• 4 digit backlit LCD display digital timer
• 24 programmable timing modes
• 0-9999sec or 0-9999min time ranges
• 24 to 240Vac/dc powered
• 1 changeover and 1 N/O relay output
• Easy to programme through front keys
• Status and timing indicators
• EEPROM memory (minimum 10 years)
• IP20 enclosure code
• DIN rail mounting
• 2 module 36mm width
• Clear hinged tamperproof cover
ENVIRONMENTAL CONDITIONS
Operating/Storage Temperature:
-5ºC to +45ºC / -10ºC to +55ºC
Protection Class:
IP20
Installation Height:
Maximum 2000m
Do not use this timer in locations where corrosive or flammable gases could be present.
ELECTRICAL
Power Supply Voltage:
24 to 240Vac/dc
Power Consumption (Burden):
<3VA
Frequency
50/60Hz
Wiring:
2mm² screw type terminals
Data Retention:
EEPROM (minimum 10 years)
CE Markings:
EN 60947-5-1:2004+A1:2009, EN 60730-1:2012,
EN 60730-2-7:2011+AC:2012, EN 61000-6-2:2005,
EN 61000-6-4:2007+A1:2011, EN 61000-3-2:2014, EN 61000-3-3:2013
OUTPUTS
Relay Outputs (R1 & R2):
R1: Single pole changeover contact 8A rated at 240Vac (resistive load)
Single pole changeover contact 8A rated at 240Vac (resistive load)
R2: Single pole N/O contact 8A rated at 240Vac (resistive load)
Single pole N/O contact 8A rated at 240Vac (resistive load)
Relay Contact Life:
Mechanical 1,000,000 operations
Electrical 100,000 operations
Reset Time:
100ms approx.
Accuracy:
±3sec/24hours
HOUSING
Housing Type:
DIN rail mounting 2 module width
Display:
Backlit LCD display
Dimensions:
36mm wide x 90mm high x 65mm deep
Weight:
Approximately 140g (without packaging)
Enclosure Materials:
Self extinguishing plastics
TECHNICAL SPECIFICATION
Page 2
WIRING CONNECTIONS
S
16
25 28 A1 A2
(-)
~
24-240Vac/dc
Supply
(+)
~
15
18
R1
R2
~ (+)
(START)