Tempco PCM10001 Скачать руководство пользователя страница 5

Page 5 of 10

The ON-OFF control may introduce excessive process oscillation

even if hysteresis is minimized. If ON-OFF control is set (i.e.,

PB=0), TI, TD, CYC1, OFST, CYC2, CPB, and DB will be hidden

and have no function in the system. The auto-tuning and bumpless

transfer functions will be disabled as well.

Heat only P (or PD) control:

Select REVR for OUT1, set TI to

0. OFST is used to adjust the control offset (manual reset). 

O1HY is hidden

if PB is not equal to 0. 

Control Outputs

Heat only ON-OFF control

: Select REVR for OUT1. Set PB

(proportional band) to 0. O1HY is used to adjust dead band for

ON-OFF control. The output 1 hysteresis (O1HY) is enabled

in case PB=0. The heat only on-off control function is shown

in the following diagram:

OFST function:

OFST is measured by % with a range of 0–

100.0%. In the steady state (i.e., process has been stabilized), if

the process value is lower than the set point by a definite value,

say 5°C, while 20°C is used for PB, that is lower by 25%, then

increase  OFST  25%,  and  vice-versa. After  adjusting  OFST

value, the process value will be varied and eventually coincide

with set point.

Refer to section 3-12 “manual tuning” for the adjustment of PB

and TD. Manual reset (adjust OFST) is not practical because the

load may change from time to time and OFST may need to be

adjusted repeatedly. PID control can avoid this situation.

Heat only PID control:

If REVR is selected for OUT1, PB and

TI should not be zero. Perform auto-tuning for the new process,

or set PB, TI, and TD with historical values. See section 3-11

for auto-tuning operation. If the control result is still unsatisfac-

tory, then use manual tuning to improve control. See section 3-

12 for manual tuning. The unit contains a very advanced PID

and Fuzzy Logic algorithm to create a very small overshoot and

very quick response to the process if it is properly tuned.

Cool only control:

ON-OFF control, P (PD) control, and PID

control can be used for cool control. Set OUT1 to DIRT (direct

action). The other functions for cool only ON-OFF control, cool

only P (PD) control, and cool only PID control are the same as

for heat only control except that the output variable (and action)

for cool control is inverse to heat control.

NOTE:

ON-OFF control may result in excessive overshoot and

undershoot problems in the process. P (or PD) control will result

in a deviation of process value from the set point. It is recom-

mended to use PID control for heat-cool control to produce a stable

and zero offset process value.

Note:

When the ramp function is used, the lower display will show

the current ramping value. The ramping value is an artificially de-

termined setpoint created and updated by the control to match the

ramp rate set by the user. However, it will revert to show the set

point value as soon as the up or down key is touched for adjust-

ment. The ramping value is initiated to process value either on

power-up or when RR and/or the set point are changed. Setting

RR to zero means no ramp function.

Ramp

The ramping function is performed during power up as well as any

time the set point is changed. If MINR or HRR is chosen for

RAMP, the unit will perform the ramping function. The ramp rate

is programmed by adjusting RR. The ramping function is disabled

as soon as failure mode, manual control mode, auto-tuning mode

or calibration mode is entered.

Example without dwell timer

Select MINR for RAMP, select °C for UNIT, select 1-DP for DP,

set RR=10.0. SV is set to 200°C initially, and changed to 100°C

30 minutes after power-up. The starting temperature is 30°C. After

power-up, the process runs like the curve shown below:

Figure 3.5  RAMP Function

Содержание PCM10001

Страница 1: ...oller 2 On Off Switch 3 1 Amp Control Fuse 4 20 Amp Main Fuse 240V model has 2 5 120V or 240V Power Cord 20A 6 120V or 240V Heater Receptacle 20A 7 Type J or K Thermocouple Jack WARNINGS 1 Dangerous v...

Страница 2: ...2 of the TEC 9100 which can be used as a cut out in the event of an over setpoint temperature condition This is a deviation contact set to 30 F above the setpoint In the event of an over setpoint tem...

Страница 3: ...Page 3 of 10 1 5 Menu Overview...

Страница 4: ...Page 4 of 10 Parameter Descriptions TEC 9100 Temperature Controller Controller Parameter Descriptions that are not applicable are not shown in the above table...

Страница 5: ...dvanced PID and Fuzzy Logic algorithm to create a very small overshoot and very quick response to the process if it is properly tuned Cool only control ON OFF control P PD control and PID control can...

Страница 6: ...2 will perform the fail ure transfer function as the controller enters failure mode Output 1 failure transfer if activated will perform 1 If output 1 is configured as proportional control PB 0 and BP...

Страница 7: ...lure mode or manual control mode is entered Procedures Auto tuning can be applied either as the process is warming up cold start or when the process has been in a steady state warm start After the aut...

Страница 8: ...Page 8 of 10 Table A 1 Error Codes and Corrective Actions...

Страница 9: ...ty does not apply to damage resulting from transporta tion alteration misuse or abuse RETURNS No product returns can be accepted without a completed Return Material Authorization RMA form TECHNICAL SU...

Страница 10: ...ce the Advantages of our Diverse and Innovative Products Copyright 2015 All Rights Reserved Electric Heating Elements Thermocouples and RTD Assemblies SCR Power Controls Solid State Relays Mechanical...

Отзывы: