Tempco PCM10001 Скачать руководство пользователя страница 6

Page 6 of 10

PV Shift

In certain applications it is desirable to shift the con-

troller display value (PV) from its actual value. This

can easily be accomplished by using the PV shift

function.

The SHIF function will alter PV only.

Example: A process is equipped with a heater, a sen-

sor, and a subject to be warmed up. Due to the design

and position of the components in the system, the sen-

sor could not be placed any closer to the part. Thermal

gradient (differing temperatures) is common and nec-

essary to an extent in any thermal system for heat to

be transferred from one point to another. If the differ-

ence between the sensor and the subject is 35°C, and

the desired temperature at the subject to be heated is

200°C, the temperature at the sensor should be 235°C.

You should enter -35°C to subtract 35°C from the ac-

tual process display. This in turn will cause the con-

troller  to  energize  the  load  and  bring  the  process

display up to the set point value.

The controller will enter failure mode if one

of the following conditions occurs:

1. 

SBER

occurs due to input sensor break

or input current below 1mA if 4–20 mA

is selected or input voltage below 0.25V

if 1–5V is selected.

2. 

ADER

occurs due to the A-D converter

of the controller failing.

Output 1 and output 2 will perform the fail-

ure transfer function as the controller enters

failure mode.

Output 1 failure transfer

, if activated, will

perform:

1.  If output 1 is configured as proportional

control (PB≠ 0), and BPLS is selected

for  O1FT,  then  output  1  will  perform

bumpless transfer. Thereafter, the previ-

ous  averaging  value  of  MV1  will  be

used for controlling output 1.

2.  If output 1 is configured as proportional

control  (PB≠  0),  and  a  value  of  0  to

100.0% is set for O1FT, then output 1

will perform failure transfer. Thereafter,

the value of O1FT will be used for con-

trolling output 1.

3.  If  output  1  is  configured  as  ON-OFF

control (PB=0), then output 1 will be

driven OFF if OFF is set for O1FT and

will be driven ON if ON is set for O1FT.

Failure Transfer

Figure 3.7  PV Shift Application

Manual Control

Operation

To enable manual control, the LOCK parameter should be set

to NONE, then press 

for 6.2 seconds; 

(hand control) will appear on the display. Press 

for 5 sec-

onds, then the MAN indicator will begin to flash and the lower

display will show 

. The controller is now in manual

control mode. 

indicates output control variable for out-

put 1, and 

indicates control variable for output 2. Now

you can use the up and down keys to adjust the percentage

values for the heating or cooling output.

The controller performs open loop control as long as it stays

in manual control mode.

Exit Manual Control

Pressing the 

key will cause the controller to revert to its

normal display mode.

R

Содержание PCM10001

Страница 1: ...oller 2 On Off Switch 3 1 Amp Control Fuse 4 20 Amp Main Fuse 240V model has 2 5 120V or 240V Power Cord 20A 6 120V or 240V Heater Receptacle 20A 7 Type J or K Thermocouple Jack WARNINGS 1 Dangerous v...

Страница 2: ...2 of the TEC 9100 which can be used as a cut out in the event of an over setpoint temperature condition This is a deviation contact set to 30 F above the setpoint In the event of an over setpoint tem...

Страница 3: ...Page 3 of 10 1 5 Menu Overview...

Страница 4: ...Page 4 of 10 Parameter Descriptions TEC 9100 Temperature Controller Controller Parameter Descriptions that are not applicable are not shown in the above table...

Страница 5: ...dvanced PID and Fuzzy Logic algorithm to create a very small overshoot and very quick response to the process if it is properly tuned Cool only control ON OFF control P PD control and PID control can...

Страница 6: ...2 will perform the fail ure transfer function as the controller enters failure mode Output 1 failure transfer if activated will perform 1 If output 1 is configured as proportional control PB 0 and BP...

Страница 7: ...lure mode or manual control mode is entered Procedures Auto tuning can be applied either as the process is warming up cold start or when the process has been in a steady state warm start After the aut...

Страница 8: ...Page 8 of 10 Table A 1 Error Codes and Corrective Actions...

Страница 9: ...ty does not apply to damage resulting from transporta tion alteration misuse or abuse RETURNS No product returns can be accepted without a completed Return Material Authorization RMA form TECHNICAL SU...

Страница 10: ...ce the Advantages of our Diverse and Innovative Products Copyright 2015 All Rights Reserved Electric Heating Elements Thermocouples and RTD Assemblies SCR Power Controls Solid State Relays Mechanical...