background image

GENERAL

INST

ALLA

TION

DUCTED WATER COOLED PACKAGED AIR CONDITIONERS

CWP models (c/w UC8)

Installation & Maintenance

1. GENERAL

1.1  Introduction

Follow these instructions to ensure the optimum 

performance, reliability and durability.
Units must be installed in accordance with all national and 

regional and local regulations and bylaws.
The appropriate permits must be acquired and adhered 

to. Seismic restraints must be fitted if required.

The accompanying 'R32 Handling Ducted Units' pamphlet 

forms part of these Installation & Maintenance instructions.

!

 WARNING. 

These units use R32 refrigerant (Class A2L) which is 

mildly flammable.

The system shall be installed, operated and stored in a 

adequately ventilated space where there is no continuously 

operating open flames (eg an operating gas appliance) or 

other R32 ignition source. If the refrigerant gas comes into 

contact with fire, a poisonous gas may occur. Be aware that 

R32 does not contain an odour.

2. INSTALLATION
2.1 
Positioning & Mounting

CWP units are designed to be fitted in a ventilated 

cupboard or closet and used with simple, short duct 

layouts. Units should be located as close to the space to 

be air conditioned as acoustic criteria allows.
When determining the position of the air conditioner, allow 

adequate space around the unit to facilitate water pipe/

hose connections, condensate drainage, future servicing 

and maintenance. 
For apartment/hotel buildings, locate the units as close as 

possible to the shared foyer/corridor of each floor of the 

building to minimise the length and cost of water piping, 

and electrical conduit.
The CWP unit has two pair of IN/OUT water connections 

(top or front). Choose the best pair to suit your 

application.
For major changes of components, the whole unit would 

need to be removed from a tight closet space. Please 

consider this when installing the CWP. This should 

include, but not be limited to, the use of isolation valves 

and barrel unions on waterlines, easily accessible 

electrical isolations on all external (including control 

circuit) power supply, and easily detached flexible duct 

connection. 
Ensure there is enough working space in front of the 

electrical access panel. Allow adequate clearance for the 

filter to be removed for cleaning.
Ventilation of the installation space, at the base level, 

permits refrigerant to disperse in the unlikely event of a 

leak.
Fasten the unit to a solid base using at least two of the 

four mounting points in the feet. Some commercial rubber 

pads between the unit feet and the base can minimise 

transmission of vibration. Alternatively, use holding straps 

to secure the unit to the place.

2.2 Condensate Drain

Mount the unit level as it comes with a sloping drain tray. 

The unit condensate drain is 'U' trapped inside the unit, 

therefore NO EXTERNAL TRAP REQUIRED.
The external drain line must not be trapped or piped to a 

level above the drain tray. 
The drain line must be maintained at least 19 mm ID 

along its full length. A vent pipe is recommended (refer 

figure 1). 

OPEN

DRAIN

MINIMUM

SLOPE

20 mm PER m

(1 IN 50)

100 mm

APPROX.

AIR VENT PIPE (10 ID)

500 mm MAX.

FROM UNIT

NO TRAP

REQUIRED

Figure 1  Condensate Drain

Check drain by pouring water into the drain tray (at the 

coil, behind the filter) and ensuring that it clears (with the 

unit operating). Failure to adhere to these instructions 

could cause flooding. If necessary, fit an external 

condensate lift-pump to assist in achieving adequate 

slope in the drain line.

Do not install the drain line in front of any access panel. 

2.3 Air Ducts, Filters and Grilles

Rigid Ducting:

a.  Use flexible connections between unit and rigid ducting.

b.  Use appropriately sized insulated ducting with 

consideration for noise transmission through the 

ducting (refer Appendix II).

c.  Option: If access to the unit's air filter is restricted, 

then a return air grille with filter incorporated could be 

installed.

d.  Supply air grilles should be selected and installed to 

avoid draughts and noise but give good air distribution.

003-000-145  11/20

Содержание CWP Series

Страница 1: ...e of isolation valves and barrel unions on waterlines easily accessible electrical isolations on all external including control circuit power supply and easily detached flexible duct connection Ensure...

Страница 2: ...Temperature EWT and the reduced flow rate Water flow needs to be balanced to suit the system design Refer Technical Data for acceptable water flow rates and pressure drop data 3 4 Air Water Flow Refer...

Страница 3: ...us over RS485 DRED data logging refer www temperzone biz model search UC8 6 START UP PROCEDURE 6 1 Power a Check the unit is electrically connected in accordance with the wiring diagrams b Check all w...

Страница 4: ...rd compressor and total run amps during stable operation e Check the readings against the specified values on Specification Sheet and record these values on the Commissioning Check List on page 11 f U...

Страница 5: ...or the procedure Example For detailed information about monitoring and control via Modbus RTU refer to document UC8 Modbus communications available at www temperzone biz model search UC8 7 4 Setting t...

Страница 6: ...e kept open Location of wall controller or remote temperature sensor is wrong Check for leaks in supply or return air ductwork Unit may be undersized for the current room size or operating under extre...

Страница 7: ...normally open remove link if used IN 1 link D1 SC UC8 Optional Condensate Drain Tray float switch normally closed remove link if used Optional Communicating BMS Controller Modbus RTU B1 A1 0V B A REF...

Страница 8: ...C Ct Condensing temperature 42 C Compressor discharge line temperature C dLt Discharge line temperature 70 C Compressor discharge side superheat K dSH Discharge side superheat 28K De ice sensor temper...

Страница 9: ...acting sensor for the electric heater elements has been triggered The display shows the message Hi t when protection is active 5 High discharge superheat protection Discharge superheat is defined as...

Страница 10: ...ting when a serious fault exists that requires the attention of a service technician The display shows the code of the fault that caused the lock out condition A unit that is locked out can be unlocke...

Страница 11: ...st Cool Cycle Low Pressure SLP kPa Return air temperature C Evap temperature Et C Supply air temperature C Suction Line temperature SLt C Entering Water temperature C Suction Superheat SSH K Leaving W...

Страница 12: ...ydney Australian Head Office and Manufacturing Wellington Christchurch Brisbane Melbourne Adelaide Singapore Shanghai Perth Hobart Newcastle Singapore Shanghai Beijing Jakarta Hong Kong Sri Lanka Maur...

Отзывы: