room away...

Страница 2: ...eparate drain tray beneath the unit could be used to drain condensate to a suitable drainage point Condensate drains should be U trapped outside the unit The trap should have a vertical height of at l...

Страница 3: ...llows DIP switch 2 ON Equipment type Heat Pump DIP switch 3 OFF Equipment stages One DIP switch 4 ON Reverse cycle valve on Heating SAT 3 Refer SAT 3 Installation Set up Guide page 3 4 4 Communication...

Страница 4: ...emperzone biz model search UC8 or com website 4 10 Setting the UC8 Modbus device address To view or change the Modbus device address of a UC8 follow these steps Power up the unit but leave the compres...

Страница 5: ...er 2 Start compressor in Cooling mode 3 Check the outdoor fan motor runs smoothly Note The outdoor fan does not necessarily start rotating immediately after the compressor is started The fans may run...

Страница 6: ...signals and transfers the signals to the outputs after enforcing safety timers and other protection functions If the compressor is held off or held on by a safety timer then the display shows message...

Страница 7: ...door coil This usually means reversing the cycle for a few minutes during which time there is no heating and in fact a little cooling can occur 8 4 In a new building why does it take some days before...

Страница 8: ...t 6K Compressor discharge line pressure kPa dLP Discharge line pressure 2447 kPa Condensing temperature C Ct Condensing temperature 42 C Compressor discharge line temperature C dLt Discharge line temp...

Страница 9: ...indication that the compressor is being starved of refrigerant gas Common reasons for this could be a lack of refrigerant under charged or loss of charge or a problem with the expansion device for exa...

Страница 10: ...ked out the compressor is not allowed to start Lock out is designed to protect the compressor from repeatedly starting when a serious fault exists that requires the attention of a service technician T...

Страница 11: ...3 4 1 1 INPUT kW 2 5 1 5 0 5 2 0 1 0 3 0 3 5 Amps 500 1000 1500 2000 2500 0 100 200 300 AIR FLOW l s AVAILABLE EXTERNAL PRESSURE Pa 2 5 m s Face Velocity 400 500 0 NOMINAL INPUT kW 3 0 2 0 1 0 2 5 1 5...

Страница 12: ...st IMPORTANT Digital compressors must be operating at 100 for at least 10 minutes when taking these readings System 1 Cool Cycle Low Pressure SLP kPa Outdoor Ambient temperature C Evap temperature Et...

Отзывы: